Inverse Finite-Element Identification of Hydraulically Stabilised Layers from Static Plate Load Tests on a Full-Scale Circular Test Track, with Geopolymer-Stabilised Alternatives

Submitted:

22 November 2026

Posted:

24 November 2026

You are already at the latest version

Abstract
Static plate load tests are routinely used to accept treated pavement layers, but the strain moduli Ev1 and Ev2 describe the layered system, not the layer. This study identifies the elasto-plastic parameters of the subgrade and of three hydraulically treated layers built on a full-scale circular test track (ALT-LIRA, Iaşi, Romania): a soil stabilised in place, a treated sandy gravel and a treated milled cement concrete. The complete first-loading–unloading–reloading plate curves were back-analysed with an axisymmetric finite-element model in Ansys Mechanical APDL, verified against independent layered-elastic and finite-element solutions (differences ≤0.1 %). The tested layers were described with an extended Drucker–Prager model with isotropic hardening, and the parameters were identified by Latin hypercube sampling followed by Levenberg–Marquardt optimisation, together with their uncertainty. For the subgrade, the model reproduced Ev1 and Ev2 within 3 % and 9 % (E=41 MPa, coefficient of variation 13 %). For the stabilised subgrade, the curve was reproduced within the resolution of the dial gauge, but the modulus of the treated layer and the stiffness of its support were almost perfectly correlated (r=−0.99): the test identifies the stiffness of the layered system, and the support had to be 4.5–4.7 times stiffer than indicated by tests on the untreated soil. The test on the treated milled concrete was at the resolution limit of the gauge, and the test on the treated sandy gravel, dominated by volumetric compaction under the plate, could not be described by the shear-hardening model. Light-weight deflectometer moduli computed with the identified parameters agreed with the measured ones within 30 % on the subgrade, but on the treated layers the measured moduli saturated at 93–177 MPa, well below the static stiffness, so that the deflectometer could not discriminate between stiff treated layers. Scenarios with geopolymer-treated layers, with strengths taken from the literature and a modulus–strength scaling calibrated on the built layers, indicate that the same plate response could be obtained with 154–171 mm of geopolymer-stabilised soil and with 115–139 mm of geopolymer-treated recycled concrete instead of 200 mm. The results show that the strain moduli of treated layers should be interpreted as system indices, and they provide a mechanical basis for comparing alternative, lower-carbon binders with the reference layers.
Keywords: 
;  ;  ;  ;  ;  ;  ;  

1. Introduction

This study starts from three premises. The first is experimental: a full-scale accelerated pavement test on the ALT-LIRA circular track in Iaşi, Romania, produced a set of construction-control records, static plate load tests and LWD tests on the subgrade and on layers treated with hydraulic road binders, that is unusually complete because the full loading–unloading–reloading curves were reported [1,2,3]. The second is methodological: the quantities derived from these tests in practice, the strain moduli and their ratio, characterise the layered system under the plate rather than the treated material, and they cannot by themselves support a comparison between materials. The third is practical: hydraulic road binders and cold recycling are now widely used to reuse milled concrete, reclaimed asphalt and marginal soils, and alkali-activated (geopolymer) binders are emerging as lower-carbon substitutes, but their field performance in pavement layers has to be judged against a reference that is itself quantified.
Static plate load tests and light-weight deflectometer (LWD) tests are the standard tools for accepting earthworks and unbound or treated pavement layers. The static test yields the strain moduli of the first and second loading, E v 1 and E v 2 , whose ratio is used as an indicator of compaction, whereas the LWD yields a dynamic modulus, E v d , from a single drop. The static test is standardised, for example in DIN 18134 [4], and the LWD test in national guidelines such as [5]. Both tests are quick and are tied to acceptance thresholds in national specifications [6,7], and their mutual correlations, as well as their dependence on stress level, layer stiffness and plate size, have been studied extensively [8,9,10,11].
These quantities, however, are not material properties. They are indices of a whole layered system under a particular plate, stress level and loading history: a stiff treated layer on a soft support and a softer layer on a stiff support can give the same E v 2 . A treated layer therefore cannot be compared with an alternative material, or carried into a mechanistic design, on the basis of E v 2 alone.
Inverse analysis of the plate test with a numerical model is the natural way to extract layer properties from the measured curve. Ahn et al. [12] back-calculated the parameters of a resilient-modulus model of the subgrade from cyclic plate load tests with an axisymmetric finite-element (FE) model, and showed that the identified values depend on the assumed boundary distance and on the parameters fixed in advance. Other FE studies of the plate test have addressed plate-size effects and the relation between the strain modulus E v 2 and the elastic modulus of the ground [13,14]. More generally, back-analysis of field measurements is an established route to soil parameters in geotechnical engineering, where the uncertainty of the identified parameters is quantified from the sensitivity of the measured response [15]. Most of the analyses of plate tests, however, use elastic or resilient models and fit either one loading branch or a cyclic response at small strains. The complete first-loading–unloading–reloading curve of the static test carries more information: it contains the irreversible settlement, which is the origin of the E v 2 / E v 1 ratio, as well as the reloading stiffness. Moreover, the inverse problem based on plate settlements is intrinsically non-unique: a single test samples a depth of influence governed by the plate diameter and yields an average modulus, so that a close fit of the measured settlements does not guarantee correct layer properties, and profiles of stiffness with depth can be recovered only with additional information such as tests with several plate diameters [16]. To our knowledge, the complete loading–unloading–reloading curve has not yet been used to identify, together with their uncertainty, the parameters of hydraulically treated layers built in situ. Three questions therefore remain open: whether the parameters of a thin treated layer can be identified from a single plate test at all, or only the stiffness of the layered system; how much the support under a treated layer contributes to the measured moduli; and how a layer built with an alternative binder can be compared with the reference layers on a mechanical rather than an empirical basis. These questions define the research gap addressed here.
Treated layers are becoming more important with the move towards cold recycling and in situ stabilisation, in which milled cement concrete, reclaimed asphalt and marginal soils are reused in base and capping layers after treatment with hydraulic road binders [1,17,18]. Recycled concrete aggregate in particular has been characterised extensively as an unbound and as a cement-stabilised base material [19,20,21], and full-scale accelerated tests have shown that cement treatment changes the structural response and the failure mode of reclaimed layers [22]. Lightly cemented layers are stiff when intact but crack under shrinkage and traffic, so that their field stiffness can differ markedly from laboratory values [23]. Alkali-activated binders, or geopolymers, made from fly ash or ground granulated blast-furnace slag, are being studied as lower-carbon substitutes for the cement-based binders in these layers, both for clay and subgrade stabilisation [24,25] and for recycled concrete aggregate bases [26,27]. The laboratory literature on these materials reports mainly compressive and indirect tensile strengths and comparatively few stiffness values. A comparison between a geopolymer-treated layer and a layer built on site with a commercial hydraulic binder therefore needs a common basis: a mechanical model whose parameters for the reference layers have been identified from field tests.
Accelerated pavement testing facilities provide such references under controlled conditions [28,29], and the ALT-LIRA circular facility in Iaşi, Romania, offers one for treated layers [1,2,3]. During the construction of its experimental sectors, static plate and LWD tests were made on the subgrade and on three treated layers: a soil stabilised in place, a sandy gravel and a milled cement concrete, the last two treated with a hydraulic road binder. The complete loading–unloading–reloading curves were reported, but they have so far been used only to compute E v 1 , E v 2 and their ratio.
This study uses these curves to answer three questions. (i) Which elasto-plastic parameters of the treated layers, and which effective stiffness of their support, reproduce the complete plate curves, and how well are these parameters constrained by the data? (ii) Are the identified parameters consistent with the independent LWD measurements made on the same layers? (iii) What thickness of a geopolymer-treated layer, with properties taken from the literature, gives the same plate response as the layers built on the track? The FE model is verified against independent layered-elastic and FE solutions before it is used, the parameters are reported with their uncertainty, and the data, model files and scripts are released with the article.

