Most solar air heater ducts collect sunlight through a single flat absorber on top. A rhombus-shaped duct stood on one of its corners exposes two sloping faces to the sky instead, so one face can catch the low morning sun and the other the evening sun. This paper reviews the computational study of Dara et al., which varied the interior angle of such a duct from 40° to 140° in 10° steps. They used RNG k–ε simulations at Reynolds numbers of 5000–28,000, with unequal heat fluxes on the two faces to represent morning, noon, and evening sun. The 90° duct, which is a square turned on its corner, performed best. At Re = 28,000 it gave 17.24% more heat transfer and 7.3% more friction than the 40° duct, and the authors report an overall performance factor 20.6% higher. The air temperature rise was almost independent of angle and increased by about 60% from morning to noon. We add a geometric and energy-balance analysis of our own. It shows that the hydraulic diameter, the mass flow, and the heated area follow directly from the side length and the angle, and that angles θ and 180° − θ give the same cross-section rotated by 90°. It also shows that the 60% daily rise is exactly the ratio of total incident flux. Two reported figures, the 20.6% performance gain and the 1.85-fold advantage over a flat-mounted square duct, cannot be reproduced from the paper’s own data and need clarification. A simple sun-path estimate confirms that two faces catch about 1.6 times the daily beam energy of a flat duct of the same side, though much of that comes from the wider footprint.
Keywords:
CFD
; hydraulic diameter
; interior angle
; Nusselt number
; rhombus duct
; solar air heater
; thermohydraulic performance
I. Introduction
A solar air heater (SAH) is a duct with a dark plate on top. Sunlight warms the plate, and air blown through the duct carries the heat away. SAHs are simple, cheap, and free of the freezing and corrosion problems of water collectors, so they are used widely for drying and space heating. They do share one weakness, however: air is a poor heat-transfer fluid, so the plate runs hot and loses energy instead of passing it to the air. Researchers have attacked this in two main ways. One is to roughen the absorber with ribs, dimples, or protrusions that disturb the slow layer of air next to the wall [1,2,3,4,5]. The other is to change the shape of the duct itself, using triangular, trapezoidal, or semicircular sections [6,7,8,9].
Duct shape matters for a second reason that is easy to overlook. A flat absorber facing upward receives the most sunlight near solar noon, when the rays strike it almost head-on. In the morning and evening, the rays arrive at a low angle and the plate intercepts much less energy [10]. A duct with two sloping absorber faces can do better, because one face points east and the other west. Dara and Muvvala had earlier tested rhombus ducts with rounded corners and ribs [11], and before that trapezoidal ducts with varying base angles [12,13]. In their latest study, Dara et al. kept the rhombus sharp-cornered and changed only its interior angle, to find the best shape for a duct mounted on its corner [14].
This paper reviews that study and adds a set of simple, independent checks. Our contributions are:
- A geometric description of the rhombus family, showing how hydraulic diameter, flow area, and corner sharpness depend on the interior angle.
- A one-line energy balance that predicts the air temperature rise for each heating case and explains why it is independent of the interior angle.
- A consistency check of the reported performance figures, with two points that need clarification.
II. Duct Geometry and Heating Cases
A. The Rhombus Family
All ducts in the study have the same 50 mm side length a [14]. Only the interior angle θ at the top corner changes, from 40° to 140°. The two upper faces are the absorbers, and the two lower faces are insulated (Figure 1). For a rhombus of side a, the flow area is A = a2 sin θ and the wetted perimeter is 4a, so the hydraulic diameter is
This simple result has three consequences that frame the whole study. First, Dh peaks at 50 mm for θ = 90° and falls to 32.1 mm at 40° and 140° (Figure 2). Second, a rhombus with angle θ has the same shape as one with 180° − θ, simply rotated by a quarter turn. The 40° and 140° ducts are therefore the same tube, heated on different pairs of faces. Third, the sharpest corner in the section is min(θ, 180° − θ), which is 90° for the square and drops to 40° at both ends of the range.
B. Daily Heating Cases
To mimic the sun’s path, the two absorbers were given unequal heat fluxes [14]. In the morning case, the east face receives more radiation than the west face. At noon, both faces receive the same flux, and the total is largest. The evening case mirrors the morning one. Combinations such as 1000 + 0, 1000 + 200, and 800 + 800 W/m2 were used, with the inlet air at 300 K and 100 kPa. All other walls were treated as adiabatic, and losses by radiation and outward convection were ignored.
