Submitted:
28 October 2026
Posted:
29 October 2026
You are already at the latest version
Abstract
Analysis of partial discharges (PDs) in solid dielectric systems improves the quality of cable line insulation diagnostics by identifying installation defects, aging, and other destructive factors. However, known ABC models and single-line equivalent circuits provide an approximate description of discharges, and the distribution of amplitude-phase (APD) and amplitude-frequency (AFC) characteristics of PDs does not sufficiently agree with experiments reflecting the stochastic nature of PD-related voltage pulses recorded at the sensor output. This paper proposes a block-hierarchical approach to PD modeling in a three-phase power cable line (PCL) in LTspice. The model is based on a multilevel equivalent circuit with distributed parameters (MRLCG), supplemented by an ABC defect model. The hybrid MRLCG+ABC model takes into account the mutual influence of conductors and the sheath, the sheath grounding scheme, laying geometry, wave attenuation, distributed defects, conductor-to-conductor and conductor-to-sheath mutual inductance, the proximity effect, and the skin effect. A stochastic set of PDs is obtained using the Monte Carlo method, which reproduces the nature of the discharge process and provides stable statistical estimates. The novelty lies in the comprehensive consideration of electromagnetic and topological factors within a unified hierarchical scheme. Verification on a 10 kV cable showed convergence between numerical and physical APD/AFC according to statistical criteria: a Pearson correlation coefficient of r ≥ 0.93, an average amplitude discrepancy of ≤ 15% (over 1000 cycles), and a peak-to-peak amplitude discrepancy of single pulses of ΔU = 2–3%. This improves diagnostic quality and provides a basis for future studies on predicting the residual life of insulation.
Keywords:
partial discharges
; cable line
; hierarchical model
; distributed parameters
; Monte Carlo method
; sheath voltage
1. Introduction
1.1. Problem Statement
One of the challenging tasks facing power grid companies is maintaining reliable, accident-free power supply to consumers, which largely depends on the condition of power cable lines (PCLs). Keeping cable lines in good technical condition requires continuous monitoring of the insulation strength of PCLs, which is achieved either through periodic preventive checks (tests) in the disconnected state using off-line methods, or through continuous monitoring using on-line methods, such as monitoring systems under operating current and voltage [1,2,3]. One of the most informative and accurate methods for assessing technical condition for both approaches is the electrical method of detection followed by analysis of partial discharges (PDs) in the cable line. PD analysis allows not only to ascertain the presence of dangerous defects in the insulation, but also to classify them both by the complexity (nature) of their origin and by their location. However, in practice, when detecting and analyzing PDs by the electrical method (e.g., using HFCT sensors), a number of problems are encountered, namely: the difficulty of recognizing and separating PDs from background noise, which is especially pronounced in three-phase cables; the need for calibration of monitoring systems, testing, and tuning of diagnostic system algorithms built using neural networks or fuzzy logic [4,5], and other issues. Modeling PDs in cable line insulation improves the reliability of high-voltage diagnostics and plays an important role in solving these applied problems and tasks of recognition and analysis of PD pulses, i.e., it serves as a bridge between the physical phenomenon in the insulation and the subsequent engineering solution. Creating models with a high degree of approximation to real physical processes allows one to gather a priori information about PD manifestations under given insulation defects. This will enable the collection of clusters of diagnostic features with their subsequent statistical processing. In subsequent on-line monitoring, the formed database will allow not only the presence of PDs to be identified, but also the nature and location of the defect in the insulation to be determined. For recurring defects in the same type of cable product, it will be possible to draw conclusions about systematic violations in the technological process of production, laying, or operation of PCLs.
It is known that modern complex models of PDs in cable line insulation enable the solution of fundamental problems in the physics of material degradation and its dynamics, for example, using COMSOL and more complex combined plasma models. However, these require significant computational resources and are often inaccessible to the general researcher. The study of PDs based on three-capacitance models or equivalent circuits of cable lines with lumped RLCG parameters provides only an approximate representation of PDs in insulation and often diverges significantly from experimental data. Modeling signal propagation over long distances is one of the most critical problems because, as signals propagate along the cable, high-frequency components attenuate more strongly than low-frequency ones due to resonant absorption. Consequently, at the measurement terminals of long lines, the recorded PD signals may become indistinguishable from noise or be significantly distorted compared to the original signal [6,7].
