A Decision-Support Framework for the Management of Water Distribution Networks by Integrating SCADA Data, Measurement Uncertainty and EPANET Hydraulic Modelling

Submitted:

24 November 2026

Posted:

25 November 2026

You are already at the latest version

Abstract
Water utilities increasingly operate SCADA systems reporting network state in real time, yet data is not the same as enough: a measurement adequate for one decision may be useless for another. As a proof of concept, we develop a decision-support framework linking measurement, uncertainty evaluation, hydraulic modelling and the decision in one chain, demonstrated on two tasks: loss detection and judging whether a network can absorb a new demand. On a laboratory rig, flow through orifices of 2.07, 3.12 and 4.07 mm measured diameter was measured as the difference of two in-line readings. A conservative worst-case combination of the meter accuracy limits yields a loss-uncertainty band falling from ±48–55% at 2.07 mm to ±13–15% at 4.07 mm, so detectability depends less on the instrument than on the ratio between loss and transit flow. The discharge coefficient, recomputed with the measured diameters and upstream head, settles at 0.64–0.68 and serves only as a physical bridge to EPANET, not a precise metrological figure. In a demonstrative DMA, a ±20% change in the loss shifts the admissible new-demand limit by only ±0.14 L/s, the decision changing only within a thin band around the threshold. The central proposal is an adequacy test: precision is sufficient whenever propagating its uncertainty leaves the decision classification unchanged, letting the framework judge a decision's robustness and whether extra instrumentation would help.
Keywords: 
;  ;  ;  ;  ;  ;  ;  ;  ;  

1. Introduction

Cutting real water losses and assessing a network’s spare capacity for new connections are two problems operators face continually. The goals differ, but both rely on the same information: flow and pressure readings, knowledge of the network state, and hydraulic models that turn these into actionable estimates.
SCADA has greatly increased how much data operators hold, yet more data does not automatically mean data fit for every diagnostic or decision. The difficulty is sharpest when the quantity one really cares about is not measured directly but inferred as the difference between two far larger readings. Therefore, the uncertainty of the result can rival the very signal being sought, even when each instrument performs perfectly well on its own.
Local leaks in pipes are described, in their simplest form, by Torricelli’s orifice flow equation [1,2]:
Q = C d · A · 2 · g · h
where Q is the flow lost through the orifice, Cd – the discharge coefficient, A – the equivalent orifice area, g – the gravitational acceleration, and h – the pressure at the orifice. In network models, the same relationship usually appears as a power law, Q = C · h N 1 , with an exponent N1 near 0.5 for a rigid opening. This is the correct rigid-orifice baseline, even if the FAVAD (fixed and variable area discharges) literature bounds departures from it at 0.5-1.5 for a single deforming leak, depending on the leak area that grows with head [3]. Finite-element analyses of cracks and holes show crack area increasing with pressure, with a slope that depends on pipe material and dimensions [4]. The literature is therefore clear, Cd and pressure–flow exponent N1 are not fixed: they shift with the geometry of the defect, the orifice-to-pipe ratio and the flow regime [1,2,5,6,7]. Also, experimental studies measured leak flow gravimetrically or volumetrically rather than by subtracting two meters [2,6]. They generally report meter and gauge precision without formal propagation of uncertainty to Cd [6,8]. Thus, for an operator, the point is not to pin down a local discharge coefficient to the last digit, but to adopt a physically sound representation and — above all — to know how much the measurement uncertainty bears on the answer that matters.
Coupling SCADA data with EPANET-type models is nowadays a routine practice for calibration, simulation, state estimation and network diagnosis [9,10,11,12,13,14,15], and existing models are likewise used to weigh system extensions [16]. What we pursue here is therefore not the SCADA–EPANET pairing itself, but the explicit thread running from measurement quality, through the detectability of the phenomenon and the passage of uncertainty across the model, to the robustness of the operational decision.
The literature is deep on each link (SCADA Data, Measurement Uncertainty, and EPANET Hydraulic Modelling) taken separately, but thin at their intersection. Therefore, the decision-support framework for the management of water distribution networks follows the sequence Measurement → Information → Prediction → Decision. Its central premise is that, for certain decisions, the instrumentation already in place can be enough even when the relative uncertainty is large — provided that carrying that uncertainty through the model does not change the verdict against the decision threshold. Therefore, four research questions/problems follow:
-
(RQ1) under what conditions a loss is distinguishable from the instrument uncertainty?
-
(RQ2) how can experimental information on water loss be transferred into an EPANET model without introducing a false precision?
-
(RQ3) can measurement uncertainty change a connection decision?
-
(RQ4) when is the existing instrumentation enough for the decision and when extra measurement information becomes justified?.

2. Conceptual Decision-Support Framework

The framework begins from a simple stance: a measurement is only as good as the task it serves. An estimate carrying a large relative uncertainty may still suffice for a given decision, as long as the interval left after propagating that uncertainty stays wholly on one side of the acceptance threshold.
The method runs through seven steps: acquiring SCADA data; evaluating the uncertainty; establishing the detectability of the loss; parameterizing and calibrating the EPANET model; simulating the hydraulic scenarios; propagating the uncertainty; and comparing the outcome with the decision threshold. The outcome is reported not as a single number but as a band of responses.
For a decision variable P — say the minimum pressure at a critical node — let P* be the acceptance threshold and [Pmin, Pmax] the interval that uncertainty propagation leaves behind. Three states follow:
Pmin > P* → ROBUSTLY ACCEPTABLE;
Pmax < P* → ROBUSTLY UNACCEPTABLE;
Pmin < P* < Pmax → UNDETERMINED.
This third state is where the framework earns its keep. Rather than forcing an accept-or-reject verdict, it tells apart the cases where the data already decide the matter from those where cutting uncertainty would actually be worth the effort. Two kinds of answers emerge together: hydraulic (is the scenario acceptable?), and informational (are data and instrumentation enough to stand behind the decision?).
Figure 1. Architecture of the framework: Measurement → Information → Prediction → Decision.
Figure 1. Architecture of the framework: Measurement → Information → Prediction → Decision.
Preprints 246096 g001