III. Numerical Model and Validation
The three-dimensional ducts were solved in ANSYS Fluent as steady, incompressible, turbulent flow with constant air properties [14]. Second-order upwind discretization and the SIMPLE pressure–velocity coupling were used. The near-wall mesh was refined to keep y+ ≤ 2, and inlet turbulence intensity was set from I = 0.16 Re−1/8. A hybrid mesh of about 479,000 cells was chosen after a grid study showed that further refinement changed the average Nusselt number by less than 0.1%. The study used a 0.45 m entry length, a 1.00 m test length, and a 0.35 m exit length, in line with ASHRAE Standard 93 [15].
Five two-equation turbulence models were compared against the Dittus–Boelter and modified Blasius correlations,
The RNG k–ε model [16] matched them best, to within ±6% for Nu and ±5.8% for f. Against an in-house test rig, a flat-mounted square duct heated electrically from the top, and against the data of Alam et al. [17], the deviations were ±4.5% and ±5.2% [14]. The validation thus covers the 90° geometry only, heated on one face. As the authors note, the other angles and the two-face heating were not tested experimentally.
The performance measures are defined in the usual way. The Reynolds number and friction factor are
and the overall performance factor is λ = j/f1/3, where j = Nu/(Re Pr1/3) is the Colburn factor [18].
IV. Reported Results
A. Effect of Interior Angle
At every Reynolds number, the average Nusselt number rose as θ increased from 40° to 90° and fell again from 90° to 140° [14]. At Re = 28,000, the 90° duct gave 17.24% more heat transfer than the 40° duct. The friction factor followed the same up-and-down pattern, with the 90° duct 7.3% higher than the 40° duct at Re = 28,000. The authors attribute the trend to the change in hydraulic diameter, which in turn changes the air velocity at a fixed Re. Based on λ, the 90° duct came out on top, with a value reported to be 20.6% above that of the 40° duct.
B. Effect of Daily Heating
Changing the heat-flux split between the two faces barely affected Nu or f. Variations were within 2%, which is expected because the air properties were held constant. Changing θ also barely affected the air temperature rise ΔTbulk, with variations within ±2% [14]. The daily heating pattern, however, made a large difference. From morning to noon, ΔTbulk rose by 56.8–62.9% across the angles and Reynolds numbers studied (Figure 4), and it fell again in the evening. Finally, the vertex-mounted 90° duct was compared with an identical square duct lying on its base with a single top absorber. The rhombus arrangement was reported to give about 1.85 times the temperature rise at noon, with no change in pumping power.
V. Independent Checks
A. Mass Flow and Temperature Rise
Because the perimeter 4a is the same for every duct, fixing Re also fixes the mass flow. Substituting U = ṁ/(ρA) and (1) into (3) gives
Here qtot is the sum of the two face fluxes and L is the heated length. Neither expression contains θ. This is the real reason why the temperature rise does not depend on the interior angle: every duct receives the same heat through the same face area and passes the same mass of air. It is a consequence of the energy balance, not of the flow pattern. With a = 0.05 m, ṁ ranges from 4.6 g/s at Re = 5000 to 25.9 g/s at Re = 28,000. Taking L = 1.0 m, (4) gives ΔTbulk ≈ 17 K at Re = 5000 and 3 K at Re = 28,000 for the 800 + 800 W/m2 case (Figure 3).
The same relation explains the daily pattern. If the morning case totals 1000 W/m2 and the noon case 1600 W/m2, then ΔTbulk must rise by 1600/1000 − 1 = 60%. The reported values cluster tightly around this figure (Figure 4). The spread of ±3 percentage points is about what one would expect from small differences in how the outlet temperature is averaged. The daily gain is therefore a direct result of collecting more total radiation, as the authors argue, and it does not depend on the duct angle.
B. Why the Square Does Best
The reported explanation for the Nu trend is that a larger Dh lowers the velocity at fixed Re and so lengthens the contact time. This needs care. At a fixed Re, a circular-tube correlation such as (2) predicts the same Nu whatever the diameter, so a change in Dh alone cannot raise Nu. A more physical reason is corner shape. In a narrow corner, the flow is slow and the heated wall is poorly cooled, which pulls down the average Nusselt number. Laminar results for rhombic ducts show the same effect clearly [19]. The square, with no corner sharper than 90°, avoids these dead zones. As Figure 2 shows, the sharpest corner follows exactly the same rise-and-fall with θ as the reported Nu and f. It is worth adding that real turbulent flow in corners also drives weak secondary vortices [20]. Linear eddy-viscosity models such as RNG k–ε cannot reproduce these, so corner effects in narrow ducts may be somewhat misjudged.