PD distortions may be related to the fact that researchers often resort to an idealized (simplified) representation of the parameters and design of the modeled line. Thus, Figure 1 shows a cross-section of a real 10 kV cable manufactured by the silane cross-linking method, in which the proximity of the screens of the cable cores is clearly visible. These design features must be taken into account when modeling PCLs, as well as other effects and factors. For example, the proximity effect directly affects the frequency characteristics and leads to a redistribution of currents in the cable insulation system. It is also important to take into account such features as: the skin effect of the conductor R(f); the influence of mutual inductance of adjacent cores and the sheath of a three-phase cable; diagnostic and grounding schemes for screens; inclusion of inhomogeneities and defects in insulation layers; and the location of measuring sensors. Neglecting these data, effects, and design features in the model is quite critical for accurate modeling of APD and AFC and subsequent comparison with experimental data.
1.2. Background Information and Relation to Other Researchers
When developing frequency-dependent line models using the equivalent circuit method with standard components of the LTSpice program, it is necessary to note a fundamental limitation of such modeling, namely the absence of ready-made blocks in LTSpice that allow for the consideration of the Proximity Effect, Skin Effect, mutual inductance of conductors/conductors and the sheath of a three-phase cable, as well as the stochasticity of PD histograms in the time domain. Solving this problem is a rather complex and non-trivial task. Often, to study wave processes in cable lines, two programs must be used simultaneously, for example, MATLAB Simulink and LTSpice complementing each other. However, such an approach often complicates the implementation of a unified qualitative analysis of PDs in the line. The authors of this article take into account and analyze previously achieved results of modeling the listed physical phenomena when developing their own hybrid model of a PCL. Thus, the result of applying the McCammon method to improve the accuracy of modeling faults in the insulation of generator stator windings, taking into account the Skin Effect (SE) and Proximity Effect (PE) in MATLAB and LTSpice [8], and the possibility of transferring the applied methodology to cable insulation modeling, were studied in detail. Using the method of finite filaments (VFM) by Clayton Paul, it is possible to obtain accurate frequency dependencies R(f) and L(f) for a three-phase cable, including mutual inductances between conductors and sheaths [9]. VFM allows for the consideration of mutual inductance in the modeled three-phase line, but it does not directly take into account the capacitive and active conductance of the cable. One of the first attempts to link the physical processes of an internal defect in insulation layers with the measured signal (apparent charge) through capacitances belongs to S. Whitehead and E. Kruger, who in 1950 described the defect using a three-capacitance PD model, which became highly popular among researchers and is known as the ABC model. For example, in [10], the model allows for the consideration of phase-resolved partial discharge (PRPD) patterns, while having significant limitations in studying the PD shape and PD propagation in the cable. To reduce these limitations, the ABC model must be supplemented or combined with other models. Models of cable lines based on RLC chains have become widespread, allowing the study of PDs taking into account the signal shape and localization of the PD source; however, this method also has limitations regarding the consideration of the mutual influence of magnetic fields between the current-carrying parts of a three-phase cable, taking into account the laying geometry and the sheath mode of the PCL [11]. Three-phase models of a power cable line based on ready-made Three-phase Programmable Voltage Source blocks from the Specialized Power Systems (SPS) library in MATLAB/Simulink allow obtaining frequency characteristics of equivalent cable modeling [12]. However, the block does not fully take into account all the previously listed phenomena and effects in the cable insulation system and is difficult to apply in LTSpice. Also well-known and widespread is the method of line modeling in LTSpice together with the finite element method (FEM) to refine the equivalent parameters of the RLCG model [13]; such an approach allows obtaining the amplitude-frequency characteristics of PDs in the line. However, due to design inaccuracies of the cable line model, discrepancies between numerical and experimental PD histograms are noted. The analysis shows that modeling a three-phase cable with a conductive sheath, taking into account frequency-dependent distributed parameters, is a multidisciplinary task, and modeling such a line using three single-phase lines is not entirely correct and leads to additional modeling error. The authors of this study have also been engaged for a long time in the study and modeling of wave processes in power cable [14] and overhead [15] transmission lines in OrCAD, LTSpice, and MATLAB/Simulink software packages, taking into account the mutual inductance of conductors/conductor-sheath, SE, and PE. The authors verify the convergence of numerical studies of high-frequency wave processes during surface and internal discharges in dielectric systems of lines with the results obtained from real objects. A systematic study of these processes and effects in the line, taking into account physical comparison of results, allowed the authors to propose in this article a refined equivalent circuit of a three-phase cable line that takes into account its design features. The hybrid equivalent circuit of series chains MRLCG+ABC based on the simple LTSpice program made it possible to qualitatively improve the accuracy of modeling time-domain PD histograms. The article presents the results of applying the numerical method (modeling) based on distributed parameter circuit theory in assessing the technical condition of PCL insulation by the PD method. The proposed PD research method allows for the consideration of the influence of the attenuation coefficient in the sheath on the line laying geometry and the sheath grounding mode. Validation of the numerical model is carried out by comparing the PD pulse shape and the peak phase angle of the APD with experimental data from real cable lines.