2. Materials and Methods

2.1. Test Track and Sectors

ALT-LIRA is a circular accelerated pavement testing facility of the Gheorghe Asachi Technical University of Iaşi. It is built in an annular reinforced-concrete pit with an outer diameter of 18 m, an inner diameter of 12 m and a depth of 1.8 m. Two 57.5 kN dual wheels, on a 15 m rotating beam, run on a mean radius of 7.5 m [1,2].
The campaign analysed here compared four structures, denoted S1–S4 [3], all with a 5 cm MAS 16 wearing course and a 6 cm BAD 22.4 binder course (Figure 1). Sector S1 has a crushed stone base over sandy gravel on subgrade soil 4b. Sector S2 has a 20 cm base of milled cement concrete 0–31.5 mm treated with a hydraulic road binder (Doroport, 3.5 %) over 20 cm of sandy gravel on soil 4b. Sectors S3 and S4 have an asphalt base and a granular subbase, treated with Doroport in S3 and of crushed stone in S4, over 25 cm of sandy gravel and a 20 cm capping layer of soil 4d stabilised in place with Dorosol (3 %). A five-sector description of the same campaign [2] includes a further sector, denoted S3* here, with a 20 cm base of sandy gravel 0–31.5 mm treated with Doroport over 20 cm of untreated sandy gravel on soil 4b; the plate test on the treated sandy gravel was made on this sector (Section 2.2). The correspondence between the two descriptions is given in the Supplementary Material.
The plate load tests analysed here were carried out during construction on four layers. L1 is the natural subgrade (soil type 4b). L2 is the subgrade stabilised in place with 3 % Dorosol over a thickness of 200 mm, on natural soil 4d. L3 is a 200 mm layer of sandy gravel 0–31.5 mm treated with 3.5 % Doroport, placed on 200 mm of untreated sandy gravel 0–63 mm and soil 4b. This structure, denoted S3* in Figure 1, appears only in the five-sector description of [2]; the LWD records of the same layer ( E v d = 177.2 MPa in [2] and 167.2 MPa in [3], both with the same anomalous second-drop reading) identify the test as made on that sector and not on the four-sector variant with a stabilised subgrade. L4 is a 200 mm layer of milled cement concrete treated with 3.5 % Doroport, on 200 mm of untreated sandy gravel and soil 4b.
Both theses report the L1–L3 records. A cross-check of the two transcriptions (Section 3.1) revealed copying errors in [3]; the curves were therefore taken from [2] for L1–L3 and from [3] for L4, which appears only there.

2.2. Static Plate Load Test and Light-Weight Deflectometer

The static tests used a Lucas plate with a diameter of 300 mm. Each test comprised a first loading in steps to the maximum pressure, an unloading and a second loading, and the settlement was read with a dial gauge with a resolution of 0.01 mm. As in DIN 18134 [4], a second-degree polynomial s ( σ ) = a 0 + a 1 σ + a 2 σ 2 is fitted to each loading branch, and the deformation modulus is computed, as in both theses, from
E v = π 4 ( 1 − ν 2 ) D a 1 + a 2 σ max ,
with ν = 0.40 , D = 300 mm and π taken as 3.14, which gives a constant of 197.82 mm; the tests and their evaluation followed the Romanian instructions for the quality control of earthworks, AND 530 [30], adopted in both theses. DIN 18134 uses 1.5 r = 225 mm instead, so that the E v values reported here are 0.879 times the DIN 18134 values computed from the same curve. With the 197.82 mm constant, the printed E v values were reproduced to within 0.01 % in all six cases, which also confirmed the plate diameter that neither thesis states explicitly. The resulting target values are listed in Table 1.
The first loading step was given a weight of 0.5 in the fit because it includes the bedding of the plate. In L3, two points that are physically inconsistent with the rest of the curve were excluded, and in L4 three reloading points at the gauge resolution were given a weight of 0.3 (Section 3.1).
The LWD tests were made according to AND 530 [30] with a ZORN ZFG 3000 GPS device (10 kg falling weight, 300 mm plate), whose standard loading, a peak force of 7.07 kN (a mean plate pressure of 0.1 MPa) with a pulse duration of 17 ms, is prescribed in [5]. The dynamic modulus is E v d = 1.5 r σ / s = 22.5 / s , with s the peak settlement in mm and E v d in MPa. The LWD records were not used in the identification and serve as an independent check (Section 2.6).

2.3. Axisymmetric Finite-Element Model

The purpose of the numerical model is to translate a measured settlement curve into properties of the tested layer. The static plate test loads a small volume of a layered system through a rigid plate, with a stress field that is strongly non-uniform near the plate edge and decays with depth; the strain moduli computed from the curve average this response over all the layers within the depth of influence. A model that reproduces the geometry of the test, the layering, the rigid plate, the self-weight and the measured load history allows the curve to be interpreted in terms of the parameters of each layer, and the same model can then predict the response of a layer made of another material, which is the basis of the scenarios of Section 2.7. Because the plate is circular, centrally loaded and the layers are horizontal and laterally uniform, the problem is axisymmetric and is solved exactly on a radial section; three-dimensional views are obtained by revolving the axisymmetric solution about the plate axis.
The static scheme of the model is shown in Figure 2. The computational domain is a radial section of radius R and depth H, with the symmetry axis at r = 0 . The tested layer occupies the top of the section (200 mm for the treated layers, the whole depth for the subgrade), and the underlying layers follow the structures of Figure 1. The plate acts on the surface over 0 ≤ r ≤ a , and gravity acts on the whole domain. Radial displacements are prevented on the axis and on the outer boundary (rollers), and both displacement components are prevented at the base.
The tests were modelled with ANSYS Mechanical APDL 2025 R2 using axisymmetric eight-node quadrilaterals with quadratic displacement interpolation (PLANE183, axisymmetric option, pure displacement formulation) [31]. The domain has a radius and a depth of 300 a = 45 m, where a = 150 mm is the plate radius; the bottom is fixed, and the outer boundary and the axis are on rollers. The mesh is structured and graded from a / 32 = 4.7 mm at the plate edge, with a growth ratio of 1.2, to a maximum size of R / 12 , and it follows the layer interfaces exactly (Figure 3); it comprises 2464 elements and 7593 nodes for the subgrade and 3024–3360 elements and 9293–10,313 nodes for the layered structures. The element size at the plate edge was chosen from the convergence study of Section 2.4, which showed that the rigid-plate settlement is within 0.25 % of the extrapolated value at this size. The rigid, smooth plate is represented by coupling the vertical displacements of all surface nodes with r ≤ a , and each pressure of the measured load history is applied as the equivalent resultant force on the coupled set. The self-weight of the layers is applied in a first load step to establish the geostatic stress state, and settlements are measured relative to the end of that step.
The tested layer is described by the linear form of the extended Drucker–Prager criterion [32,33], matched to the outer Mohr–Coulomb cone,
F = q + α I 1 − σ Y , α = 2 sin ϕ 3 ( 3 − sin ϕ ) , σ Y = 6 c cos ϕ 3 ( 3 − sin ϕ ) ,
with non-associated flow of zero dilatancy and linear isotropic hardening with a tangent modulus E t = h E . The underlying layers are linear elastic. Their moduli are the design values of the structures [2,3], except for soil 4b under L3 and L4, for which the modulus identified in L1 is used.
Each analysis is a static, materially non-linear analysis (small displacements) solved with the full Newton–Raphson method in a sequence of load steps: a first step that applies gravity, followed by one load step for each pressure of the measured history (16 steps for the complete loading–unloading–reloading cycle). Automatic load stepping subdivides each step into 5–200 substeps as required by the convergence of the plastic increments. The force and displacement convergence criteria were set to fixed values, 10 N for the L 2 norm of the residual force and 10 − 3 mm for the largest displacement increment, because the automatic reference values are dominated by the self-weight reactions (about 8 × 10 6 N) and would leave the plate load (5–35 kN) uncontrolled. Two further numerical observations matter for reproducibility. With the mixed u–P formulation, the volumetric-compatibility check oscillated in the plastic zone at the plate edge and the increments did not converge, whereas the pure displacement formulation converged. With perfect plasticity ( h = 0 ), the solution did not converge beyond about 0.16 MPa, while a small hardening modulus was sufficient to trace the complete loading–unloading–reloading history; the identified hardening ratios range from 0.010 to 0.18 (Section 3.2).