Because θ and 180° − θ give the same tube, any difference between, say, the 40° and 140° results comes only from which pair of faces is heated. In the 40° duct, the heated faces meet at the sharp top corner. In the 140° duct, the heated faces meet at an obtuse corner, and the sharp corners lie at the sides where heated and unheated faces meet. Separating these two cases in future work would show how much of the angle effect is due to heating position rather than to shape.
C. How Much Sunlight Do the Two Faces Really Catch?
The simulations used fixed flux pairs such as 800 + 800 W/m2 at noon against 1000 W/m2 on a flat plate. To check whether these are realistic, we estimated the direct-beam radiation on each face over an equinox day at latitude 15.8° N, close to where the study was done. The duct axis was taken as running north–south, so that one face looks east and the other west. Each upper face is tilted at β = 90° − θ/2 from horizontal, and clear-sky direct irradiance was taken from the Meinel air-mass model [10]. Diffuse light was ignored. Figure 5 shows the result for θ = 90°, and Table II summarizes the daily totals.
Three findings stand out. First, the two-face idea works. Over the day, the 90° duct catches about 1.58 times the beam energy of a flat square of the same side, and the east face does most of the work before about 10 a.m. Second, the assumed noon fluxes are somewhat optimistic. A 45° face receives only about cos 45° ≈ 0.71 of the horizontal value at noon, so the realistic noon pair is about 640 + 640 W/m2 rather than 800 + 800 when the flat plate gets 1000. Third, much of the gain comes simply from size. A convex duct intercepts sunlight in proportion to its width as seen from the sun, and the corner-mounted square is 1.41 times wider than a flat one. Per unit of roof width, its daily advantage shrinks to about 1.12. Flat rhombi such as 140° catch the most energy per duct, but almost all of that is footprint. These figures do not change the ranking of angles by heat transfer, but they matter when the duct is sized for a given roof area.
D. Consistency of Reported Figures
Table I compares several headline numbers with what the paper’s own data imply. Two of them cannot be reconciled.
Performance factor. Since λ ∝ Nu/f1/3 at fixed Re and Pr, the reported ratios at Re = 28,000 give 1.1724/1.0731/3 = 1.145, a 14.5% gain. A 20.6% gain would need either a larger Nu ratio or a lower friction ratio at some other Re. Since 17.24% is described as the maximum Nu gain and the 90° duct always has the higher friction, the bound on the λ gain is 17.2%. The 20.6% figure is therefore inconsistent with the stated maxima.
Comparison with the flat square. At equal Re, both square ducts have the same side and the same mass flow, and all walls except the absorbers are adiabatic. By (4), the ratio of their temperature rises must equal the ratio of absorbed heat, 1600/1000 = 1.6. The reported 1.85 implies either a different heat input for the flat duct (about 865 W/m2), a different heated length or flow, or a different averaging method. The qualitative conclusion stands, since two faces do collect more heat than one (Section V-C), but the size of the gain should be restated as about 1.6 under the stated conditions.
VI. Discussion and Outlook
The study’s central message, that a corner-mounted duct collects more sunlight over the day, is sound and practically useful. Our checks show that this gain comes from optics and the energy balance, not from the internal flow. Any duct with two sloping absorbers would show it, and the choice of angle then rests on heat transfer and friction, where the square wins. Two further points deserve attention. First, in a real collector the two faces would not receive the fixed fluxes used here. The incidence angle on each face depends on latitude, season, and tilt [10], so a sun-path model would give more realistic daily totals. Second, as Section V-C shows, part of the gain is simply a wider collector, and the duct presents more glazed and exposed surface, so top heat losses, which were neglected, may cut into the gain. Outdoor tests of the 90° duct, experiments at other angles, and simulations that include radiation and external losses would make the case complete. Adding ribs or dimples to both faces, as the authors suggest, is a natural next step [11].