1.3. Methodology of Block-Hierarchical Stepwise Modeling
For the first time, for the tasks of partial discharge diagnostics in cable lines, a block-hierarchical multilevel model of a three-phase line with distributed parameters has been developed, taking into account the proximity effect, skin effect, sheath mode, test mode, and cable topology. The originality of this solution lies in the fact that the previously listed factors were considered either in isolation or within simplified models insufficient for an adequate description of wave processes in a real line. The proposed model provides a correct reproduction of the propagation and distortion of PD pulses, and also allows differentiating changes in PDs caused by insulation aging from distortions introduced by the line and the measuring system. This creates prerequisites for improving the accuracy of diagnostics and predicting the residual life of cable line insulation. The scientific novelty of the work lies in the comprehensive consideration of electromagnetic and topological factors in a unified hierarchical equivalent circuit, which ensures adequate modeling of PDs and their dynamics.
The modeling is implemented in stages. At the first stage, a model of one meter of cable line is formed on the basis of a three-phase hybrid MRLCG+ABC circuit with distributed parameters, which allows a correct description of electromagnetic processes in an elementary section of the line taking into account the mutual influence of conductors and the sheath. Such a choice of the elementary section length ensures, on the one hand, sufficient detail in describing distributed parameters, and on the other hand, the possibility of subsequent sequential extension of the model without loss of computational stability. At the second stage, the elementary sections are combined into an extended model of a cable line with a length of 100 meters, which corresponds to the conditions of the conducted experiments and allows moving from the analysis of a single discharge to the study of PD pulse propagation along a real line. It is on this model that correct consideration of attenuation, dispersion, and distortion of the pulse shape, as well as the influence of the laying topology on the recorded signal, becomes possible. The next, third stage is the modeling of the voltage on the cable sheath, since the sheath simultaneously performs the functions of a return conductor and an element of the measuring system that determines the nature of electromagnetic wave propagation. Analysis of the sheath voltage allows linking the processes occurring in the internal insulation with the signal recorded at the external terminals of the line, and thereby ensuring comparability of digital and experimental PD oscillograms. To evaluate the advantages of the proposed approach, a comparison was made between the results obtained on the refined MRLCG+ABC model and the results of a traditional series RLC circuit, which is considered as a baseline variant and a reference point in the analysis of accuracy. Such comprehensive modeling, built on the sequential complication of the equivalent circuit and stepwise verification, allows for a justified choice of the degree of model detail for a specific task and ensures the transition from a qualitative description of processes to quantitative estimates applicable in practice.
2. Materials and Methods
2.1. Refined Equivalent Circuit of the MRLCG+ABC Line
As mentioned above, PD is a fast-occurring process in which a spectrum of harmonic electromagnetic oscillations with a wide frequency range is present. As it propagates from the PD site to the registration point, each oscillation attenuates to a different degree. Ignoring the proximity effect, skin effect, sheath operating mode, line laying geometry, as well as the frequency properties of the dielectric, which contribute to the dissipation of oscillation energy and ultimately reduce the level of the recorded signal to the noise level, leads to the registration of false pulses unrelated to PDs or to the loss of true information about the nature of the partial discharge.
When modeling high-frequency wave processes in PCLs, it is critically important for the study and analysis of PDs to take into account the frequency-dependent parameters of the line. Excluding such parameters from the equivalent circuit leads to a decrease in modeling accuracy and lower convergence between experimental data and numerical simulation results. To study PDs in a three-phase power cable line, the authors propose using a synergistic effect obtained by combining equivalent circuits that have been well studied separately, namely, the cable line represented by a series RLCG circuit, the considered insulation defect model based on the ABC model, and taking into account the mutual inductance (M) of conductor/conductor-sheath. The refined equivalent circuit of a three-phase power cable line is shown in Figure 2, where: MAB, MBC, MAC are the mutual inductances between the conductors of the corresponding phases of the cable line; MAO, MBO, MCO are the mutual inductances between the conductor of the corresponding phase and the sheath.