3. Materials and Methods

3.1. Experimental Rig and Instrumentation

The tests were run on a steel pipe of 35.6 mm internal diameter, drilled with circular orifices of 2, 3 and 4 mm nominal diameter. The diameters actually measured — 2.07, 3.12 and 4.07 mm — were the ones used in every area and discharge-coefficient calculation. Each orifice was driven at several inlet flows across six pressure stages.
Pressure was read by two ifm PT5404 transducers (0–10 bar) and flow by two ifm SM7020 magneto-inductive meters (0.1–75 L/min). Following the specification used in the computation, a single meter’s error is approximated by e(Q) = 0.008·Q + 0.15 L/min. The transit flow during the tests stayed in the 40–65 L/min range. The head driving the orifice flow was taken as the upstream pressure P1, measured on the orifice axis.
Figure 2. Layout of the experimental rig and position of the instruments (two flow meters in series, two pressure taps).
Figure 2. Layout of the experimental rig and position of the instruments (two flow meters in series, two pressure taps).
Preprints 246096 g002

3.2. Estimation of the Loss Flow and its Uncertainty

The flow discharged through the orifice was determined as the difference between the two in-line flow measurements:
QRL = Q1 − Q2
Both meters read the transit flow, whereas the quantity we are after is the far smaller gap between the two readings. To keep the instruments’ repeatability from being mistaken for the accuracy of this computed difference, the uncertainty was propagated explicitly. The two limits were added as e1 + e2 to form a conservative maximum/minimum (worst-case) bound, intentionally more conservative than a root-sum-square combination and not presented as a standard uncertainty in the GUM sense [29,30]. Three scenarios were used:
Q RL max = Q RL + e 1 + e 2 ;   Q RL med = Q RL ;   Q RL min = Q RL − e 1 + e 2 ;  
Across the tested transit flows, the resulting absolute band is about ±0.93–1.32 L/min, but what this means in relative terms hinges on how large the loss is. At the 2.07 mm orifice, where QRL is only some 1.7–2.7 L/min, the relative uncertainty runs to ±48–55%; at 3.12 mm it eases to roughly ±20–24%, and at 4.07 mm to about ±13–15%. The lesson is plain: the accuracy of a figure obtained by subtracting two readings cannot be read off from the accuracy of either reading alone.

3.3. The Discharge Coefficient and its Role in the Model

The experimental discharge coefficient was computed from the relation:
C d exp = Q RL A · 2 · g · P 1
Recomputed with the measured diameters and the upstream pressure P1, the central values come out near 0.64 for the 2.07 mm orifice, 0.68 for 3.12 mm and 0.65 for 4.07 mm — the same order of magnitude as values reported for orifices and local losses [17,18,19,20]. Because the flow behind them is itself an uncertain difference, we do not treat Cd as a precise metrological result or as grounds for a universal correlation. Its job here is narrower: to check that the experiment is physically coherent and to tie the observed loss to its counterpart in the hydraulic model.
In EPANET, a local loss is written as an emitter — a pressure-dependent nodal discharge, q = CE·Pγ, in which q is the flow leaving the node, P – the nodal pressure, CE – the emitter coefficient attached to that node, and γ represents a global pressure exponent. For leaks through orifices in rigid pipes, one takes γ = 0.5, which collapses the expression to the familiar Torricelli form; setting the two flow expressions equal at the same pressure gives C E = C d · A · 2 · g , so the nodal coefficient simply gathers the orifice area, the discharge coefficient and 2 · g   into one number. A base demand is held pressure-independent in a demand-driven run, but an emitter is not: it ties the outflow to the computed pressure, which is exactly why it suits a leak. In the network, CE is never fixed from the laboratory alone — it is calibrated until the model reproduces the loss inferred from field data.
To bring the rig conditions into EPANET, the experimental model was set up with the recorded flows and pressures. The pipe segment analyzed is 34, and point H marks the section holding the orifice. The 18 measurement sets were each simulated, and the CE values were obtained from relation (5).
Figure 3. EPANET model of the experimental rig.
Figure 3. EPANET model of the experimental rig.
Preprints 246096 g003
For an orifice in rigid pipes, the relation can be written:
q = CE∙P0.5
where q is the flow leaving the node, P the pressure head, and CE the coefficient of the loss element. Calibration proceeds in two steps. First, the experimental Cd is carried into the model through the relation above, giving an initial CE grounded in the rig behavior. That value is then tuned so that the total simulated loss matches the loss read from the field — for instance from the minimum-night-flow balance. The two steps play distinct, complementary parts: the experiment fixes the shape of the representation (the P0.5 dependence) and the starting coefficient, while calibration on real data sets the final loss level.