VII. Conclusion
Turning a rhombus-section duct onto its corner gives a solar air heater two absorber faces that share the daily sun. Simulations of eleven interior angles show that the square case, θ = 90°, gives the highest Nusselt number and the best balance of heat transfer and friction, at the cost of slightly more friction than narrow rhombi. Our analysis shows that the hydraulic diameter equals a sin θ, that θ and 180° − θ are the same duct rotated, and that the mass flow and air temperature rise at a given Re do not depend on θ at all. The roughly 60% morning-to-noon temperature gain is exactly the ratio of total incident flux. The advantage of the square comes mainly from its lack of sharp corners. The reported 20.6% performance gain and 1.85-fold temperature advantage are not consistent with the paper’s own data. Our estimates are about 14.5% and 1.6-fold respectively, and the original figures should be confirmed. When ducts are compared per unit of roof width rather than per duct, the two-face advantage is smaller, about 12% for the square.
References
- Karwa, R. Experimental studies of augmented heat transfer and friction in asymmetrically heated rectangular ducts with ribs on the heated wall in transverse, inclined, V-continuous and V-discrete pattern. Int. Commun. Heat Mass Transf. 2003, vol. 30, 241–250. [Google Scholar] [CrossRef]
- Skullong, S.; Kwankaomeng, S.; Thianpong, C.; Promvonge, P. Thermal performance of turbulent flow in a solar air heater channel with rib-groove turbulators. Int. Commun. Heat Mass Transf. 2014, vol. 50, 34–43. [Google Scholar] [CrossRef]
- Gawande, V. B.; Dhoble, A. S.; Zodpe, D. B.; Chamoli, S. Experimental and CFD-based thermal performance prediction of solar air heater provided with right-angle triangular rib as artificial roughness. J. Braz. Soc. Mech. Sci. Eng. 2016, vol. 38, 551–579. [Google Scholar] [CrossRef]
- Pandey, N. K.; Bajpai, V. K. Experimental investigation of heat transfer and friction characteristics of arc-shaped roughness elements having central gaps on the absorber plate of solar air heater. J. Sol. Energy Eng. 2016, vol. 138, art. no. 041005. [Google Scholar] [CrossRef]
- Gupta, D.; Varshney, L. Performance prediction for solar air heater having rectangular sectioned tapered rib roughness using CFD. Therm. Sci. Eng. Prog. 2017, vol. 4, 122–132. [Google Scholar] [CrossRef]
- Kumar, R.; Khurana, S.; Kumar, A.; Goel, V. Effect of dimple intrusions and curvature radius of rounded corner triangular duct on fluid flow and heat transfer. J. Therm. Sci. Eng. Appl. 2019, vol. 11, art. no. 031001. [Google Scholar] [CrossRef]
- Kumar, R.; Kumar, A. Computational fluid dynamics based study for analyzing heat transfer and friction factor in semi-circular rib-roughened equilateral triangular duct. Int. J. Numer. Methods Heat Fluid Flow 2017, vol. 27, 941–957. [Google Scholar] [CrossRef]
- Jain, S. K.; Agrawal, G. D.; Misra, R.; Verma, P.; Rathore, S.; Jamuwa, D. Performance investigation of a triangular solar air heater duct having broken inclined roughness using computational fluid dynamics. J. Sol. Energy Eng. 2019, vol. 141, art. no. 061008. [Google Scholar] [CrossRef]
- Misra, R.; Singh, J.; Jain, S. K.; Faujdar, S.; Agrawal, M.; Mishra, A.; Goyal, P. K. Prediction of behavior of triangular solar air heater duct using V-down rib with multiple gaps and turbulence promoters as artificial roughness: A CFD analysis. Int. J. Heat Mass Transf. 2020, vol. 162, art. no. 120376. [Google Scholar] [CrossRef]
- Duffie, J. A.; Beckman, W. A. Solar Engineering of Thermal Processes, 4th ed.; Wiley: Hoboken, NJ, USA, 2013. [Google Scholar]
- Dara, R.; Muvvala, P. An experimental and computational investigation on fluid flow and thermal performance of a rhombus passage solar air heater of various configurations. Arab. J. Sci. Eng. 2024, vol. 49, 10839–10857. [Google Scholar] [CrossRef]
- Dara, R.; Muvvala, P. Effect of base angle of an isosceles trapezoidal solar air heater duct on flow and thermal characteristics—A numerical investigation. J. Sol. Energy Eng. 2023, vol. 145, art. no. 041008. [Google Scholar] [CrossRef]
- Dara, R.; Muvvala, P. Effect of the base angle of an isosceles obtuse-angled trapezoidal duct of a solar air heater on fluid flow and thermal characteristics—An experimental and computational investigation. J. Mech. Sci. Technol. 2024, vol. 38, 3801–3815. [Google Scholar] [CrossRef]
- Dara, R.; Muvvala, P.; Konda Reddy, B. Thermo-hydraulic analysis of rhombus-shaped solar air heater ducts with varying interior angles. Proc. Inst. Mech. Eng. E J. Process Mech. Eng. 2025, 1–13. [Google Scholar] [CrossRef]
- ANSI/ASHRAE Standard 93-1986; Methods of Testing to Determine the Thermal Performance of Solar Collectors. Atlanta, GA, USA, 1986.