2.2. Configuration of the Numerical Model of the MRLCG+ABC Cable Line in LTspice
This paper presents the simulation results of wave processes in a cable line using a block-hierarchical approach for PD dynamics in a three-phase power cable line within the LTspice environment. A detailed demonstration of the block-hierarchical construction for three-phase models is omitted. The full parameter matrix (mutual inductances (M), SE, PE, cable geometry, per-unit-length parameters, ABC defect model parameters, and LTspice settings) has already been thoroughly documented in the authors’ previous publications referenced in Section 1.2. Since the model parameters are utilized without modification, their repeated description is avoided to prevent redundancy. The block-hierarchical model of a power cable line contains a multilevel equivalent circuit of the cable line (Figure 2), where at the highest level (Level 1) there is the equivalent circuit of the line with distributed parameters, represented as series-connected hierarchical blocks; inside each block (sublevel – Level 2) there are cascades of an improved frequency-dependent equivalent circuit of the cable line with lumped parameters of a cable line segment (MRLCG) including the ABC model of the insulation defect; one level lower (Level 3) there are freely parameterized cascade chains MRLCG+ABC. This representation of modeling discharges in PCLs allows obtaining and studying not only internal PDs in the solid insulation layers of the cable, but also surface PDs, for example, between the conductor and the sheath, which is achieved by the corresponding arrangement of programmable discharge control switches in the model.
Such a representation of a PCL makes it possible to improve modeling accuracy by taking into account in the model the design features of three-phase cable lines, the formation of the random (stochastic) nature of PDs, the operating mode of the cable line, the sheath, and the laying geometry.
Figure 3.
Block-hierarchical multilevel equivalent circuit of a cable line for studying wave processes.
Figure 3.
Block-hierarchical multilevel equivalent circuit of a cable line for studying wave processes.

This representation of the PCL improves modeling accuracy by accounting for the design features of three-phase cable lines, the stochastic nature of PD generation, the cable line operating mode, the sheath, and the laying geometry. The simulation results were verified against oscillograms of PD signals from real cable lines of various lengths. The verification of the digital (simulated) and analog (experimental) PD signals in the PCL was performed according to the following criteria: qualitative agreement, specifically the coincidence of the shape of single PD current pulses in the model and experiment (aperiodic considering polarity, or damped oscillatory); the shape and stochasticity of the temporal distribution of PD signal amplitudes, specifically the sequence of discharge histogram shapes in the cable; and the correspondence of the phase angles of the occurring discharges. It should also be noted that the proposed model accounts for important aspects such as the line operating mode, the test (measurement) setup, and the sheath grounding mode. In practice, insulation monitoring is performed both under operating voltage—operating mode 1 (on-line methods)—and in a disconnected state—operating mode 2 (off-line methods). Operating modes 1 and 2 can be characterized by different connection schemes of the cable conductors and sheaths; for example, in the high-voltage test mode (operating mode 2), the conductors at the cable end are open, and at the El.t.lab connection point the free conductors are grounded (Figure 4); in the operating state (mode 1), the cable sheaths are grounded based on design conditions.