2.4. Verification of the Finite-Element Model

The MAPDL model was verified against independent solutions: the layered elastic theory and a separate axisymmetric finite-element formulation, implemented independently of the MAPDL model. With identical geometry and boundary conditions, the two codes differ by at most 0.002 % for a flexible circular load on a half-space and by at most 0.08 % for the surface deflection and the interface strains and stresses of a two-layer system. For the rigid smooth plate, the differences are − 0.55 , − 0.24 and − 0.10 % for mesh factors of 1, 2 and 4, i.e., first-order convergence caused by the edge singularity.
Against the exact solutions (Boussinesq, the rigid punch w = π p a ( 1 − ν 2 ) / ( 2 E ) and Burmister’s multilayer theory [34]), the deflection error caused by a fixed base decreases as 1 / L , where L is the domain size; at L = 20 a it amounts to − 3.9 % for the flexible load, − 5.1 % for the rigid plate and − 12.4 % for the two-layer case. Values extrapolated from L = 20 a and 40 a differ from the exact solutions by − 0.002 , − 0.14 and − 0.02 %, respectively. The domain of L = 300 a used here therefore leaves a truncation error below 0.4 % on a half-space and below 1 % on the layered structures. In the elastic limit, the model gives a settlement of 3.86 mm for E = 25 MPa and 0.5 MPa, against 3.88 mm analytically. A single analysis of the complete load history takes 40–150 s on two processor cores, which makes it possible to run the several hundred analyses required by the identification.

2.5. Inverse Identification

For the subgrade (L1), the inverted parameters are θ = ( E , c , h ) . For the treated layers (L2–L4), θ also includes a factor k that multiplies the moduli of all underlying layers. This factor is needed because the measured stiffness cannot be reached with the support moduli inferred from LWD tests on the soil before treatment ( E v d = 13 –16 MPa on soil 4d): a layered elastic calculation shows that, on a 30 MPa support, a 200 mm layer of any stiffness gives a rigid-plate compliance of at least 0.86 mm/MPa, whereas the measured reloading compliance of L2 is 0.47 mm/MPa. The LWD tests on the treated surface ( E v d = 93 –115 MPa) confirm that the system as a whole is stiff, and k is therefore interpreted as an effective stiffening of the support (Section 4). All parameters are optimised in logarithmic form. Because c and ϕ cannot be separated from a single plate curve, the friction angle is fixed per material, at 25 for the cohesive subgrade, 35 for the stabilised subgrade and 40 for the treated granular layers, and its effect is discussed in Section 4.
The objective function is the weighted sum of squared settlement residuals over all points of the three branches,
F ( θ ) = ∑ i w i s i , FE ( θ ) − s i , meas σ s 2 ,
with σ s = 0.01 m m + 0.02 s max , i.e., the gauge resolution plus 2 % of the maximum settlement. A Latin hypercube sample [35] of 30 parameter sets within physical bounds is evaluated first, and Levenberg–Marquardt iterations [36,37] are then started from the best samples (two for L1, one for L2–L4). The Jacobian is computed by forward differences, or backward differences on an active bound, and four damping factors are tried per iteration. All parameter sets of one stage are solved in a single MAPDL run that restarts from a stored base model for each set. Parameter uncertainty is estimated, as is common in geotechnical back-analysis [15], from the linearised covariance Cov ( θ ) ≈ s 2 ( J T J ) − 1 , with s 2 = F / ( n − p ) . L1 is identified first, because its modulus enters the models of L3 and L4.

2.6. Light-Weight Deflectometer Model

The LWD tests are simulated with the same mesh and the identified parameters in a transient analysis. After the self-weight step, a half-sine force pulse with a peak of 7.07 kN and a duration of 17 ms is applied to the plate, whose mass (15 kg) is represented by a lumped mass on the coupled set; Rayleigh stiffness damping ( β = 5 × 10 − 4 s, about 5 % at 30 Hz) is included. The modelled E v d is computed from the peak settlement as for the device and compared with the measured values, which were not used in the identification.

2.7. Geopolymer-Treated Alternatives

The properties of geopolymer-treated materials were taken from the literature, using only values stated in the text or tables of the source papers, each with a verified DOI. Two groups of materials match the treated layers for which reliable parameters were identified (Section 3.2): slag–fly-ash geopolymer treatment of soils [38,39] for the stabilised subgrade L2, and geopolymer-stabilised recycled concrete aggregate [26,27] for the milled-concrete base L4; fly-ash geopolymer bases with crushed aggregate [40] indicate the upper end of the strength range. No scenario was computed for L3, whose parameters could not be identified. Most sources report the unconfined compressive strength (UCS) and few report a stiffness. Laboratory moduli of intact specimens are, in any case, not directly comparable with the modulus of a field layer identified from a plate test, which reflects compaction variability, shrinkage cracking and the plate-scale stress state.
The scenarios are therefore anchored to the identified reference layers and scaled with the 28-day UCS. For each treated layer, the modulus and cohesion of the geopolymer-treated material are taken as
E gp = E ref UCS gp UCS ref n , c gp = c ref UCS gp UCS ref ,
where E ref and c ref are the identified values and UCS ref is the strength measured in the theses on the same Dorosol and Doroport mixtures (2.67–2.98 MPa); h, ϕ and the support factor k are kept unchanged. Because no verified modulus–strength relation exists for field layers treated with geopolymers, the exponent is varied as n = 0.5 , 0.75 and 1.0. Conservative strengths were adopted for the geopolymer materials: 5.2 MPa for the treated soil [38] and 12.45 MPa for the treated recycled concrete [27], the lower end of the reported range (up to 22.4 MPa [26]). The plate test is then simulated for layer thicknesses of 100–250 mm, and the equivalent thickness is the one at which the modelled E v 2 equals that of the reference layer at 200 mm.

3. Results

3.1. Consistency of the Field Records

The plate records were cross-checked before use: for each curve, the printed E v 1 and E v 2 were recomputed from the printed settlements, and the two theses were compared where they report the same test. Both theses report L1–L3 with the same settlements, but some transcribed values differ. E v 2 of L3 is printed as 269.43 MPa in [3], whereas the curve gives 576.6 MPa, the value given in [2]; the L3 pressures in [3] are also mis-transcribed. In all four tables, the printed reloading settlement at 0.7 σ max (3.62–3.63 mm) is a copying remnant and was not used. Two points of L3 are physically inconsistent and were excluded: at the first unloading step the settlement increases by 0.03 mm, which indicates creep rather than elastic rebound, and at the first reloading step it decreases under increasing load. In L4, the reloading settlements change by only one or two gauge divisions (0.01 mm) over the whole branch, so that E v 2 cannot be determined at the gauge resolution and these points were down-weighted. Finally, the conversion from LWD to static E v 2 given in [3] (Equation 5.1) does not reproduce the static E v 2 measured on the same layers and was not used as a target. The full list of checks is given in the Supplementary Material.

3.2. Identified Parameters

Subgrade (L1). The Latin hypercube stage gave converged solutions for 23 of 30 parameter sets. The non-converged sets combined very low hardening with low cohesion. Both Levenberg–Marquardt runs reached the same minimum ( F = 127.8 ):
  • E = 41.1 MPa, with a coefficient of variation of 13 %;
  • c = 36 kPa (CV 60 %);
  • h = 0.18 (CV 37 %);
  • ϕ = 25 (fixed).
The model reproduces the first loading closely (Figure 4). The RMS settlement error over all points is 0.30 mm, i.e., 6 % of the maximum settlement. The derived moduli are given in Table 2.
The model gives E v 2 / E v 1 = 2.06 ; the measured ratio is 1.94.
The largest misfit is on the unloading branch. In the model, unloading is linear elastic. The measured unloading is strongly non-linear: most of the recovery occurs below 0.12 MPa. This hysteresis cannot be represented by an isotropic-hardening model, and it bounds the achievable fit.
Cohesion is the least constrained parameter. Over the stress range of the test, c trades off against the hardening modulus, and the curve constrains only their combination.
Stabilised subgrade (L2). With the support moduli of the untreated soil ( k = 1 ), the best fit placed the modulus of the stabilised layer on its upper bound and still under-predicted E v 2 by more than a factor of two ( F = 562 ). With the support factor included, the Latin hypercube stage converged for 26 of 30 sets and the Levenberg–Marquardt iterations reduced the objective to F = 13.7 , with E = 7376 MPa, k = 4.65 , c = 84 kPa and h = 0.010 ( ϕ = 35 , fixed). The computed curve follows the measured one to within one or two gauge divisions over all three branches (RMS error 0.018 mm, 4 % of the maximum settlement). The model gives E v 1 = 224.5 MPa against 229.2 MPa measured ( − 2 %) and E v 2 = 511 MPa against 443 MPa ( + 15 %). The larger difference in E v 2 does not reflect a poorer fit of the curve: the reloading branch spans only 0.17 mm, so that differences of 0.01–0.02 mm in individual readings change the polynomial slope, and hence E v 2 , substantially.
The modulus of the layer and the support factor are almost perfectly correlated (correlation coefficient − 0.99 ), and their individual coefficients of variation are correspondingly large (323 % for E and 148 % for k). The plate curve therefore constrains the stiffness of the system formed by the treated layer and its support, but not the share of each; this limitation is discussed in Section 4. The computed fields (Figure 5) show that, unlike in the subgrade, plastic straining is confined to the treated layer, near the edges of the plate, and that the underlying soil remains elastic.
Treated milled concrete (L4). The Latin hypercube stage converged for 26 of 30 sets, and the Levenberg–Marquardt iterations reduced the objective from 78.8 to 57.4, with E = 14 , 480 MPa, k = 4.54 , c = 45 kPa and h = 0.013 ( ϕ = 40 , fixed); several later iterations were rejected because perturbed parameter sets did not converge. The fit is the poorest of the four cases (RMS error 0.028 mm, about three gauge divisions and 17 % of the maximum settlement; Figure 4), and the model gives E v 1 = 457 MPa against 636 MPa measured. The measured curve explains why. Its maximum settlement is only 0.17 mm, and most of the irreversible settlement (0.05 of 0.13 mm) occurs in the first load step, which is characteristic of the bedding of the plate rather than of the response of the layer; after that step the layer behaves almost rigidly, and the whole reloading branch spans three gauge divisions. A continuum model of the layered system cannot reproduce a bedding offset of this kind, and its compromise between the bedding step and the stiff remainder of the curve underestimates E v 1 . The identified parameters of L4 are correspondingly uncertain (coefficients of variation of 86–260 %), although the support factor is consistent with that of L2. The test on L4 is therefore at the resolution limit of the static plate test with a dial gauge, and its parameters should be read as an order of magnitude rather than as identified values. The computed fields (Figure 7) are nevertheless instructive: the settlement bowl extends to a depth of more than 1 m, which shows that the plate test on a stiff 200 mm base is governed by the deeper layers, and plastic straining is again confined to the treated layer near the plate edge.
Treated sandy gravel (L3). The Latin hypercube stage converged for 24 of 30 sets. The Levenberg–Marquardt iterations reduced the objective from 194 to 112 but drove the support factor to the upper bound of its range ( k = 20 ), with a low modulus of the treated layer ( E = 182 MPa), c = 75 kPa and h = 0.031 . The model then gives E v 1 = 109 MPa against 128 MPa measured and E v 2 = 279 MPa against 577 MPa (RMS error 0.076 mm, 9 % of the maximum settlement). This solution is not physically meaningful, since it implies a support several times stiffer than the treated layer above it, and L3 is regarded as not identifiable with the present material model.
The reason lies in the shape of the measured curve. Of the 0.74 mm settlement reached at the end of the first loading, only 0.06 mm is recovered on unloading, and the reloading branch is very stiff, which gives the unusually high ratio E v 2 / E v 1 = 4.5 . The plate therefore produced an almost entirely irreversible settlement in a layer that is otherwise stiff. Such behaviour is characteristic of volumetric compaction of an insufficiently compacted or not yet fully bound layer under the plate, which a pressure-dependent shear yield criterion with isotropic hardening cannot reproduce: to obtain the irreversible settlement, the optimiser must make the layer soft, and to recover the reloading stiffness it must then make the support unrealistically stiff. A model with a compaction cap, in which plastic volumetric strain develops under increasing mean stress [41], would be needed to describe this test; this is left for further work, and the L3 parameters are not used in the scenarios.
The identified parameters of all cases are summarised in Table 3.

3.3. Light-Weight Deflectometer: Model versus Measurement

Table 4 compares the dynamic moduli computed with the identified elastic parameters with those measured on the same layers. On the subgrade, the computed modulus (47.8 MPa) is 30 % higher than the measured one (34.8–37.3 MPa), which is consistent with the absence of plastic straining and plate bedding in the linear dynamic model and with the static E v 2 of 38.7 MPa. On the treated layers, however, the computed moduli exceed the measured ones by factors of 1.8 to 6.9, whereas the measured values remain within 93–177 MPa although the static reloading moduli of the same layers are three to five times larger. The measured E v d of the treated layers therefore saturates: a 10 kg falling weight produces peak settlements of only 0.13–0.24 mm on these layers, of the same order as the bedding and seating effects of the plate, and the typical LWD moduli reported for stiff granular and bound materials lie in the same range [6]. The model, which reproduces the stiffness of the layered system under the static plate, consequently over-predicts E v d on the stiff layers, and the comparison does not provide an independent constraint on the parameters of the treated layers.

3.4. Geopolymer-Treated Alternatives

Figure 8 shows the modelled E v 2 as a function of the thickness of the treated layer, for the reference layers and for the geopolymer-treated alternatives. For the stabilised subgrade (L2), E v 2 increases almost linearly with thickness, from 268 to 630 MPa between 100 and 250 mm for the reference binder, and the geopolymer-treated soil is stiffer at every thickness. The reference value at 200 mm ( E v 2 = 512 MPa) is reached by the geopolymer-treated layer at 154, 162 and 171 mm for n = 1.0 , 0.75 and 0.5, respectively, i.e., with a thickness reduction of 14–23 % (Table 5). For the treated milled concrete (L4), the reference layer gives E v 2 = 828 MPa at 200 mm. The geopolymer-treated recycled concrete gives 659–736 MPa at 100 mm and 875–1036 MPa at 150 mm, so that the equivalent thickness is 139, 126 and 115 mm for n = 0.5 , 0.75 and 1.0, i.e., a reduction of 30–42 % (Table 5). Several analyses of L4 with other thicknesses did not converge on the unloading branch, which is consistent with the very small and nearly reversible settlements of this stiff layer (Section 3.2); the equivalent thicknesses were therefore interpolated between 100 and 150 mm.

4. Discussion

4.1. Contribution with Respect to the Research Gap

The Introduction identified three open questions: whether the parameters of a thin treated layer can be identified from a single plate test, how much the support contributes to the measured moduli, and how an alternative binder can be compared with the reference layers on a mechanical basis. The present results answer the first two directly and provide the basis for the third.
First, the complete plate curve identifies the elasto-plastic parameters of a homogeneous ground with acceptable uncertainty (L1), but for a 200 mm treated layer it identifies the stiffness of the layered system and the irreversible settlement rather than the modulus of the layer itself; this is shown quantitatively by the near-perfect correlation between the layer modulus and the support factor. Second, the support under the treated layers responded four to five times more stiffly than tests on the untreated soil indicated, so that the moduli measured on treated layers cannot be attributed to the treated material alone. Third, because the identified model reproduces the measured system response, it can be used to compare alternative layers on equal terms, in terms of the same plate test and the same support, which is how the geopolymer scenarios were built. The study also shows where the approach stops: a test at the resolution limit of the gauge (L4) and a test dominated by volumetric compaction (L3) cannot be interpreted with a shear-hardening model, and recognising these cases is itself useful for the acceptance of treated layers.
Two practical consequences follow. For construction control, the strain moduli of treated layers should be read as system indices and interpreted together with the support conditions, preferably with tests made at the same location before and after treatment. For research on alternative binders, field moduli of reference layers identified in this way provide the missing link between laboratory strengths and field stiffness, and a basis on which a trial section with a geopolymer-treated layer can be designed and evaluated.

4.2. What the Plate Curve Can and Cannot Identify

The complete plate curve constrains two quantities well: the stiffness of the system under the plate, expressed by the reloading branch, and the irreversible settlement of the first loading, which is the origin of the E v 2 / E v 1 ratio. On the subgrade, where the tested material extends over the whole depth of influence, the elastic modulus is identified with a coefficient of variation of 13 %. The plastic parameters are much less certain because cohesion and hardening act together in producing the irreversible settlement, and the friction angle cannot be identified at all from a single test at one plate size. This agrees with earlier inverse analyses of plate tests, which found that only a subset of the model parameters can be back-calculated and that the others must be assigned from laboratory tests or from the literature [12].
On the treated layers the limitation is more fundamental. The modulus of a 200 mm layer and the stiffness of its support are almost perfectly correlated in the identification (correlation coefficient − 0.99 for L2): a stiffer layer on a softer support and a softer layer on a stiffer support reproduce the same curve to within the gauge resolution. The plate test therefore measures the stiffness of the layered system rather than that of the treated layer, which is the very limitation of E v 2 discussed in the Introduction, now expressed in terms of parameters. This is a direct manifestation, for a layered treated structure, of the non-uniqueness of settlement-based inversion demonstrated for stiffness profiles in [16]. The layer modulus can be separated from the support only with additional, independent information: tests with plates of different diameters, which sample different depths [16], LWD tests made at the same location before and after treatment, or laboratory moduli of the treated material. The LWD tests made on the same layers do not remove this ambiguity: on the stiff treated layers, the measured dynamic moduli saturate at 93–177 MPa and are not sensitive to the stiffness of the layer (Section 3.3). For acceptance and design, the robust outputs of the identification are thus the system stiffness, the irreversible settlement at the test pressure and, on homogeneous ground, the modulus of the tested material.

4.3. Effective Stiffness of the Support Under Treated Layers

The stiffness measured on the treated layers could not be reproduced with the support moduli inferred from LWD tests on the soil before treatment, whatever the stiffness assigned to the treated layer. The LWD tests made on the treated surface ( E v d = 93 –115 MPa on L2) independently confirm that the whole system was stiff. The identified support factors, k = 4.65 for L2 and k = 4.54 for L4, indicate that the material under the treated layers responded four to five times more stiffly than the LWD tests on the untreated soil suggested; for L3 the factor reached its upper bound, which is part of the evidence that this test is not described by the model (Section 3.2).
Three mechanisms can explain this, and they are not mutually exclusive; LWD and static moduli are in any case known to depend strongly on the stress level and on the stiffness of the underlying layers [8,9]. The binder and the reduction of moisture during mixing and compaction can partially treat and dry the soil beneath the nominal thickness; the compaction of the overlying layers preloads the soil and leaves it in an overconsolidated, stiffer state [42]; the actual mixing depth can exceed the nominal 200 mm; and the soil modulus is stress-dependent, so that LWD tests made on the untreated soil at a lower and shorter stress underestimate the stiffness mobilised under a static plate on a treated layer. Because of the E–k correlation discussed above, part of the stiffening attributed to the support may also belong to the layer itself. Whatever the split, the practical consequence is that the design or back-calculation of treated layers built on soft subgrades should not take the support modulus from tests on the untreated soil.

4.4. Limits of the Material Model

The extended Drucker–Prager model with isotropic hardening reproduces the first loading and the reloading stiffness but not the hysteresis of the unloading branch. The measured unloading of the subgrade is strongly non-linear, with most of the recovery occurring at the lowest stresses, which points to time-dependent rebound and to a stress-dependent unloading stiffness. A model with kinematic hardening, or a hardening-soil type model with a stress-dependent unloading–reloading modulus [43], would capture this better, at the cost of more parameters that a single test cannot constrain. Because E v 2 is computed from the reloading branch, this limitation affects the E v 2 match less than the unloading residuals suggest.
The model also needed a hardening modulus for numerical convergence at the edge of the rigid plate, because perfectly plastic solutions did not converge beyond about 0.16 MPa. The identified hardening ratios ( h = 0.18 for the subgrade, 0.010 for L2 and 0.013 for L4) lie above the lower bound of the search range (0.005), so the hardening is supported by the data rather than imposed by the numerics, although for the treated layers the identified values are close to that bound and the irreversible settlement is controlled mainly by the cohesion. The computed fields (Figure 6, Figure 7, Figure 8 and Figure 9) show the qualitative difference between the cases: on the subgrade, plastic straining starts at the plate edge and extends to a depth of about 0.7 m, whereas on the stabilised subgrade it is confined to the treated layer near the plate edge and the soil below remains elastic.

4.5. Implications for Geopolymer-Treated Layers

With the conservative strengths adopted, the geopolymer-treated layers reach the stiffness of the built layers with 14–23 % less thickness for the stabilised soil and 30–42 % less for the recycled-concrete base. The sensitivity to the modulus–strength exponent is moderate for the soil (154–171 mm), because the plate response of a 200 mm layer on a stiff support depends on the layer modulus only weakly, as shown by the E–k correlation; for the same reason, the equivalent thicknesses are governed as much by the assumed support as by the material. They should therefore be read as estimates of the potential of the alternative binders under the same construction and support conditions, not as design thicknesses.
The scenarios rest on two assumptions that should be tested in the field: that the modulus–strength scaling calibrated on the hydraulic-binder layers applies to geopolymer-treated layers, and that the support stiffening observed under the hydraulic binders also occurs under a geopolymer treatment. Both are plausible for a binder mixed in place, but a trial section with a geopolymer-treated layer on the same track would turn the scenario into a test. Moreover, the geopolymer strengths used here come from laboratory mixtures with higher binder contents than the 3–3.5 % of the commercial binders; equal-dosage comparisons, for example with locally available fly ash, are needed before the thickness reductions can be used in design.

5. Conclusions

The complete loading–unloading–reloading curves of static plate load tests made during the construction of the ALT-LIRA test track were back-analysed with a verified axisymmetric finite-element model in order to identify the parameters of the subgrade and of three hydraulically treated layers. The main conclusions are as follows.
  • On a homogeneous subgrade, the complete curve identifies the elastic modulus with a coefficient of variation of 13 % and reproduces E v 1 and E v 2 within 3 % and 9 %; cohesion and hardening are identified only in combination.
  • On a 200 mm treated layer, the test identifies the stiffness of the layered system rather than that of the layer: the layer modulus and the support factor are almost perfectly correlated ( r = − 0.99 ), so that a single plate test cannot separate them.
  • The support under the treated layers responded 4.5–4.7 times more stiffly than tests on the untreated soil indicated. Design and back-calculation of treated layers on soft subgrades should therefore not take the support modulus from tests made before treatment.
  • Two of the four tests lie outside the scope of the method: the test on the treated milled concrete is at the resolution limit of the dial gauge, and the test on the treated sandy gravel is dominated by volumetric compaction, which requires a model with a compaction cap.
  • The simulated light-weight deflectometer reproduces the measured dynamic modulus of the subgrade within 30 %, but on the treated layers the measured E v d saturates at 93–177 MPa, three to five times below the static reloading moduli; with a 10 kg falling weight, the LWD is not a discriminating acceptance test for stiff treated layers.
  • Under the same support and construction conditions, geopolymer-treated layers with literature strengths would reach the plate response of the built layers with 154–171 mm instead of 200 mm for the stabilised soil and with 115–139 mm for the recycled-concrete base; these values are estimates of potential, conditional on the modulus–strength scaling and on equal-dosage field validation.
Further work should combine plate tests of different diameters, LWD tests before and after treatment and laboratory moduli of the treated materials, and should test the geopolymer scenarios on a trial section of the same track.

Author Contributions

Conceptualization, F.-E.Ţ., G.-R.G. and S.-C.I.; methodology, F.-E.Ţ. and G.-R.G.; software, F.-E.Ţ.; validation, S.-C.I. and D.-N.D.; formal analysis, F.-E.Ţ. and G.-R.G.; investigation, S.-C.I., D.-N.D. and C.R.; resources, D.U., C.O. and S.-V.H.; data curation, G.-R.G.; geopolymer materials review, D.-D.B.-N.; writing—original draft preparation, F.-E.Ţ. and G.-R.G.; writing—review and editing, S.-C.I., D.-D.B.-N., D.-N.D., C.R., D.U., C.O. and S.-V.H.; visualization, F.-E.Ţ. and S.-V.H.; supervision, D.U. and S.-V.H.; project administration, G.-R.G. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Data Availability Statement

The digitised plate load and LWD records, the consistency checks, the MAPDL input files, the verification solutions and the computed fields will be deposited in the Zenodo repository upon acceptance of the article; until then they are available from the corresponding authors on reasonable request. The original field records are reported in [2,3]; they are used with the permission of their authors.

Acknowledgments

The authors thank Dr. Eng. Didi Hoha, whose experimental programme on the ALT-LIRA test track, carried out within a doctoral thesis at the Gheorghe Asachi Technical University of Iaşi under the supervision of Prof. Dr. Eng. Nicolae Ţăranu, provided part of the field records analysed in this study, and for the permission to use these data. The authors also thank Dr. Eng. Ştefan Vladimir Zghibarcea (Holcim Romania), whose doctoral thesis on the same test track [3] provided the structures of the experimental sectors and the plate load, LWD and accelerated loading records used in this study, and for the permission to use these data.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
ALT-LIRA Circular accelerated pavement testing facility (Iaşi)
CV Coefficient of variation
FE Finite element
LWD Light-weight deflectometer
UCS Unconfined compressive strength

References

  1. Ungureanu, D.; Ţăranu, N.; Hoha, D.; Zghibarcea, Ş.; Isopescu, D.N.; Boboc, V.; Oprişan, G.; Scutaru, M.C.; Boboc, A.; Hudişteanu, I. Accelerated testing of a recycled road structure made with reclaimed asphalt pavement material. Constr. Build. Mater. 2020, 262, 120658. [Google Scholar] [CrossRef]
  2. Hoha, D. Soluţii eficiente din materiale reciclabile pentru structuri rutiere. Phd thesis, Gheorghe Asachi Technical University of Iaşi, Iaşi, Romania, 2021. [Google Scholar]
  3. Zghibarcea, Ş.V. Soluţii sustenabile din materiale stabilizate şi reciclabile pentru structuri rutiere. Phd thesis, Gheorghe Asachi Technical University of Iaşi, Iaşi, Romania, 2021. [Google Scholar]
  4. DIN. Soil – Testing Procedures and Testing Equipment – Plate Load Test. DIN 18134; Deutsches Institut für Normung. Berlin, Germany, 2012. [Google Scholar]
  5. FGSV. Technische Prüfvorschriften für Boden und Fels im Straßenbau (TP BF-StB), Teil B 8.3: Dynamischer Plattendruckversuch mit Hilfe des Leichten Fallgewichtsgerätes; Forschungsgesellschaft für Straßen- und Verkehrswesen: Köln, Germany, 2012. [Google Scholar]
  6. Duddu, S.R.; Chennarapu, H. Quality control of compaction with lightweight deflectometer (LWD) device: a state-of-art. Int. J. Geo-Eng. 2022, 13. [Google Scholar] [CrossRef]
  7. Vennapusa, P.K.R.; White, D.J. Comparison of Light Weight Deflectometer Measurements for Pavement Foundation Materials. Geotech. Test. J. 2009, 32, 239–251. [Google Scholar] [CrossRef]
  8. Mooney, M.A.; Miller, P.K. Analysis of Lightweight Deflectometer Test Based on In Situ Stress and Strain Response. J. Geotech. Geoenvironmental Eng. 2009, 135, 199–208. [Google Scholar] [CrossRef]
  9. Marradi, A.; Pinori, U.; Betti, G. Subgrade and Foundation Dynamic Performance Evaluation by Means of Lightweight Deflectometer Tests. Transp. Res. Rec. J. Transp. Res. Board 2014, 2457, 51–57. [Google Scholar] [CrossRef]
  10. Mikolainis, M.; Ustinovičius, M.; Sližytė, D.; Zhilkina, T. ANALYSIS OF STATIC AND DYNAMIC DEFORMATION MODULUS. Eng. Struct. Technol. 2016, 8, 79–84. [Google Scholar] [CrossRef]
  11. Choi, Y.J.; Ahn, D.; Nguyen, T.H.; Ahn, J. Assessment of Field Compaction of Aggregate Base Materials for Permeable Pavements Based on Plate Load Tests. Sustainability 2018, 10, 3817. [Google Scholar] [CrossRef]
  12. Ahn, J.; Cote, B.M.; Robinson, B.; Gabr, M.A.; Borden, R.H. Inverse Analysis of Plate Load Tests to Assess Subgrade Resilient Modulus. Transp. Res. Rec. J. Transp. Res. Board 2009, 2101, 110–117. [Google Scholar] [CrossRef]
  13. Son, M.; Jung, H.; Yoon, H.; Sung, D.; Kim, J. Numerical Study on Scale Effect of Repetitive Plate-Loading Test. Appl. Sci. 2019, 9, 4442. [Google Scholar] [CrossRef]
  14. Li, W.; Tao, Q.; Gu, R.; Li, C.; Dai, G.; Gong, W. Plate Size Effects in Gravelly Soil Based on In Situ Plate Load Tests and Finite Element Analysis. Appl. Sci. 2025, 15, 760. [Google Scholar] [CrossRef]
  15. Ledesma, A.; Gens, A.; Alonso, E. Estimation of parameters in geotechnical backanalysis — I. Maximum likelihood approach. Comput. Geotech. 1996, 18, 1–27. [Google Scholar] [CrossRef]
  16. Pelekis, P.C.; Osmani, G.L.; Depountis, N.K. On the Non-Uniqueness of the Settlement-Based Inverse Problem in Recovering Soil Modulus Profiles from Plate Bearing Test Data: The Case for a Simplified, Poisson Ratio-Calibrated Inversion Method. Geotechnics 2026, 6, 85. [Google Scholar] [CrossRef]
  17. Zghibarcea, Ş.; Ungureanu, D.; Ţăranu, N.; Hoha, D.; Polcovnicu, R.; Leizeriuc, T. Cold in-place recycling of aged and deteriorated asphalt and concrete pavements. IOP Conf. Ser. Mater. Sci. Eng. 2021, 1182, 012084. [Google Scholar] [CrossRef]
  18. Gonzalo-Orden, H.; Linares-Unamunzaga, A.; Pérez-Acebo, H.; Díaz-Minguela, J. Advances in the Study of the Behavior of Full-Depth Reclamation (FDR) with Cement. Appl. Sci. 2019, 9, 3055. [Google Scholar] [CrossRef]
  19. Arulrajah, A.; Piratheepan, J.; Disfani, M.M. Reclaimed Asphalt Pavement and Recycled Concrete Aggregate Blends in Pavement Subbases: Laboratory and Field Evaluation. J. Mater. Civ. Eng. 2014, 26, 349–357. [Google Scholar] [CrossRef]
  20. Mohammadinia, A.; Arulrajah, A.; Disfani, M.M.; Darmawan, S. Small-Strain Behavior of Cement-Stabilized Recycled Concrete Aggregate in Pavement Base Layers. J. Mater. Civ. Eng. 2019, 31. [Google Scholar] [CrossRef]
  21. Aytekin, B.; Mardani-Aghabaglou, A. Sustainable Materials: A Review of Recycled Concrete Aggregate Utilization as Pavement Material. Transp. Res. Rec. J. Transp. Res. Board 2021, 2676, 468–491. [Google Scholar] [CrossRef]
  22. Jones, D.; Wu, R.; Louw, S. Comparison of Full-Depth Reclamation with Portland Cement and Full-Depth Reclamation with No Stabilizer in Accelerated Loading Test. Transp. Res. Rec. J. Transp. Res. Board 2015, 2524, 133–142. [Google Scholar] [CrossRef]
  23. Fedrigo, W.; Visser, A.T.; Steyn, W.J.; Núñez, W.P. Flexural behaviour of lightly cement stabilised materials: South Africa and Brazil. Road Mater. Pavement Des. 2019, 22, 397–422. [Google Scholar] [CrossRef]
  24. Jeremiah, J.J.; Abbey, S.J.; Booth, C.A.; Kashyap, A. Geopolymers as Alternative Sustainable Binders for Stabilisation of Clays—A Review. Geotechnics 2021, 1, 439–459. [Google Scholar] [CrossRef]
  25. Abdila, S.R.; Abdullah, M.M.A.B.; Ahmad, R.; Burduhos Nergis, D.D.; Rahim, S.Z.A.; Omar, M.F.; Sandu, A.V.; Vizureanu, P.; Syafwandi. Potential of Soil Stabilization Using Ground Granulated Blast Furnace Slag (GGBFS) and Fly Ash via Geopolymerization Method: A Review. Materials 2022, 15, 375. [Google Scholar] [CrossRef] [PubMed]
  26. Tiyasangthong, S.; Yoosuk, P.; Krosoongnern, K.; Sakdinakorn, R.; Tabyang, W.; Phojan, W.; Suksiripattanapong, C. Stabilization of Recycled Concrete Aggregate Using High Calcium Fly Ash Geopolymer as Pavement Base Material. Infrastructures 2022, 7, 117. [Google Scholar] [CrossRef]
  27. Hoy, M.; Traiyasut, C.; Horpibulsuk, S.; Chinkulkijniwat, A.; Suddeepong, A.; Buritatum, A.; Yaowarat, T.; Julvorawong, M.; Savetviwat, T. Strength Development of Bottom Ash-Based Geopolymer-Stabilized Recycled Concrete Aggregate as a Pavement Base Material. Coatings 2025, 15, 935. [Google Scholar] [CrossRef]
  28. Hugo, F.; Epps Martin, A. Significant Findings from Full-Scale Accelerated Pavement Testing. In NCHRP Synthesis 325; Transportation Research Board: Washington, DC, USA, 2004. [Google Scholar] [CrossRef] [PubMed]
  29. Steyn, W.J.v. Significant Findings from Full-Scale Accelerated Pavement Testing. In NCHRP Synthesis 433; Transportation Research Board: Washington, DC, USA, 2012. [Google Scholar] [CrossRef] [PubMed]
  30. CNADNR. AND 530–2012: Instrucţiuni privind controlul calităţii terasamentelor, Anexa 4 – Metode rapide de teren pentru estimarea capacităţii portante şi a gradului de compactare [Instructions for the quality control of earthworks, Annex 4 – Rapid field methods for estimating bearing capacity and degree of compaction]. Compania Naţională de Autostrăzi şi Drumuri Naţionale din România: Bucharest, Romania, 2012. [Google Scholar]
  31. Ansys, Inc. Ansys Mechanical APDL Element Reference, Release 2025 R2; Ansys, Inc.: Canonsburg, PA, USA, 2025. [Google Scholar]
  32. Drucker, D.C.; Prager, W. Soil mechanics and plastic analysis or limit design. Q. Appl. Math. 1952, 10, 157–165. [Google Scholar] [CrossRef]
  33. Ansys, Inc. Ansys Mechanical APDL Material Reference, Release 2025 R2; Ansys, Inc.: Canonsburg, PA, USA, 2025. [Google Scholar]
  34. Burmister, D.M. The General Theory of Stresses and Displacements in Layered Systems. I. J. Appl. Phys. 1945, 16, 89–94. [Google Scholar] [CrossRef]
  35. McKay, M.D.; Beckman, R.J.; Conover, W.J. Comparison of Three Methods for Selecting Values of Input Variables in the Analysis of Output from a Computer Code. Technometrics 1979, 21, 239–245. [Google Scholar] [CrossRef]
  36. Levenberg, K. A method for the solution of certain non-linear problems in least squares. Q. Appl. Math. 1944, 2, 164–168. [Google Scholar] [CrossRef]
  37. Marquardt, D.W. An Algorithm for Least-Squares Estimation of Nonlinear Parameters. J. Soc. Ind. Appl. Math. 1963, 11, 431–441. [Google Scholar] [CrossRef]
  38. Yang, C.; Jiang, Y.; Li, Z.; Huang, Y.; Yue, J. Research on the Pavement Performance of Slag/Fly Ash-Based Geopolymer-Stabilized Soil. Materials 2025, 18, 3173. [Google Scholar] [CrossRef] [PubMed]
  39. Bai, L.; Yang, Z.; Wu, Y.; Anbarlouie, M.; Pan, Z. Stabilization of Aeolian Sand for Pavement Subbase Applications Using Alkali-Activated Fly Ash and Slag. Minerals 2023, 13, 453. [Google Scholar] [CrossRef]
  40. Sofri, L.A.; Abdullah, M.M.A.B.; Sandu, A.V.; Imjai, T.; Vizureanu, P.; Hasan, M.R.M.; Almadani, M.; Aziz, I.H.A.; Rahman, F.A. Mechanical Performance of Fly Ash Based Geopolymer (FAG) as Road Base Stabilizer. Materials 2022, 15, 7242. [Google Scholar] [CrossRef] [PubMed]
  41. DiMaggio, F.L.; Sandler, I.S. Material Model for Granular Soils. J. Eng. Mech. Div. 1971, 97, 935–950. [Google Scholar] [CrossRef]
  42. Vámos, M.J.; Szendefy, J. Overconsolidated Stress and Strain Condition of Pavement Layers as a Result of Preloading during Construction. Period. Polytech. Civ. Eng. 2023. [Google Scholar] [CrossRef]
  43. Schanz, T.; Vermeer, P.; Bonnier, P. The hardening soil model: Formulation and verification. In Beyond 2000 in Computational Geotechnics; Routledge, 1999; pp. 281–296. [Google Scholar] [CrossRef]
Figure 1. Pavement structures of the experimental sectors S1–S4 and of sector S3*, with the layers tested with the static plate (L1–L4, red frames). Sector S3* (treated sandy gravel on soil 4b) is described in [2]. Thicknesses in cm.
Figure 1. Pavement structures of the experimental sectors S1–S4 and of sector S3*, with the layers tested with the static plate (L1–L4, red frames). Sector S3* (treated sandy gravel on soil 4b) is described in [2]. Thicknesses in cm.
Preprints 245728 g001
Figure 2. Static scheme of the axisymmetric model: (a) detail under the plate, showing the rigid plate of radius a, the resultant force applied according to the measured load history, the tested (treated) layer described by the extended Drucker–Prager model and the linear elastic underlying layers; (b) computational domain with its boundary conditions (not to scale).
Figure 2. Static scheme of the axisymmetric model: (a) detail under the plate, showing the rigid plate of radius a, the resultant force applied according to the measured load history, the tested (treated) layer described by the extended Drucker–Prager model and the linear elastic underlying layers; (b) computational domain with its boundary conditions (not to scale).
Preprints 245728 g002
Figure 3. Finite-element discretisation (stabilised subgrade L2, PLANE183 elements; corner nodes shown), visualised in Tecplot 360: (a) the whole computational domain ( 45 × 45 m); (b) the zone under the plate, with the 200 mm treated layer (light) and the underlying soil (dark); (c) the refinement at the plate edge ( r = 0.15 m), where the element size is a / 32 = 4.7 mm. The plate is shown in grey.
Figure 3. Finite-element discretisation (stabilised subgrade L2, PLANE183 elements; corner nodes shown), visualised in Tecplot 360: (a) the whole computational domain ( 45 × 45 m); (b) the zone under the plate, with the 200 mm treated layer (light) and the underlying soil (dark); (c) the refinement at the plate edge ( r = 0.15 m), where the element size is a / 32 = 4.7 mm. The plate is shown in grey.
Preprints 245728 g003
Figure 4. Measured (symbols) and computed (line) plate load curves with the identified parameters for the subgrade (L1), the stabilised subgrade (L2), the treated sandy gravel (L3; parameter set on the bound, not identifiable) and the treated milled concrete (L4). Settlements are measured from the start of the test; pressures refer to the 300 mm plate.
Figure 4. Measured (symbols) and computed (line) plate load curves with the identified parameters for the subgrade (L1), the stabilised subgrade (L2), the treated sandy gravel (L3; parameter set on the bound, not identifiable) and the treated milled concrete (L4). Settlements are measured from the start of the test; pressures refer to the 300 mm plate.
Preprints 245728 g004
Figure 5. Computed fields under the plate for the stabilised subgrade (L2), post-processed in Tecplot 360; panels as in Figure 6. The dashed line marks the base of the 200 mm stabilised layer.
Figure 5. Computed fields under the plate for the stabilised subgrade (L2), post-processed in Tecplot 360; panels as in Figure 6. The dashed line marks the base of the 200 mm stabilised layer.
Preprints 245728 g005
Figure 6. Computed fields under the plate for the subgrade (L1), post-processed in Tecplot 360: (a) vertical displacement at the peak of the first loading (0.5 MPa); (b) accumulated equivalent plastic strain at the same stage; (c) residual vertical displacement after unloading; (d) vertical stress increment due to the plate at the peak of the first loading. Displacements and stresses are relative to the geostatic state; the rigid plate is shown in grey.
Figure 6. Computed fields under the plate for the subgrade (L1), post-processed in Tecplot 360: (a) vertical displacement at the peak of the first loading (0.5 MPa); (b) accumulated equivalent plastic strain at the same stage; (c) residual vertical displacement after unloading; (d) vertical stress increment due to the plate at the peak of the first loading. Displacements and stresses are relative to the geostatic state; the rigid plate is shown in grey.
Preprints 245728 g006
Figure 7. Computed fields under the plate for the treated milled concrete (L4), post-processed in Tecplot 360; panels as in Figure 6. Dashed lines: base of the treated layer (0.2 m) and of the untreated sandy gravel (0.4 m).
Figure 7. Computed fields under the plate for the treated milled concrete (L4), post-processed in Tecplot 360; panels as in Figure 6. Dashed lines: base of the treated layer (0.2 m) and of the untreated sandy gravel (0.4 m).
Preprints 245728 g007
Figure 8. Modelled E v 2 as a function of the thickness of the treated layer for the reference layers (black) and for the geopolymer-treated alternatives (green; shaded band for the modulus–strength exponent n = 0.5 –1.0, dashed line for n = 0.75 ). Dotted lines: reference layer at the built thickness of 200 mm.
Figure 8. Modelled E v 2 as a function of the thickness of the treated layer for the reference layers (black) and for the geopolymer-treated alternatives (green; shaded band for the modulus–strength exponent n = 0.5 –1.0, dashed line for n = 0.75 ). Dotted lines: reference layer at the built thickness of 200 mm.
Preprints 245728 g008
Figure 9. Three-dimensional view of the response of the stabilised subgrade (L2) at the peak of the first loading, rendered as in Figure 10: (a) vertical displacement; (b) accumulated equivalent plastic strain, confined to the 200 mm stabilised layer.
Figure 9. Three-dimensional view of the response of the stabilised subgrade (L2) at the peak of the first loading, rendered as in Figure 10: (a) vertical displacement; (b) accumulated equivalent plastic strain, confined to the 200 mm stabilised layer.
Preprints 245728 g009
Figure 10. Three-dimensional view of the subgrade response (L1) at the peak of the first loading, obtained by revolving the axisymmetric solution about the plate axis (270°, one quadrant removed) and rendered in Tecplot 360: (a) vertical displacement; (b) accumulated equivalent plastic strain. Window: radius and depth of 0.8 m.
Figure 10. Three-dimensional view of the subgrade response (L1) at the peak of the first loading, obtained by revolving the axisymmetric solution about the plate axis (270°, one quadrant removed) and rendered in Tecplot 360: (a) vertical displacement; (b) accumulated equivalent plastic strain. Window: radius and depth of 0.8 m.
Preprints 245728 g010
Table 1. Target strain moduli of the static plate tests used in the identification.
Table 1. Target strain moduli of the static plate tests used in the identification.
Layer E v 1 (MPa) E v 2 (MPa)
L1 19.92 38.71
L2 229.1 443.2
L3 128.3 576.61
L4 635.6 not determinable2
1 E v 2 = 269.43 MPa printed in [3] (Table 5.16) is a transcription error. 2 Not determinable at the gauge resolution.
Table 2. Strain moduli of the subgrade (L1): measured and computed with the identified parameters.
Table 2. Strain moduli of the subgrade (L1): measured and computed with the identified parameters.
Measured (MPa) Model (MPa) Difference
E v 1 19.9 20.5 + 2.8  %
E v 2 38.7 42.2 + 8.9  %
Table 3. Identified parameters and fit statistics. Coefficients of variation from the linearised covariance in parentheses; ϕ fixed.
Table 3. Identified parameters and fit statistics. Coefficients of variation from the linearised covariance in parentheses; ϕ fixed.
Layer E (MPa) k (–) c (kPa) h (–) RMS (mm) E v 1 meas./model (MPa) E v 2 meas./model (MPa)
L1 41 (13 %) – 36 (60 %) 0.18 (37 %) 0.30 19.9/20.5 38.7/42.2
L2 7376 (323 %) 4.65 (148 %) 84 (63 %) 0.010 (42 %) 0.018 229/225 443/511
L31 182 20 (bound) 75 0.031 0.076 128/109 577/279
L42 14,480 (260 %) 4.54 (86 %) 45 (203 %) 0.013 (234 %) 0.028 636/457 n.d./828
1 Not identifiable with the shear-hardening model (support factor on its bound). 2 Test at the resolution limit of the dial gauge; n.d.: not determinable.
Table 4. Dynamic modulus of the light-weight deflectometer: computed with the identified parameters (linear transient analysis) and measured on the same layers, with the static E v 2 for reference.
Table 4. Dynamic modulus of the light-weight deflectometer: computed with the identified parameters (linear transient analysis) and measured on the same layers, with the static E v 2 for reference.
Layer E v d computed (MPa) E v d measured (MPa) Ratio computed/measured E v 2 measured (MPa)
L1 47.8 34.8–37.3 1.3 38.7
L2 672 93.0–115.4 6.4 443
L31 317 177.2 1.8 577
L4 1177 171.8 6.9 n.d.
1 Parameters not identifiable (Section 3.2); n.d.: not determinable.
Table 5. Equivalent thickness of the geopolymer-treated layer, i.e., the thickness giving the same modelled E v 2 as the reference layer of 200 mm.
Table 5. Equivalent thickness of the geopolymer-treated layer, i.e., the thickness giving the same modelled E v 2 as the reference layer of 200 mm.
Layer E v 2 reference, 200 mm (MPa) n = 0.5 n = 0.75 n = 1.0
L2 512 171 mm ( − 14  %) 162 mm ( − 19  %) 154 mm ( − 23  %)
L4 828 139 mm ( − 30  %) 126 mm ( − 37  %) 115 mm ( − 42  %)
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.
Copyright: This open access article is published under a Creative Commons CC BY 4.0 license, which permit the free download, distribution, and reuse, provided that the author and preprint are cited in any reuse.