3.4. The Detectability Threshold

For the two-meter arrangement, the uncertainty band on the computed loss follows from the instruments’ accuracy specification. One meter’s error is e(Q) = 0.008·Q + 0.15 L/min (0.8% of the reading plus 0.2% of the 75 L/min full scale). Since QRL = Q1 − Q2 comes from two independent readings, combining the errors deterministically (eq. 3) yields ΔQRL = ±(e1 + e2). Because the loss is far smaller than the transit flow (Q1 ≈ Q2 ≈ Q), the band is well approximated by:
ΔQRL = ±(0.016·Q + 0.30) L/min
Two parts separate out cleanly. The fixed term, near 0.30 L/min, is twice the full-scale component (0.15 L/min per meter) and sets a floor on the band that the size of the loss cannot lower. The variable term, 0.016·Q, is twice the reading percentage and grows with the transit flow. Detectability, in short, is a property of the loss, the transit flow and the instrumentation together — not of the loss on its own.
In the field, three moves bring a loss more clearly above this threshold: working in the minimum-night-flow window; sizing the DMA so the boundary transit flow is small next to the loss of interest; or watching the change over time with the same meter, which lets part of the systematic error cancel. None of these calls for new sensors — they simply get more out of the instrumentation already installed.
Figure 4 puts this on a graph. Panel (a) traces the uncertainty band on the loss, ΔQRL = ±(e1 + e2), against the transit flow Q: the solid blue line is the full term (0.016·Q + 0.30), and the dashed red line is the irreducible floor of 0.30 L/min set by the two instruments. Two operating points are marked for one and the same 2 L/min loss. By day, with a high transit of about 50 L/min, the band reaches roughly ±1.10 L/min — some ±55% in relative terms; at the critical flow (≈ MNF, extrapolated), with transit down near 10 L/min, it drops to about ±0.46 L/min, or ±23%. The same loss, in other words, is far easier to see at low transit even though neither the loss nor the meters have changed. Panel (b) sets the relative uncertainty for that 2 L/min loss against four ways of operating: (A) an instantaneous daytime balance with two meters (≈ ±55%); (B) a nighttime balance with two meters (≈ ±20%); (C) a single-fed DMA at night (≈ ±19%); and (D) tracking the minimum-night-flow change with one meter over time (≈ ±11%, falling to ≈ ±3–4% once averaged over several nights). One caveat matter: only the daytime point (≈ 50 L/min) lies inside the range actually measured on the rig (40–65 L/min, shaded grey). The 10 L/min point and modes B–D (marked with *) were not reproduced experimentally; they are estimates from relation (6) and from operating assumptions (night analysis, a single feed, and averaging over several nights). The extrapolation is fair because relation (6) comes straight from the meter’s accuracy specification, which holds over the whole 0.1–75 L/min range, rather than from a fit confined to 40–65 L/min. The panel thus shows how the uncertainty model behaves as transit falls, not measurements taken in that regime.

3.5. Demonstrative DMA Case and the Decision Rule

To walk the full measurement–model–decision chain from end to end, we built a synthetic DMA in EPANET — a source, six demand nodes, a branched layout, and distributed losses represented by pressure-dependent nodal discharges. It is a demonstrator, not a validation on a real network.
The computation runs as follows: find the minimum night flow (MNF); split off the legitimate night consumption from the estimated loss; calibrate the total loss coefficient so the model reproduces the night balance; add a new demand at the critical node, stepping it up; simulate the peak regime; compare the minimum pressure with a service threshold; and carry the loss uncertainty through to the decision. The 20 m threshold used here is only illustrative; a real case would use the operator’s figure or the governing regulation.
Put formally, the available precision is adequate when the whole band [Pmin, Pmax] falls on one side of P*. If the band straddle the threshold, the decision is marked undetermined, and cutting the uncertainty is worth doing only if it clears that ambiguity.

4. Results

4.1. Discharge Coefficient and Experimental Detectability

Across the three diameters, the central discharge coefficient barely moves — it stays near 0.64–0.68 (Table 1, Figure 4). This lies inside the classical band of about 0.61-0.67 quoted for sharp-edged circular openings and within the 0.60-0.85; 0.59-0.86; 0.60-0.80, respectively, ranges reported for holes in pipes [2,21,22]. It is close to 0.643 measured for a steel pipe with a 1.5 mm wall; a thinner 0.5 mm wall gave 0.734 when computed with an enlarged area [23]. For our purposes, though, the telling quantity is the relative uncertainty. At fixed transit-flow, a larger orifice and so a larger loss flow, drives that uncertainty steadily down: about ±48–55% at 2.07 mm, ±20–24% at 3.12 mm and ±13–15% at 4.07 mm. The laboratory literature avoided this problem by weighing the discharged water [6,7]. The subtraction of two in-line readings used here is the dominant uncertainty source, and no peer-reviewed treatment of leak flow has been obtained this way.
Table 1. Experimental data, Cd and conservative worst-case bands for the three diameters (P1 + measured diameters; three-scenario band).
Table 1. Experimental data, Cd and conservative worst-case bands for the three diameters (P1 + measured diameters; three-scenario band).
Stage
(Q1)
P1
(mH2O)
QRL
(L/min)
Conservative band
±(e1+e2)
Cd
min
Cd
mean
Cd
max
Rel.
d = 2.07 mm (measured) · Cd mean ≈ 0.64 · band ±48–55%
40 8.63 1.68 ±0.93 0.288 0.640 0.993 ±55%
45 10.96 1.92 ±1.01 0.308 0.647 0.987 ±52%
50 13.53 2.07 ±1.08 0.301 0.630 0.959 ±52%
55 16.32 2.30 ±1.16 0.315 0.636 0.957 ±50%
60 19.58 2.53 ±1.24 0.326 0.640 0.953 ±49%
65 22.85 2.74 ±1.32 0.332 0.641 0.949 ±48%
d = 3.12 mm (measured) · Cd mean ≈ 0.68 · band ±20–24%
40 7.75 3.81 ±0.91 0.512 0.673 0.834 ±24%
45 9.79 4.32 ±0.99 0.525 0.680 0.835 ±23%
50 12.00 4.80 ±1.06 0.531 0.682 0.832 ±22%
55 14.60 5.27 ±1.14 0.532 0.678 0.825 ±22%
60 17.37 5.78 ±1.21 0.540 0.683 0.826 ±21%
65 20.27 6.33 ±1.29 0.551 0.692 0.833 ±20%
d = 4.07 mm (measured) · Cd mean ≈ 0.65 · band ±13–15%
40 6.92 5.91 ±0.90 0.551 0.649 0.748 ±15%
45 8.66 6.71 ±0.97 0.564 0.659 0.754 ±14%
50 10.81 7.33 ±1.04 0.553 0.645 0.737 ±14%
55 13.10 8.13 ±1.12 0.560 0.650 0.739 ±14%
60 15.50 8.97 ±1.19 0.571 0.659 0.746 ±13%
65 17.99 9.70 ±1.26 0.576 0.661 0.747 ±13%
Table 1. The CE values from the 18 simulations. CE are computed consistently as Q RL / P 1 from the measured loss flow and upstream head; the column labels use the measured orifice diameters, not nominal ones.
Table 1. The CE values from the 18 simulations. CE are computed consistently as Q RL / P 1 from the measured loss flow and upstream head; the column labels use the measured orifice diameters, not nominal ones.
Q1 [L/min] d = 2.07 mm d = 3.12 mm d = 4.07 mm
40 0.572 1.369 2.247
45 0.580 1.381 2.280
50 0.563 1.386 2.229
55 0.569 1.379 2.246
60 0.572 1.387 2.278
65 0.573 1.406 2.287
Experimentally, detectability is thus governed by how the loss compares with the transit flow, not by the meter’s nominal precision alone. One and the same measurement setup can fail to reveal a small daytime loss yet be perfectly adequate for a larger loss, or for the same loss read at night.
For this reason, a critical transit flow was defined as the friendliest operating point to loss diagnosis, where the transit flow is at its lowest, and the loss forms the largest share of what the boundary meter sees. The rig did not reach this regime (its tests ran at 40–65 L/min); it is obtained from the detectability relation (eq. 6). In a real, hydraulically delimited metering zone, it coincides with the minimum night flow (MNF), when legitimate consumption is least, and the 10 L/min point in Figure 4 stands for this critical regime. This is the same reasoning that underlies MNF analysis in practice [24], with one qualification from the literature: at night the limiting term often becomes the estimate of legitimate consumption rather than the meter [24,25,26]
Figure 5. Cd and relative uncertainty for the three diameters (P1 + measured diameters; three-scenario band).
Figure 5. Cd and relative uncertainty for the three diameters (P1 + measured diameters; three-scenario band).
Preprints 246096 g005