2.3. Methodology of PD Measurements on a One-Meter PCL Segment
To refine the parameters of the MRLCG+ABC equivalent circuit of the numerical cable line model by comparing numerical and experimental PDs, a 1-meter segment was chosen as the elementary section of the line. The attenuation of electromagnetic waves over 1 m of a real cable in the frequency range from hundreds of kHz to tens of MHz is 0.001–0.01 dB/m, which corresponds to minimal losses and is not critical for the study of wave processes at this length. A one-meter segment is electrically short for PDs (travel time ~6.25 ns); therefore, the defect position along the segment does not significantly affect the shape, amplitude, and qualitative pattern of the PDs. The location of the SW switch was chosen for modeling convenience, and the adequacy criterion is the matching of amplitude, phase, and pulse shape, rather than the coordinate. For extended lines, accounting for the position becomes essential. This allows the selected segment to be considered as a basic element of the model, the parameters of which are subsequently used in constructing an extended line model. A comparison of the experimental and numerical PD results was performed for a one-meter cable line segment. Signals were recorded with an oscilloscope having a bandwidth of 100 MHz while an alternating voltage of 8–15 kV at 50 Hz was applied from a high-voltage installation for at least 15 minutes. Varying the applied voltage range made it possible to record changes in discharge intensity—from single PDs to a series of discharges in time intervals (histograms). The PCL model in LTspice is represented by ten series-connected hierarchical blocks, each containing an equivalent circuit of a 0.1 m length of three-phase cable, similar to Figure 2 and Figure 3. The stochastic nature of the PDs was implemented using the Monte Carlo method with the following random parameters: the inception delay time (exponential distribution, λ=1/τmean), the discharge amplitude (truncated Gaussian distribution), and the defect capacitance (uniform distribution within the geometric tolerance). The residual charge Qres was modeled with an exponential decay (τmem≈10 ms) to reproduce the memory effect between half-periods. The number of realizations was set to Nreal=1000 for each voltage level. The convergence criterion was defined as a relative change of less than 5% in both the mean value and the 95th percentile of the amplitudes when doubling NrealNreal. Subsequently, the numerical PD simulation results were compared with the measured PD signals for the XLPE insulation of an APvPug-10 kV cable line that had been in long-term operation and contained electrical trees. The comparison was performed using criteria based on the AFC, APD, and the qualitative pattern of a series of random PDs (stochasticity). The schematic diagram of the PD measurement setup is shown in Figure 5a.
As the main testing and measuring equipment shown in Figure 5b, the following were adopted: 1 – control unit of the high-voltage source SKAT-70M and high-voltage unit – 2; 3 – high-voltage kilovoltmeter ProfKIP S100M; 4 – two-channel oscilloscope FNIRSI 1013D; 5 – high-frequency current transformer RFCT-5 [16] installed in the grounding conductor of the cable – 6.
The PD signals were recorded using a two-channel digital oscilloscope. Channel 1 (Ch 1) was connected to the output of a high-frequency current transformer (RFCT-5) installed on the sheath of the tested APvPug-10 kV cable. Measurements were performed using the oscilloscope and RFCT-5 without calibration in terms of apparent charge. The amplitudes are given in millivolts (mV) and reflect the relative intensity of the PD signals; the absolute apparent charge according to IEC 60270:2025 was not measured. This does not affect the research objectives, as the study analyzes the shapes, statistical distributions, and relative amplitudes of PDs, rather than performing a metrologically strict charge measurement in pC. Channel 2 (Ch 2) was used to synchronize the measurements with the phase of the applied test voltage. This input received a signal from the built-in high-voltage divider of the SKAT-70M test setup, which is connected to the output high-voltage terminal and generates a signal proportional and in phase with the applied 50 Hz voltage. The oscilloscope sweep was synchronized via Ch 2 at the zero-crossing of the signal, which ensured a stable alignment of the recording time window with the supply voltage period. This connection scheme allowed the simultaneous recording of PD pulse amplitudes (Ch 1) and their position relative to the test voltage phase (Ch 2) for the subsequent construction of amplitude-phase diagrams (APDs).
2.4. Methodology of PD Measurements on a One-Hundred-Meter PCL Segment
The equipment and methodology for verifying the experimental and numerical PD results for a 100-meter segment of the APvPug-10 kV cable line were similar to those in Section 2.3; the test bench is shown in Figure 6.
The model of the APvPug-10 kV cable line was implemented in the LTspice software package as 33 series-connected hierarchical blocks (Figure 3, Level 1). Each block (Level 2) contains three series-connected one-meter segments of the hybrid equivalent circuit MRLCG+ABC, forming three meters of the modeled cable; the 33rd block contains four such segments. Thus, the 33 blocks together form a power cable line with a length of 100 m based on an equivalent circuit with distributed MRLCG parameters, which provides the possibility of forming distributed insulation defects with a step of 1 m based on the ABC model.
During high-voltage tests on a 100-meter segment of the APvPug-10 kV cable line, both surface PDs developing at the interface between two media (XLPE–air) in the direction from the conductor to the sheath under single-sided sheath grounding, and internal PDs in the cable insulation were recorded. The test bench allows both types of discharges to be recorded, which makes it possible to compare their characteristics with the modeling results. Examples of recording PD histograms in the sheath of a 100-meter cable are shown in Figure 7.
2.5. Influence of Cable Line Topology on PD Measurement in the Sheath
An important task in assessing the sheath voltage (U_sh) relative to ground during PD measurement or operation is the analysis of the voltage at the open end of the cable line sheath in normal mode or in short-circuit (SC) mode, since the value of U_sh often requires additional measures and protections that directly depend on the line operating mode and can significantly affect noise. Different countries have different methodologies and standards defining the value of U_sh; for example, in TCP 611-2017 (Belarus) it is specified that in normal mode the sheath voltage (U_sh) should not exceed 25 V for the “flat” laying type (consistent with the requirement in Russia), while Schneider Electric documentation for 6–35 kV power cable lines with XLPE insulation recommends a value of no more than 50 V; however, there is no unified methodology for determining U_sh that takes into account the design features of cable lines, for example, for three-phase or drum-type cables (special cables (N)TSCGEWOU 6/10 kV). Modeling of U_sh can serve as an alternative or additional method for checking the sheath voltage relative to ground, taking into account the winding density or the combined flat/drum type of operation with different ratios of the geometric laying factor F(β). In the model, this can be achieved by changing the distributed mutual inductance along the cable length (existing methodologies take into account the absolute mutual inductance of the line or, as a rule, the total one). The cable laying method (flat/drum) and the sheath grounding mode significantly affect U_sh, because in this case the cable on a drum is a multi-turn coil–choke, and the sheath, ungrounded on one side, is essentially an antenna. The mutual inductance between the conductor and the sheath M_sh is proportional to the square of the number of turns of the coil N2, and since the sheath is grounded on one side, the demagnetizing effect disappears, and the conductor field induces an additional EMF on the sheath along the entire cable length; therefore, even at insignificant load currents, U_sh can exceed hundreds of volts or even kilovolts, in contrast to flat-type laying, where U_sh is mainly determined by the cable length and the capacitive coupling between the conductor and the sheath, and the influence of mutual inductance with such laying is minimal. The mutual inductance of the conductor and the cable sheath for flat-type laying averages about 0.15–0.18 µH/m (refined experimentally); for drum-type laying it increases proportionally to N2 of the number of coil turns.
2.6. Methodology for PD Measurement in a PCL with Capacitive Decoupling of the Sheath
For the measurement and verification of partial discharges in solid XLPE insulation layers, the cable line sheath is solidly grounded on the source side, and on the other side it is grounded through a capacitor C of type K15-4 N70 470 pF 40 kV (Figure 8a); the HFCT is connected on the capacitor side, and the measurement scheme is shown in Figure 8b.
The presented scheme for recording PD signals in a cable line with a capacitor in the sheath circuit makes it possible to significantly reduce the antenna effect on the sheath and performs the function of high-frequency (HF) decoupling. Connection through a capacitor with a capacitance of 470 pF provides reliable grounding of the sheath at high frequencies of the measured PD and does not overload the measuring circuit with power-frequency currents: the capacitor’s own capacitive reactance at f = 50 Hz is 6.8 MΩ, which is equivalent to an open circuit, whereas for PDs at f = 1 MHz, Xc is 338 Ω, which practically corresponds to a short circuit and creates an unobstructed channel for the HF signal. The nominal voltage of the capacitor, 40 kV, provides a high-voltage safety margin with respect to the applied voltage and maintains operability during voltage surges and PD pulses. Connecting the HFCT into the sheath circuit on the capacitor side allows recording HF PD pulses in the cable sheath.
3. Results
3.1. Verification of LTspice PD Simulation Results for a One-Meter Segment
During high-voltage experiments according to the scheme in Figure 5a, surface PDs were recorded along the interface between two dielectric media of the cable (XLPE insulation and air). The discharge was recorded in the gap between the conductor and the conductive water-blocking tape of the APvPug-10 cable; its occurrence is due to the transfer of copper shavings, formed during cable termination, from the shielding wire to the water-blocking tape. The measured surface PDs from the conductor to the cable tape (Figure 9) were also modeled for the purpose of model verification. Modeling of such PDs is carried out by shunting a portion of the insulation between the cable conductor and the conductive copper sheath (which follows immediately after the water-blocking tapes); in the model, this is implemented by installing a controlled switch SW in LTSpice (Level 1) between the conductor and the conductive sheath (screen). The result of comparing the amplitude-phase diagram of the numerical and experimental single surface PD over 1 meter of cable length is shown in Figure 9. The stability of the statistical estimates was tested at Nreal = 100, 500, 1000, 2000, and 5000. The mean value and the 95th percentile of the amplitudes stabilize at Nreal≈1000 (change < 2% with a further increase). This justifies the choice of Nreal=1000 for all voltage levels.
