3. Results and Discussion
The experimental work [
15] for measuring the non-uniform circumferential distributions of wall temperature and heat transfer coefficient for a HCT is adopted to assess the present CFD methodology.
Figure 1 shows the schematics of HCT for the present simulations. The right portion of this figure represents the circumferential angle (
φ) on the HCT wall. The corresponding mesh distributions on the cross-section of HCT are indicated in
Figure 2. Based on the requirements of the CFD Best Practice Guidelines [
14], the structured grids should be adopted near the wall and mesh independent calculations should be performed. The sensitivity simulations for the various mesh are applied on the cross-section of HCT, including 860 (Coarse), 1,425 (Standard), and 3525 (Fine) cells, respectively. The corresponding values of y+ for these three mesh models are 28.9~36.2 (Coarse), 0.8~1.2 (Standard), and 0.6~1.1 (Fine). Uniform girds are adopted along the HCT with the interval of 10
o helical coil. The constant heat flux is set at the tube wall; the inlet mass flux and temperature are set at the tube inlet; the pressure is set at the tube outlet. The simulation conditions for all the case are listed in
Table 2.
Figure 3 compares the predicted results for the circumferential distributions of wall temperature at x = -0.147 under the coarse, standard, and fine mesh. The conditions of Case 1 in
Table 2 and the SSTKW turbulence model are adopted. In this figure, the abscissa represents the circumferential angle (
φ) of HCT. Similar to the location index using the quality (x) in the measured data presentation of Wang et al., [
15], x is also adopted as the location index of HCT. As illustrated in the upper portion of
Figure 3,
φ = 90
o and 270
o are the tube wall on the outer and inner sides, respectively, of HCT. This figure implies that the predicted result of circumferential temperature distribution using the standard mesh is close to that from the fine mesh.
Since the BPGs provides useful guidelines for the single-phase applications of CFD to nuclear reactor safety (NRS) problems [
14], these guidelines should be followed to ensure accuracy and credibility of CFD predictions. The essential requirements for the BPGs are applied in the mesh model, the physical models, especially the turbulence model, and the model validation. Therefore, in addition to the mesh model, the sensitivity calculations of turbulence models are also conducted, including the SKE, RKE, and SSTKW. The blind calculations using different turbulence models are clearly revealed in
Figure 4 and the simulation conditions are the same as those in
Figure 3. As shown in this figure, the predicted results of circumferential wall-temperature distribution at x = -0.147 using both the SSTKW and the RKE are similar. Both the SSTKW and RKE turbulence models provide superior performance for flow characteristics with adverse pressure gradient, recirculation, and separation, which are similar to the flow characteristics in a HCT. The SSTKW is less sensitive to the inlet turbulence properties and less restriction for the near-wall mesh model. Therefore, the SSTKW turbulence model and the standard mesh are adopted to be assessed in the followings (
Figure 5,
Figure 6 and
Figure 7) with the experimental data and then applied in the extended discussion in the thermal-hydraulic characteristics in a HCT with confidence.
Figure 5 compares the circumferential distributions of wall temperature at x = -0.147 (
L = 2.07 m) and -0.236 (
L = 0.57 m), respectively, predicted by the present CFD model (red dots) with those from the measurements (blue dots) for Case 1. It can be clearly seen in this figure that the predicted distributions agree well with the measured ones at these two locations. Both the measured and predicted results also show the strong non-uniform circumferential distribution of wall temperature for the HCT. As the aforementioned descriptions, the thermal-hydraulic characteristics in a HCT are governed by the centrifugal force and the gravitational force. The lower-temperature water with the higher density would be push to the outer portion of HCT due to the centrifugal force and tends to accumulate on the lower portion of tube due to the gravitational force. As shown in
Figure 6 (a), the higher-density water is located near the outer and right-bottom portion of HCT (
φ ~ 135
o). In addition, the lower density water with the higher-temperature water can be found near
φ = 315
o. These predicted density distributions can provide the obvious images to explain the inhomogeneity distribution of circumferential wall temperature, which cannot be revealed in the measured results.
As the mass flux in the HCT decreases (i.e. Case 2), the thermal-hydraulic characteristics are governed by the gravitational force more than the centrifugal force. The lower-temperature water with the higher density is accumulated in the lower portion of HCT than that for the Case 1. This difference can be found in the density contours for both cases, as clearly revealed in the comparison of Figures 6 (a) and (b).
Figure 7 (a) shows the circumferential distributions of wall temperature at x = -0.167 (
L = 1.49 m) and -0.219 (
L = 0.74 m), respectively, obtained from the CFD simulations (red dots) and the test data (blue dots) for Case 2. As revealed in this figure, the lower wall temperature is located near
φ = 180
o and the higher wall temperature appears near
φ = 360
o. Both the measured and predicted results show this trend. In contrast to the Case 2 with the lower mass flux, the inlet mass flux increases enough (i.e. Case 3) so that the gravitational effect can be neglected as shown in
Figure 7 (b) that is the circumferential distributions of wall temperature at x = -0.108 (
L = 4.76 m) and -0.197 (
L=2.15 m), respectively, for Case 3. Therefore, The peak wall temperature then is predicted to occur at
φ = 270
o. The thermal-hydraulic characteristics for Case 3 are symmetric along the horizontal line on the cross-section for a vertical HCT, as clearly shown in the density contour of
Figure 6 (c). In addition, the predicted values for the circumferential distributions of wall temperature also correspond well with the measured ones, as clearly seen in both plots of
Figure 7.
The Lu number represents the ratio of centrifugal force and buoyancy and can be written as
This non-dimensional number can characterize the flow and heat transfer patterns for the HCT. The Lu number increases with the increasing mass flux in a HCT, which also enhances the influence of centrifugal force, and vice versa. Therefore, three simulation cases with the Lu number of 1.226, 0.12, and 13.7 are selected in the present work, which characterizes the middle (centrifugal force balanced by buoyancy force), low (buoyancy force dominated), and high (centrifugal force dominated) Lu number, respectively. Figures 8 (a) and 9 (a) show the distribution patterns of temperature on the cross-section of HCT for Case 1 and Case 2. Combined observation of density and temperature contours in
Figure 6 (a) and
Figure 8 (a) reveals that the higher heat transfer region with the lower-density and higher-temperature water is located near the upper left corner and the lower heat transfer one with the higher-density and lower-temperature water is near the lower-right corner. These predicted results can provided the clear images of two-region flow and heat transfer characteristics. This two-region heat transfer pattern is also confirmed in the experimental work of Wang et al. [
15]. They suggested the schematic of two-region heat transfer patterns with the higher heat transfer region in the upper-left corner and the lower heat transfer one in the lower-right corner, as indicated in
Figure 8 (b). The predicted heat transfer flow pattern from the present CFD results and the schematic one from the work [
15] for Case 2 are also revealed in Figures 9 (a) and (b) , respectively.
The vector distributions of secondary flow on the cross-section of HCT are also plotted on Figures 8 (a) and 9 (a). As clearly shown in these plots, a vortex-pair of secondary flow is shown on these cross-sections of HCT and the higher wall temperature occurs where the secondary flow leaves away. In addition,
Figure 8 (a) indicates that the higher wall temperature may appear between
φ =270
o and 315
o. However, the circumferential distribution of measured temperatures is presented in the discrete pattern on the selected locations only. Based on the measured data of Case 1, the peak wall temperature at x = -0.147 occurs at
φ = 270
o. However, as shown in
Figure 8 (c), the peak wall temperature is located at
φ ~ 308
o. The exact location of peak wall temperature can be captured only in the CFD results and cannot be revealed in the experimental data, which is one of the main contributions for the CFD simulations. Similar result for Case 2 is also shown in
Figure 9 (c). The peak wall temperature at x = -0.167 is measured at
φ = 0
o (i.e. 360
o), while the peak wall temperature may be actually at
φ ~ 342
o, based on the predicted result. Therefore, in addition to matching the measured data, the calculated results from the present CFD model then can help interpret the test results and expand their application.
Figure 10 compares the circumferentially averaged heat transfer coefficients in different regions, which are obtained from the measurements and the predictions for Case 2 and Case 3, respectively. As shown in
Figure 10 (a) of Case 2 with Lu < 0.25, two regions with the different averaged heat transfer along the HCT circumferential wall is suggested from the work [
15], including
φ = 270
o - 45
o (i.e regions A, B, G, H) and 90
o -225
o (i.e. regions C, D, E, F). The definition of A-H regions is illustrated in the right portion of this plot. The former region (i.e regions A, B, G, H) is the lower heat transfer region where the higher temperature water with the lower density occurs and the latter region is the higher heat transfer one. It can be clearly revealed in
Figure 10 (a) that the circumferentially averaged heat transfer coefficients over the regions A, B, G, H, the regions C, D, E, F, and the overall circumferential wall (i.e. defined Avg. in the
Figure 10 (a)) predicted by the present CFD model correspond well with those from the experiment. The non-uniform distribution for the wall heat transfer coefficients can be also shown in both the measurements and predictions.