4.2. Relevance of the Operating Point

The results make clear that “SCADA precision” is not a single number. How much the data can tell you depends on the transit flow, the size of the loss, the fixed error term, the averaging time, the number of instruments and their stability. For a 2 L/min loss, an instantaneous balance at about 50 L/min of transit gives a relative uncertainty of order ±55%. Lowering the transit at night brings it down, and following the change with the same meter trims the systematic error further. Taken together, this argues for the minimum night flow as the natural operating point for screening and diagnosis. Therefore, the design of the measurement procedure can count for as much as upgrading to a higher metrological class of instrument.
It is useful to set eq. (6) against metering errors reported for DMAs. The band ±(0.016-Q + 0.30) L/min corresponds to about 2.2% of a 50 L/min transit flow and about 4.6% of a 10 L/min transit flow (our arithmetic on eq. 6). It is a worst-case sum for two meters of the stated specification.
That is the same order as the ±2% quoted for electromagnetic meters above 0.4 m/s [24] and as the below-2% error on estimated daily DMA consumption obtained by smart-metering about 60% of users [27]. It is smaller than the roughly 9% relative error at 90% confidence reported on daily supplied volume in a Barcelona case, where sensor error was estimated from the sensors’ own time series rather than from manufacturer specifications [28]. Two caveats follow. The deterministic el + e2 combination is conservative. For independent errors, the GUM prescribes quadrature [29,30], which for two equal errors gives about 71% of the interval sum (standard algebra, not a water-sector result). The scenarios in Figure 6 are therefore a bounding case. The second caveat concerns the lower-uncertainty modes. The approx. ±11% for the same-meter tracking (D), and the ±3-4% after several nights, rest on two assumptions: a common gain error cancels at first order, and random error averages down roughly as 1 / N . Neither bias nor drift averages out in this way. In the existing literature, the multi-period narrowing of intervals reported in [28] concerns random error only, with systematic error excluded by annual calibration, and no water-sector paper quantifying systematic error cancellation for change detection was found. Mode D therefore remains a methodological estimate, as flagged in Figure 6, and should be tested on field data. Finally, MNF-based loss is the night inflow minus legitimate night consumption, so any error in the latter transfers one-for-one into the loss [24,25]. This sets a floor on detectable loss that is independent of the sensors.
Published detectability limits are expressed differently from eq. (6). Probabilistic and sensitivity-matrix studies obtain a smallest detectable leak per network location for a given measurement set-up [31,32]. Interval state estimation sets thresholds so that no alarm is raised inside the uncertainty envelope [33]. Eq. (6) is the corresponding single-zone, two meter limit, and shares with those methods the property that the minimum detectable leak scales with the width of the uncertainty interval. A localization study makes the same point at network scale: it detects only leaks whose hydraulic impact exceeds sensor error [34].

4.3. Transfer to the Hydraulic Model

The measured Cd values are coherent enough to justify representing the loss as a pressure-dependent nodal discharge. The central result, however, is not a fixed Cd dropped into the network, but a loss calibrated against field data. The experimental parameterization supplies the physics (the P0.5form and a starting coefficient CE), while the night balance and observed pressures settle the final calibration. Keeping these apart heads off a false sense of precision: a Cd quoted to many decimals cannot compensate for the uncertainty of a loss inferred indirectly or for the absence of representative field data. The same logic applies to the CEtable (computed as Q RL / P 1 with the measured diameters), whose near-constant values within each diameter confirm the model reproduces the Torricelli relation and say nothing about the accuracy of the underlying loss.
On the exponent, the rig supports γ=0.5 for a rigid steel pipe, and the literature points the same way for rigid walls: a steel leak in a 1.5 mm wall gave an exponent of 0.5192 [23]. Read from the end points of Table 1, the loss flow rises with P1 at an effective exponent of about 0.5 for each diameter (our indicative calculation: 0.50, 0.53 and 0.52, with no fit and no uncertainty propagation, so it should not be reported as a fitted exponent). The article does not state the wall thickness of the rig, which matters because the same study found 0.6116 and a higher Cd for a 0.5 mm wall [6]. The exponent should not be carried unchecked to field networks. A single deforming leak lies between 0.5 and 1.5 [35], values above that arise from aggregation, leaks opening from a closed state or data artefacts, and zone-scale fits are fragile [5,20]. The practical consequence for EPANET is that a global γ lumps area growth into CE. Calibrating CE at night pressure and then simulating the lower peak pressure assumes the same exponent applies across both. A larger true exponent would make the loss fall faster as pressure drops, so the 0.5 assumption would tend to overstate peak-regime loss and understate the remaining pressure. Quantified errors from the power equation are of order 20% in total leakage [36], comparable to the ±20% loss encountered in the present study. Nevertheless, no source of quantifying their effect on detectability thresholds was found; it is therefore recommended a sensitivity run over γ of 0.5 – 1.5 alongside the loss sweep, or the use of a modified-orifice formulation where available [36,37]. Also, the EPANET manual itself distinguishes emitters from the pressure-dependent demand analysis [38], and where capacity near the threshold is at issue the choice of smooth pressure-driven formulation affects pressure mainly in the low-pressure [39].