- Patel, D.; Sheth, K. Penrose-tiled rhombus solar panels: A novel approach for optimizing rooftop utilization and aesthetic integration [Preprint]; TechRxiv, 2026. [Google Scholar]
- Alam, T.; Saini, R. P.; Saini, J. S. Experimental investigation on heat transfer enhancement due to V-shaped perforated blocks in a rectangular duct of solar air heater. Energy Convers. Manag. 2014, vol. 81, 374–383. [Google Scholar] [CrossRef]
- Manglik, R. M. “Heat transfer enhancement,” in Heat Transfer Handbook; Bejan, A., Kraus, A. D., Eds.; Wiley: Hoboken, NJ, USA, 2003; pp. 1029–1130. [Google Scholar]
- Shah, R. K.; London, A. L. Laminar Flow Forced Convection in Ducts; Academic Press: New York, NY, USA, 1978. [Google Scholar]
- Sheth, K.; Patel, D.; Disa, R. Rhombus-shaped solar panel . U.S. Patent and Trademark Office, 2026. Available online: https://patents.google.com/patent/USD1126137S1/en.
Figure 1.
Cross-sections of vertex-mounted rhombus ducts with (a) θ = 40°, (b) θ = 90°, (c) θ = 140°, and (d) a conventional square duct on its base. Heated absorber faces are shown in red (drawn for this paper).
Figure 1.
Cross-sections of vertex-mounted rhombus ducts with (a) θ = 40°, (b) θ = 90°, (c) θ = 140°, and (d) a conventional square duct on its base. Heated absorber faces are shown in red (drawn for this paper).

Figure 2.
Hydraulic diameter from (1) and sharpest corner angle versus interior angle for a = 50 mm (computed in this work).
Figure 2.
Hydraulic diameter from (1) and sharpest corner angle versus interior angle for a = 50 mm (computed in this work).

Figure 3.
Air temperature rise estimated from (4) for three heat-flux combinations, with a = 50 mm and a heated length of 1.0 m (computed in this work).
Figure 3.
Air temperature rise estimated from (4) for three heat-flux combinations, with a = 50 mm and a heated length of 1.0 m (computed in this work).

Figure 4.
Reported rise in air temperature from morning to noon [14] compared with the ratio of total heat input (computed in this work).
Figure 4.
Reported rise in air temperature from morning to noon [14] compared with the ratio of total heat input (computed in this work).

Figure 5.
Estimated clear-sky beam irradiance on the east and west faces of the θ = 90° duct and on the top of a flat square duct, equinox, 15.8° N (computed in this work).
Figure 5.
Estimated clear-sky beam irradiance on the east and west faces of the θ = 90° duct and on the top of a flat square duct, equinox, 15.8° N (computed in this work).

Table II.
Daily Beam Energy Relative to a Flat Square Duct.
| θ | β | Footprint width / a | Two faces / flat top | |
| 40° | 70° | 0.68 | 1.16 | |
| 60° | 60° | 1.00 | 1.34 | |
| 90° | 45° | 1.41 | 1.58 | |
| 120° | 30° | 1.73 | 1.79 | |
| 140° | 20° | 1.88 | 1.90 |
Computed in this work: equinox, 15.8° N, beam radiation only, same side length a for all ducts.
Table I.
Reported Values and Independent Checks.
| Quantity | Reported [14] | Check (this work) |
| ṁ independent of θ | Yes | Yes: ṁ = Re μ a from (4) |
| ΔTbulk independent of θ | ±2% | Exact from (4) |
| Morning → noon ΔT rise | 56.8–62.9% | 60% = 1600/1000 − 1 |
| λ, 90° vs 40° | +20.6% | +14.5% from 1.1724/1.0731/3 |
| ΔT, rhombus vs flat square | 1.85× | 1.60× = 1600/1000 |
| Pumping power, same θ | Equal | Equal: same Re, ṁ, Δp |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |