Submitted:
12 December 2024
Posted:
14 December 2024
You are already at the latest version
Abstract
Keywords:
1. Introduction
- Determine the dependence of the zero-sequence voltage and currents taking into account the transverse conductivities of the lines in normal mode and during ground faults;
- Determine the characteristics of the ground overcurrent relays during changing the characteristics of the zero-sequence circuit.
- Develop a scheme and algorithm for identifying and protecting the network during ground faults through the transient resistance, and also determine the protection settings for operation.
2. Determination of Dependence of Zero-Sequence Voltage and Current Considering Lines Conductivity in Normal Mode and During Ground Faults
- − 6-35 kV busbar section with outgoing lines;
- − circuit breakers (Q1, Q2, Qn) of outgoing lines (Line 1, Line 2, Line n) and zero-sequence current transformers (CBCT 1, CBCT 2, CBCT n);
- − centralized ground fault protection unit, signals to which come from each zero sequence current transformer installed on each line;
- − voltage transformer (VT), necessary for measuring zero-sequence voltage U0 and line voltage UL.
- − transient resistance Rf at the ground fault location.
- − a ground fault occurs through the active transient resistance Rf (with bolted GF Rf = 0);
- − the system of electromotive forces (EMF) of the power source is symmetrical.
3. Determination of Characteristics of the Ground Overcurrent Relays During Changing of the Characteristics of the Zero-Sequence Circuit
4. Development of an Algorithm and Device for Detecting a Damaged Line During a Ground Fault
5. Experiments on the “Physical Model of 6-35 kV Networks” Test Bench
6. Conclusions
- The first chapter provides an analysis and types of neutral grounding modes used in Kazakhstan, as well as methods of ground fault protection. The types of neutral grounding for which a method for identifying a faulty line in the event of a ground fault being developed are selected. The dependencies of the zero-sequence voltage and currents are determined considering conductivities of the lines in the normal mode and during a ground fault.
- The second chapter defines the characteristics of the ground fault protection when changing characteristics of the zero-sequence circuit takes place and calculations of the settings are provided.
- The third chapter describes the development of an algorithm and a device for detecting a faulty line during a ground fault.
- Calculation of settings and simulation of transient processes during ground faults.
- Experiments on the test bench of the physical model of 6–35 kV networks.
- -
- presence of a load in the network does not affect phasor diagrams;
- -
- in normal network operation, charging currents of the same magnitude flow through the wires, shifted by 120 electrical degrees relative to each other;
- -
- the phasor of the ground fault current in the faulty feeder lags the phasors of the capacitive currents by 180° degrees, which means that the phase angles of the undamaged feeders are equal by magnitude and angle;
- -
- the phasor of a ground fault in the faulty feeder lags the phasor of the zero-sequence voltage in the open-delta windings of the instrument transformer by 90 degrees.
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Acknowledgments
Conflicts of Interest
References
- Chelaznov, A. A. Methodological guidelines for selecting the neutral grounding mode in 6-10 kV networks of Gazprom OJSC enterprises. 2006.
- Ilyinykh, M.V.; Sarin, L.I. Integrated approach to selection of means of overvoltage limitation in 6, 10 kV networks of large industrial enterprises of pulp and paper and metallurgical industries. Proceedings of the Fourth All-Russian scientific and technical conference, Novosibirsk, 2006, p.55-62.
- Evdokunin, G. A. Selection of the method of neutral grounding in 6-10 kV networks. Electricity, 1998, 12, 8-23.
- Ilyinykh, M. Compensated and combined grounded neutral. Electrical Engineering News, 2016, 5(101), 16-26.
- Yemelyanov, N. I. Current issues of application of resistive and combined neutral grounding in 6-35 kV electrical networks, Energoexpert, 2010, 2, 44-50.
- Weinstein, P. A. Neutral grounding modes in electrical systems: a tutorial. TPU Publishing House, 2006, 118.
- Khalilova, F. A. Characteristics of arc-suppressing reactors used to compensate for capacitive fault currents. Fergana, Uzbekistan, 2019.
- Shirkovets, A. Resistive grounding of neutral in 6-35 kV networks with XLPE cables. Electrical Engineering News, 2008.
- Titenkov, S. S.; Pugachev, A. A. Neutral grounding modes in 6–35 kV networks and organization of relay protection against single-phase ground faults. Energy Expert, 2010, 2.
- Fedoseyev, A. M. Relay protection of electrical systems: textbook for universities. Energy, 1976, 560.
- Kostrov, M. F. Fundamentals of Relay Protection Engineering: A Textbook. Gosenergoizdat, 1944, 436, 37.
- Andreev, V. A. Relay protection and automation of power supply systems: a tutorial. Higher School, 1991, 496.
- Andreev, V. A. Relay protection, automation and telemetry in power supply systems: textbook for universities. Vysshaya shkola, 1975, 375.
- Lin, X.; Ke, S.; Gao, Y.; Wang, B.; Liu, P. A selective single phase-to-ground fault protection for neutral ineffectively grounded systems. IJEPES, 2011, 33, 1012–1017.
- Henriksen, T. Faulty feeder identification in high impedance grounded network using charge-voltage relationship. Electr. Power Syst. Res., 2011, 81, 1832–1839. [CrossRef]
- Huang, S. J.; Wan, H.H. A Method to enhance ground-fault computation. IEEE Trans. Power Syst., 2010, 25, 1190–1191. [CrossRef]
- Lin, W. M.; Ou, T. C. Unbalanced distribution network fault analysis with hybrid compensation. IET Gen. Transmiss. Distrib,. 2011, 5, 92–100. [CrossRef]
- Ou, T. C. A novel unsymmetrical faults analysis for microgrid distribution systems. Int. J. Electr. Power Energy Syst., 2012, 43, 1017–1024. [CrossRef]
- Ou, T. C. Ground fault current analysis with a direct building algorithm for microgrid distribution. Int. J. Electr. Power Energy Syst., 2013, 53, 867–875. [CrossRef]
- Andreev, A. A. Analysis of existing types of protection against single-phase ground faults and conditions of their application. Bulletin of Samara State Technical University, 2021, 29(4), 56-70.
- Shabad, M.A. Protection against single-phase ground faults in 6-35 kV networks: a tutorial. Energetik, 2007, 63.
- Shirkovets, A.I.; Telegin A.V. Problems of ground faults in medium voltage networks of European and American countries. Relay Protection and Automation, 2012, 3(08).
- Manilov, A.; Barna, A. OZZ in 6-10 kV networks with combined neutral grounding. Method of ensuring protection sensitivity. Electrical Engineering News, 2012, 6(78).
- Ukil, A.; Deck, B.; Shah, V. Smart distribution protection using current-only directional overcurrent relay. In Proceedings of the IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT Europe), Gothenburg, Sweden, 11–13 October 2010; p. 1–7.
- Stojanovic, A. N; Djuric, M. B An algorithm for directional earth-fault relay with no voltage inputs. Electr. Power Syst. Res., 2013, 96, 144–149.
- Bukhtoyarov, V. F. Protection against ground faults of electrical installations in quarries: a tutorial. Nedra, 1986, 184.
- Hanninen, S. Single phase earth faults in high impedance grounded networks. Seppo Hanninen, 2001, 143.
- Patent of the Russian Federation No. 2578123. Device for protecting medium-voltage electrical networks from single-phase ground faults.
- Sapunkov, M. L. Analysis of the influence of transient resistance on the performance of current protection against ground faults. Electric power engineering through the eyes of youth, 2013, 2, 65-69.
- Bychin, M. A. Development and justification of algorithms for protection against single-phase earth faults in networks with resistively grounded neutral: dis. for the degree of candidate of technical sciences: 05.09.03, Bychin Maksim Anatolyevich - St. Petersburg, 2010, 160.
- Shabad, M. A. Calculations of relay protection and automation of distribution networks: monograph. PEIPK, 2003, 350.
- Khabarov, I. A. Development and study of characteristics of protection against single-phase earth faults in 6-35 kV networks with resistive grounding of the neutral: dis. for the degree of candidate of technical sciences 05.14.02, Khabarov Andrey Mikhailovich - Novosibirsk, 2006, 232.
- Shabad, M. A. Protection against single-phase ground faults in 6-35 kV networks: a tutorial. Energetik, 2007, 63.
























| Mode | Normal mode | K1 (at the beginning of the line) Feeder 2 |
K2 (at the beginning of the line) Feeder 3 |
K3 (at the end of the line with transient resistance) Feeder 3 |
|
|---|---|---|---|---|---|
|
Incomer |
2.1 | 1.4 | 1.4 | 0.69 | |
| +20° | +60° | +57 | +65 | ||
| 2.1 | 1.4 | 1.5 | 1.2 | ||
| -103° | -3° | -5 | -33 | ||
| 2.0 | 2.3 | 2.3 | 1.36 | ||
| +136° | -155° | -155 | +177 | ||
| 0 | 0 | 0 | 0 | ||
| 0 | 0 | 0 | 0 | ||
| 0 | 38.9 | 39.1 | 18.6 | ||
| 0 | +125° | +125° | +68° | ||
|
Feeder 1 |
0.2 | 0.33 | 0.33 | 0.19 | |
| +93° | +66° | +65° | +70 | ||
| 0.2 | 0.34 | 0.34 | 0.28 | ||
| -28° | +5° | +5° | -25 | ||
| 0.2 | 0 | 0 | 0.19 | ||
| -145° | 0 | 0 | -115 | ||
| 0 | 0.58 | 0.58 | 0.28 | ||
| 0 | +35° | +35° | -25 | ||
|
Feeder 2 |
0.3 | 0.53 | 0.53 | 0.26 | |
| +90° | +65° | +65° | +67 | ||
| 0.3 | 0.56 | 0.55 | 0.45 | ||
| -28° | +5° | +5° | -25 | ||
| 0.33 | 2.3 | 0 | 0.3 | ||
| -147° | -155° | 0 | -115 | ||
| 0 | 1.5 | 0.94 | 0.44 | ||
| 0 | -156° | +32° | -30 | ||
|
Feeder 3 |
2 | 0.66 | 0.68 | 0.33 | |
| +11° | +64° | +61° | +65° | ||
| 2 | 0.68 | 0.68 | 0.56 | ||
| -112° | +2° | +2° | -30° | ||
| 1.9 | 0 | 2.3 | 1.2 | ||
| +125° | 0 | -157° | +160° | ||
| 0 | 1.2 | 1.3 | 0.62 | ||
| 0 | +30° | -157° | +145° |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).