4.4. Connection Assessment and the Decision-Switching Zone

In the present case, the minimum night flow was 3.94 L/s, of which 1.44 L/s is legitimate night use and 2.50 L/s is loss. With the loss calibrated, a new demand was added at the critical node and raised step by step. Against the illustrative 20 m threshold, +5 L/s leaves the minimum pressure near 22.1 m, while +9 L/s pulls it down to about 17.1 m; the hydraulic limit works out at roughly 6.8 L/s. The 20 m threshold is illustrative and sits mid-range among reported criteria: above the 7 m (England and Wales guaranteed standard) and 14.1 m (USA) floors, near the 22 m Australian criterion, below the 24 m and 25 m criteria of South Africa and New Zealand [40]. A threshold at one of those other values would move the switching window. A lower one, such as 14.1 m, lies below the 17.1 m reached at +9 L/s and would need new runs beyond the simulated demand range.
Varying the loss by ±20% shifts that limit by only about ±0.14 L/s. The uncertainty band crosses the threshold only for demands lying roughly between 6.65 and 6.94 L/s, a window about 4% wide relative to the grantable limit; in pressure terms it corresponds to a margin of some 0.18 m from the threshold (Figure 6). A ±20% swing on the 2.50 L/s loss is ±0.50 L/s. Because night loss is the inflow minus legitimate night consumption, that swing also stands in for error in the 1.44 L/s consumption estimate [24,25,26]. The 6.8 L/s figure belongs to this synthetic DMA and should not be read as general. What matters is the mechanism: a sizeable relative uncertainty in the loss scarcely affects the decision when the system sits well clear of the threshold, while close to it even a small uncertainty may tip the balance. The finding that large loss uncertainty can leave a threshold decision untouched is consistent with, but is not shown by, the sensitivity literature. Demand and decay coefficients dominated pressure predictions in a six-network Monte Carlo study [41], and calibration uncertainty changed expansion-design cost in [42]. No paper testing whether leakage-level uncertainty flips a capacity or new connection decision was found, so the present case remains a synthetic demonstration, not corroboration.

5. Discussion

The results show why an estimate’s precision must be separated from its adequacy for a decision. Metrologically, less uncertainty is always welcome. Within a decision-support framework, a reduction is worth something only to the extent that it can change, sharpen, or confirm the decision.
The shift is from “how precisely do we know the loss?” to “can the loss uncertainty change the decision?”. In the worked case, a ±20% swing in the loss matters for diagnosis yet barely moves the connection capacity across most of the range; only near the threshold does a finer estimate — or the explicit propagation of other uncertainties — become necessary.
What this paper offers is not the separate use of SCADA, EPANET, MNF or pressure-dependent loss elements, which are already well established [9,10,11,12,13,14,15,16,25,34,38,43,44]. Nor is it a new account of leak hydraulics, for which the FAVAD literature is the reference [19,35]. Digital-twin reviews likewise report that data and interoperability limits, and the lack of native bidirectional EPANET coupling, are recurrent barriers [45]. The contribution is the thread tying these together through one information-adequacy criterion: the measurement refers to detectability, the loss enters the model with its uncertainty attached, and that uncertainty is followed all the way to the decision threshold. The three-state verdict is compatible with robustness thinking in water planning, where info-gap and robust decision-making ask whether a requirement is met across an uncertainty set [46]. It also resonates with the argument that probability-of-failure measures are hard to apply when distributions are poorly known, favoring interval reporting [46]. No prior use of the “undetermined” state was found in the water-distribution literature, so it is presented as an adaptation, not an established category.
The same framework points toward the value-of-information question. If the decision band already sits entirely on one side of the threshold, an extra sensor adds little to that decision, however much it sharpens the loss estimate. If the band straddles the threshold, a further measurement pays off only when it narrows the relevant uncertainty enough to resolve the ambiguity. The instrumentation decision, in other words, can be reasoned about exactly as the hydraulic one is. Value of information has been operationalized in the water sector in three ways: as expected decision value in a Bayesian framework for pressure sensors for leak detection [46], as change in design cost as data reduce parameter variance [42], and through proxy information measures such as covariance traces and entropy [47,48,49]. The straddle test proposed here is a cheap qualitative proxy for the first, with no costs or priors. Sumer and Lansey note that the cause of a given cost change is not always clear [42], and a threshold-based criterion avoids that ambiguity at the price of ignoring magnitude. Quantifying it with action costs and sensor reliability, as in [46], is a natural extension.
In a mature form, such a tool would draw on four kinds of input: SCADA data (flows, pressures, levels, operational states), GIS/model data (topology, diameters, materials, roughness, connectivity), consumption data (profiles and new demands), and decision criteria (service thresholds and operating scenarios). Its output would be not merely a hydraulic simulation but a verdict — ROBUSTLY ACCEPTABLE, UNDETERMINED or ROBUSTLY UNACCEPTABLE — together with a note on which source of uncertainty dominates.
Where the verdict is UNDETERMINED, the tool could then name the move with the highest information value: lengthening the observation window, a night analysis, checking a flow meter, dropping in a temporary pressure logger, pinning down the legitimate consumption, inspecting a valve, or adding a measurement point. Thus, this supports both the hydraulic decision and the prioritization of investment in measurement.

6. Limitations and Validation Program

This is a proof-of-concept study. The rig is a single steel pipe (D = 35.6 mm) with three orifice diameters over a limited span of pressures and Reynolds numbers, so the Cd values obtained should not be carried over, unchecked, to other materials, crack shapes, wall thicknesses or scales.
A second limitation is the metrological step up to a real DMA. The laboratory meter belongs to a small pipe, whereas field networks run instruments of different class, resolution, drift, and sampling rate. The qualitative link between transit flow and detectability carries over, but the numerical threshold must be recomputed for each system based on the specifications of the already installed meters.
In real life, a connection decision is not only governed by the loss alone. Peak demand, consumption distribution in space, roughness, state of valves and pumps, reservoir levels, and boundary conditions can all take over near the threshold. A field application would therefore have to widen the band [Pmin, Pmax] to include all these in through scenarios or probabilistic propagation.
Next, a real DMA must be made, including audit of the SCADA and GIS data, check on synchronization, calibration over representative periods, validation on independent ones, real detectability thresholds, and comparison of scenarios with and without added instrumentation. A key output of such a pilot would be the value of information itself — pinning down when one more measurement point cuts the uncertainty enough to change or confirm a decision.
In technology-readiness terms, the actual work represents an experimental proof-of-concept. A real-DMA validation would be the next step toward demonstrating the framework in a relevant setting, short of full operational integration into an operator’s systems.

7. Conclusions

The timeliness of this work focuses on what operators are being asked to do: cut real water losses, use SCADA they have already installed, and ground their decisions despite the uncertainty in numbers. With cost pressure, sustainability targets, non-revenue-water goals and recurring need to judge spare capacity for new connections, the question of whether the measurement information actually fits the hydraulic decision or not is squarely a present-day concern for network management.
The paper proposes a decision-support framework that joins SCADA information to EPANET modelling through an explicit stage of uncertainty evaluation and propagation. The experiments confirm that a loss obtained as the difference between two transit flows can carry a high relative uncertainty even when the individual meters are accurate.
Detectability depends on the ratio between the size of the loss and the transit flow. Over the three studied diameters, the relative uncertainty falls from about ±48–55% at 2.07 mm to ±13–15% at 4.07 mm. This argues for working in the minimum-night-flow window, sizing DMAs sensibly and following changes with the same meter — all ways of getting more value from the SCADA already in place.
The discharge coefficient, around 0.64–0.68, serves as a physical link between experiment and the pressure-dependent loss in EPANET, not as a headline high-precision result. In the network, the loss level has to be calibrated against real data, avoiding the false precision of a local coefficient quoted too finely.
In the worked case a ±20% change in the loss moves the connection limit by only about ±0.14 L/s, and the decision turns over only within a narrow window near the threshold. Precision, in short, has to be judged against the decision at hand rather than in the abstract.
The main methodological contribution is the information-adequacy criterion itself: if the whole uncertainty band stays on one side of the threshold, the available information is enough; if it crosses, the decision is undetermined and reducing the uncertainty becomes worthwhile. The connection-approval case (Section 4.4,Figure 6) shows this in numbers — a ±20% uncertainty on the loss leaves the decision untouched outside a narrow window (≈ ±0.14 L/s) around the hydraulic limit, and only inside it does the classification turn undetermined. The same logic also emphasizes when extra instrumentation worth its cost and where to place it: near the threshold, where the band crosses.
The authors’ own, specific contributions are: (i) an experimental quantification of the uncertainty of a loss obtained by differencing two flows, across three orifice diameters, with the discharge coefficient recomputed from the measured diameters and the upstream driving head; (ii) a detectability-threshold relation that ties the metrological class of the instrument explicitly to the transit flow at which a loss becomes observable; (iii) the information-adequacy criterion, with its sorting into robust states (acceptable / undetermined / unacceptable); and (iv) an end-to-end, quantitative demonstration of the measurement–uncertainty–model–decision chain on a new-demand approval case, including the decision-switching zone. Of these, the detectability branch (i, ii) was validated experimentally, while the decision branch (iii, iv) was demonstrated numerically on a small, hydraulically delimited metering zone and remains to be tested on a real network.
Through these contributions, the paper speaks to a live operational problem: not merely gathering SCADA data or running a hydraulic model but telling apart the situations in which the information in hand already supports a robust decision from those in which reducing the uncertainty could change it.
The next step is to validate the framework on a real DMA and build a semi-automatic SCADA–GIS–EPANET–uncertainty–decision demonstrator that delivers both the hydraulic verdict and reading of whether the available information is sufficient.

Author Contributions

Conceptualization, E.V. and A.H.; methodology, E.V., A.H. and D.M.; software, N.S. and D.M.; validation, A.H. and R.M.; formal analysis, E.V.; investigation, E.V. and A.H.; writing—original draft preparation, E.V.; writing—review and editing, R.M.; visualization, E.V. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The data presented in this study are available on request from the corresponding author.

Acknowledgments

During the preparation of this manuscript, the authors used Claude (Anthropic, Claude Opus 4) and ChatGPT (OpenAI, GPT-5.6 Sol) for the purposes of drafting and language editing of parts of the text, translation of the manuscript into English, and assistance with the preparation of figures and tables. The authors have reviewed and edited the output and take full responsibility for the content of this publication.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Ekmekcioğlu, Ö.; Başakın, E.E.; Özger, M. Discharge coefficient equation to calculate the leakage from pipe networks. J. Inst. Sci. Technol. 2020, 10(3), 1737–1746. [CrossRef]
  2. Yu, T.; Zhang, X.; Lima Neto, I.E.; Zhang, T.; Shao, Y.; Ye, M. Impact of orifice-to-pipe diameter ratio on leakage flow: an experimental study. Water 2019, 11(10), 2189. [CrossRef]
  3. Lambert, A. Leakage reductions: the fundamental role of pressure management. Water World, (secondary summary of May 1994) 2013.
  4. Cassa, A.M.; van Zyl, J.E. A numerical investigation into the behaviour of cracks in uPVC pipes under pressure. WDSA Proceedings 2008. [CrossRef]
  5. Levin. Secondary compilation of exponent and Cd ranges; primary analysis of 107 South African zones, MSc dissertation, University of Cape Town, 2019.
  6. Shahangian, S. A.; Tabesh, M.; Mirabi, M. H. Effects of Flow Hydraulics, Pipe Structure and Submerged Jet on Leak Behaviour. Civ. Eng. Infrastruct. J. 2019, 52(2):225–243. [CrossRef]
  7. Uchôa, J.G.S.M.; Yu, T.; Yu, S.; Lima Neto, I.E. Computational Simulation of the Flow Induced by Water Leaks in Pipes. J of Irriga Drain Eng 2023, 149(6). [CrossRef]
  8. Altoukhy, M.; Alsaydalani, M. INVESTIGATION OF THE DISCHARGE COEFFICIENT FOR ORIFICE AND PIPE BEHAVIOR. J Eng Sci Technol 2022; 17(2): 839-853.
  9. Sunela, M.I.; Puust, R. Real time water supply system hydraulic and quality modeling – a case study. Procedia Eng 2015, 119, 744–752. [CrossRef]
  10. Kshirsagar, S.; Grayman, W.; Chenevey, B.; Shetti, A.; Gupta, S.; Bedinghaus, B.; Mylroie, S. Development of real-time drinking water distribution systems modeling technology using the EPANET Extended Period Simulation modeling toolkit. Int Conf Hydroinf 2014, CUNY Academic Works.
  11. Kim, J.H.; Chung, G.; Yoo, D.G. 2010). Calibration of C-Town network using Harmony Search algorithm. In: WDSA 2010, ASCE. [CrossRef]
  12. Alves, Z.; Muranho, J.; Albuquerque, M.T.D.; Ferreira, A. Water distribution network’s modeling and calibration: a case study based on scarce inventory data. Procedia Eng 2014, 70, 31–40. [CrossRef]
  13. Jun, S.; Lansey, K. Comparison of AMI and SCADA systems for leak detection and localization in water distribution networks. J. Water Resour. Plan. Manag. 2023, 149(11). [CrossRef]
  14. Ma, X.; Li, Y.; Zhang, W.; Li, X.; Shi, Z.; Yu, J.; Wang, J.; Liu, J. A real-time method to detect the leakage location in urban water distribution networks. J. Water Resour. Plan. Manag 2022, 148(12). [CrossRef]
  15. Zaman, D.; Gupta, A.K.; Uddameri, V.; Tiwari, M.K.; Sen, D. Exploring the key facets of leakage dynamics in water distribution networks: experimental verification, hydraulic modeling, and sensitivity analysis. J. Clean. Prod. 2022, 362, 132236. [CrossRef]
  16. Knickerbocker, K.L.; Snow, K. Application of existing water models for use on new development. In: WDSA 2010, ASCE, 1470–1478. [CrossRef]
  17. Lambert, A.O. What do we know about pressure: leakage relationships in distribution systems? IWA Conference System Approach to Leakage Control and Water Distribution Systems Management 2001, 1–9.
  18. Fox, S.; Collins, R.; Boxall, J. Experimental study exploring the interaction of structural and leakage dynamics. J. Hydraul. Eng. 2016, 143(2). [CrossRef]
  19. Schwaller, J.; Van Zyl, J.E. Modeling the Pressure-Leakage Response of Water Distribution Systems Based on individual leak behavior. J. Hydraul. Eng. 2014, 141(5), 04014089.
  20. Yavari, P.; Akhtari, A.A.; Azari, A. Comparison of head–leakage flow equations for circular holes in water distribution networks with a new equation. J. Appl. Res. Water Wastewater 2023, 10(2), 1–9. [CrossRef]
  21. Hotupan, A.; Hadarean, A. Experimental Determination of the Discharge Coeffcient Through Circular Orifice in PVC Pipes. J. Appl. Eng. Sci., University of Oradea, Civil Engineering and Architecture Faculty, 2020;10(2): 133-138. [CrossRef]
  22. Alsaydalani, M.O. Effect of Orifice Hydraulic and Geometric Characteristics on Leakage in Water Distribution Systems. Int. J. of GEOMATE 2023, 25(107), 59–67. [CrossRef]
  23. Ferrante, M.; Massari, C.; Brunone ,B.; Meniconi, S. Leakage and pipe materials. WDSA 2010 Proceedings (published 2012), pp.1140-1145. [CrossRef]
  24. Tricarico, C.; Cappello, C.; de Marinis, G.; Leopardi, A. Minimum Night Flow Estimation in District Metered Areas. Water 2024, 16, 3642. [CrossRef]
  25. Giudicianni, C.; Mazzoni, F.; Marsili, V.; Alvisi, S.; Creaco, E. Modelling minimum night consumption as a function of long-run average outflow to users and applications to real world case studies. Front. Water 2025, 7:1693893. [CrossRef]
  26. Marzola, I.; Alvisi, S.; Franchini, M. Minimum Night Flow Analysis and Application of the Fixed and Variable Area Discharges Model for Characterizing Leakage in the Gorino Ferrarese (FE-Italy) District. Environ. Sci. Proc. 2020, 2, 8. [CrossRef]
  27. Alvisi, S.; Luciani, C.; Franchini, M. Using water consumption smart metering for water loss assessment in a DMA: a case study. Urban Water J. 2019, 16(1), 77–83. [CrossRef]
  28. Quevedo, J.; Perez, R.; Pascual, J.; Puig, V.; Cembrano, G.; Peralta, A. Methodology to detect and isolate water losses in water hydraulic networks: application to Barcelona water network. 8th IFAC SAFEPROCESS 2012, pp. 922-927.
  29. JCGM 100:2008. Evaluation of measurement data: Guide to the expression of uncertainty in measurement (GUM). [CrossRef]
  30. JCGM 101:2008. Supplement 1 to the GUM: propagation of distributions using a Monte Carlo method. [CrossRef]
  31. Diaz, S.; Minguez, R.; Gonzalez, J. Probabilistic leak detectability assessment via state estimation in water transport networks. Stoch Environ Res Risk Assess 2018; 32(7): 2111-2128. [CrossRef]
  32. Nejjari, F.; Sarrate, R.; Blesa, J. Optimal pressure sensor placement in water distribution networks minimizing leak location uncertainty. Procedia Eng 2015, 119, 953-962. [CrossRef]
  33. Vrachimis, S. G.; Eliades, D. G.; Polycarpou, M. M. Leak Detection in Water Distribution Systems Using Hydraulic Interval State Estimation, IEEE Conference on Control Technology and Applications (CCTA), Copenhagen, Denmark, 2018, pp. 565-570. [CrossRef]
  34. Sophocleous, S.; Savić, D.; Kapelan, Z. Leak Localization in a Real Water Distribution Network Based on Search-Space Reduction. J. Water Resour. Plan. Manag 2019;145(7):04019024. [CrossRef]
  35. Van Zyl, J.; Cassa, A. Modeling Elastically Deforming Leaks in Water Distribution Pipes. J. Hydraul. Eng. 2014. 140. 182-189. 10.1061/(ASCE)HY.1943-7900.0000813.
  36. Kabaasha, A.M.; van Zyl, J.E.; Piller, O. Modelling Pressure: Leakage Response in Water Distribution Systems Considering Leak Area Variation. 14th CCWI international conference, Computing and Control in Water Industry, Nov 2016, Amsterdam, Netherlands. 7 p. ⟨hal-01549955⟩.
  37. Kabaasha, A.M.; Piller, O.; Van Zyl, J. Incorporating the Modified Orifice Equation into Pipe Network Solvers for More Realistic Leakage Modeling. J. Hydraul. Eng. 2018. 144. 8. [CrossRef]
  38. EPANET manual, Chapter 3: network model (emitters). https://epanetmanual.readthedocs.io/en/latest/3_network_model.html.
  39. Ciaponi, C.; Creaco, E. Comparison of Pressure-Driven Formulations for WDN Simulation. Water 2018, 10, 523. [CrossRef]
  40. Strijdom, L.; Speight, V.; Jacobs, H.E.; An assessment of sub-standard water pressure in South African potable distribution systems. J. Water Sanit. Hyg. Dev. 2017; 7 (4): 557–567. [CrossRef]
  41. Pasha, M.F.K; Lansey, K. Effect of Data Collection on the Estimation of Wall Reaction Coefficients for Water Distribution Models. J. Water Resour. Plan. Man 2012. 138(6). [CrossRef]
  42. Sumer, D.; Lansey, K. Effect of Uncertainty on Water Distribution System Model Design Decisions. J. Water Resour. Plan. Man 2009. 135(1). [CrossRef]
  43. Giustolisi, O.; Savic, Dragan; Kapelan, Zoran (2008). Pressure-driven Demand and Leakage Simulation for Water Distribution Networks. J. Hydraul. Eng. 2008. 134(5). [CrossRef]
  44. Momeni, A.; Piratla, K.R. A Proof-of-Concept Study for Hydraulic Model-Based Leakage Detection in Water Pipelines Using Pressure Monitoring Data. Front. Water 2021. 3:648622. [CrossRef]
  45. Qureshi, M.; Feng, Z.; Kumar, V. et al. A systematic literature review of digital twin applications for sustainable water systems in natural and built environment. Discov Sustain 2026. 7, 1386. [CrossRef]
  46. Jung, D.; Kang, D.; Kim, J.; Lansey, K. Robustness-Based Design of Water Distribution Systems. J. Water Resour. Plan. Man 2014. 140. [CrossRef]
  47. Khorshidi, M.S.; Nikoo, M. R.; Sadegh, M. Optimal and objective placement of sensors in water distribution systems using information theory. Water Res. 2018. 143, Pages 218–228. [CrossRef]
  48. Khorshidi, M.S.; Nikoo, M. R.; Taravatrooy, N.; Sadegh, M.; Al-Wardy, M.; Al Rawas, G. Pressure sensor placement in water distribution networks for leak detection using a hybrid information-entropy approach, Inf. Sci. 2020. 516, Pages 56-71, . [CrossRef]
  49. Behzadian, K.; Kapelan, Z.; Savic, D.; Ardeshir, A. Stochastic sampling design using a multi-objective genetic algorithm and adaptive neural networks. Environ. Model. Softw. 2008, 24 (4). pp. 530-541. [CrossRef]
Figure 4. Detectability threshold as a function of transit flow and comparison of the operating points. The grey area marks the range measured on the rig (40–65 L/min); the point at ≈ 10 L/min and modes B–D (marked with *) are methodological estimates (eq. 6 and operating assumptions), not verified experimentally.
Figure 4. Detectability threshold as a function of transit flow and comparison of the operating points. The grey area marks the range measured on the rig (40–65 L/min); the point at ≈ 10 L/min and modes B–D (marked with *) are methodological estimates (eq. 6 and operating assumptions), not verified experimentally.
Preprints 246096 g004
Figure 6. Minimum pressure as a function of the new demand and the decision-switching zone.
Figure 6. Minimum pressure as a function of the new demand and the decision-switching zone.
Preprints 246096 g006
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.