The quantity correspondence between the measured and predicted heat transfer coefficient at the different regions as well as its average value is also shown in
Figure 10 (b) for Case 3. Three regions with different heat transfer characteristics are only suggested based on the measured data, but these characteristics have been clearly seen in the present predicted results in the density contour of
Figure 6 (c). In addition, the predicted heat transfer coefficients shown in plots (a) and (b) of
Figure 10 are the fully-developed one. The heat transfer coefficient would decrease from the inlet of HCT and approaches to the fully-developed value, as clearly revealed in
Figure 10 (c) for Case 3. In this plot, the longitudinal axis is the normalized heat transfer coefficient (
hnorm) that is the local
h divided by the fully-developed one. The abscissa axis is the distance from the inlet of HCT. Detailed observation of this plot implies that the entrance length (developing length) is about 42 ~ 50 pipe diameter (
d). The correlation for the entrance length for a HCT has been proposed by Saffari et al. [
19]) and is expressed as the function of Reynolds number (Re), Dean number (
De), and curvature ration (
δ).
Using the conditions of Case 3, the entrance length calculated using this correlation is 51.24 that is close to the present predicted range.
In addition, the thermal-hydraulic characteristic would reach the fully-developed condition as the flow passes over the coil angle (
ψ) of 210
o ~ 275
o based on the coil/tube diameter values, implying that the entrance effect may be neglected for evaluating the overall heat transfer characteristics for a whole HCT or HCTHX. Then, the fully-developed correlations of heat transfer coefficient can be applied to estimate the heat transfer capability for a HCT or HCTHX.
Figure 11 compares the fully-developed heat transfer coefficient for a HCT obtained from the present CFD model, the appropriate correlations, and experiment for Case 2 (a) and Case 3 (b). These correlations include those proposed by Rogers and Mayhew [
20], Mikaila & Poskas [
21], Xin & Ebadian [
22], Guo et al. [
23], Hardik et al. [
24], and El-Genk & Schriener [
25] since Gou et al. [
23] had suggested that these correlations are suitable for predicting the heat transfer coefficient for a HCT. Similar to the comparison in
Figure 10, the agreement between the predicted
h and the measured one is also shown in this figure under different flow conditions. In addition, the calculated
h from the Xin & Ebadian’s correlation [
22] matches with the data better than that from others for Case 2 and the
h calculated using the correlation of Rogers & Mayhew [
20] or Mikaila & Poskas [
21] shows more agreement with the data for Case 3. Therefore, these comparison results strong imply that applicability of various kinds of
h-correlation for the HCTs depends on their flow conditions, which reveals that the contribution of CFD simulation in this area.
The inhomogeneity of circumferential distributions for single-phase heat transfer characteristics for a vertically helical-coiled tube are clearly shown in
Figure 5,
Figure 6,
Figure 7,
Figure 8,
Figure 9 and
Figure 10, which is essentially caused by the constant-heat-flux boundary condition. This boundary condition for CFD simulations is not suitable to investigate the flow and heat transfer behaviors within the HCTHX, as described in the work of Bahrehmand and Abbassi [
26]. The higher wall temperature occurs near the region with inferior heat transfer under the condition of constant
. However, the heat transfer mechanism for a HCT heat exchange is mainly belong to the conjugated heat transfer from the hot fluid in the shell side to the cold fluid in the tube side. The wall heat flux would decrease around the location with the poor heat transfer capability within the tube side, suppressing this higher-wall-temperature phenomenon. Therefore, the conjugated heat transfer effect by including the shell-side solution domain is simulated herein in order to investigate the effect of conjugated heat transfer on the non-uniform characteristics of HCT wall in the HCTHX.
Figure 12 compares the circumferential dependence of normalized temperature predicted using the constant-heat flux BC and the conjugated heat transfer simulation, respectively. The normalized temperature shown on the longitudinal axis is the local wall temperature divided by the average wall temperature. The simulation conditions under the constant-heat-flux cases in Figures 12 (a) and (b) are similar to those for Cases 1 and 3. The inlet mass flux/temperature and pressure of tube side for the conjugated-heat-transfer cases are the same as those for the constant-heat-flux ones. For the conjugated-heat-transfer cases, the mass flowrate in the shell side is set to be 0.2 kg/s. The temperature drops for the shell side in Figures 12 (a) and (b) are set to be 35.6 and 58.1
oC, respectively, so that the heat transfer rate from the shell side to the tube is similar to that set in the constant-heat-flux cases. It can be clearly shown in
Figure 12 that the non-uniform circumferential distribution of heat transfer is essentially caused by the constant-heat-flux boundary condition on the HCT wall. This characteristic can be significantly reduced by actually considering the heat transfer from the shell side.