On a one-meter cable line segment, sets of single PDs recorded in the experiment and obtained in the model were compared. The closing moment of the controlled switch SW was set by a time scenario (PULSE); however, the phase of the simulated PD is not a strictly specified quantity: due to the finite switching time of the switch and the delay in discharge formation, the observed PD phase varies from realization to realization. Therefore, the comparison was carried out not for individual discharges “one-to-one”, but for the statistical characteristics of their distributions: peak phase angle, standard deviation, generation range, and repetition rate. The discrepancy in the peak phase angle did not exceed Δφ = 2°, which at a frequency of 50 Hz corresponds to 111 µs; since the PULSE moments were set independently of the experiment, this value reflects the objective error of the model, rather than a fitting result.
The results of modeling single surface PDs showed high convergence of statistical characteristics. A key technical condition is the synchronization of the recording oscilloscope and the time-controlled switch SW in LTspice: without it, part of the discrepancy in phase angle would be due not to the physics of the model, but to the asynchrony of the start of recording and discharge generation. The more accurately the recording and switch actuation are synchronized, the higher the convergence of the phase characteristics of the PD distribution. The amplitude of a single partial discharge also showed good peak-to-peak convergence with a discrepancy of ΔU = 2–3%. The proposed model also demonstrated good convergence of amplitude-phase diagrams (APDs) for internal single PDs in the solid insulation layer, confirming its adequacy in reproducing diagnostically significant PD features.
The final errors in modeling APD in phase and amplitude have different physical natures and are caused by different factors: the phase error Δφ is related to the accuracy of synchronizing the SW switch with the voltage phase, while the amplitude error ΔU is related to the accuracy of reproducing the discharge amplitude. For internal PDs, the phase error did not exceed Δφ = 2°, and the amplitude error did not exceed ΔU = 3%, which confirms the adequacy of the proposed model for reproducing diagnostically significant PD features. The result of comparing a single amplitude-phase diagram of the numerical and experimental internal PD over 1 meter of cable length is shown in Figure 10.
However, the greatest practical (engineering) and research interest is represented by dynamic modeling of PDs over time, since it is precisely the temporal evolution of a sequence of PDs that reflects the degree of insulation aging and allows a transition to predicting its residual life. In such modeling, it is advisable to compare with experiment not a single pulse, but a sequence of PDs in terms of shape, sign, amplitude, repetition rate, and phase distribution. Complete coincidence of model and experimental PD histograms over the entire service or experimental interval (Figure 11) is practically unattainable, since the amplitude, duration, and repetition rate of pulses are influenced by the duration and phase angle of the applied voltage, the nature of the inhomogeneity (location, shape, and type of defect), wave attenuation, noise of the real measuring system, and the design features of the cable line. Therefore, the criterion for the adequacy of the model is not element-by-element coincidence, but the stable reproduction of diagnostically significant features and their trends. The three-phase combined model with distributed parameters proposed in this work, implemented in LTspice, is a multilevel equivalent circuit of a cable line. The novelty of the approach lies in the transition from simplified models to a three-phase distributed model, which more correctly describes the propagation and distortion of PD pulses in a real line. In practical terms, this improves the efficiency of predicting the residual life of insulation: the model makes it possible to separate source-induced changes in PDs from the distortions introduced by the line and the measurement system, providing a basis for future studies on estimating the insulation degradation rate.
The noted stochasticity of PD processes does not exclude the possibility of practical use of numerical modeling. On the contrary, to improve the efficiency of PD measuring systems, their calibration, and the tuning of sensor sensitivity, preference should be given not to “standard” calibration pulses injected into the line, but to signals as close as possible to real discharges and PD histograms obtained on the basis of digital twins of cable lines. The three-phase combined model with distributed parameters proposed in this work, implemented in LTspice, makes it possible to generate such signals, since it takes into account the propagation and distortion of PD pulses in a real line. This enables the calibration of PD measuring systems not by abstract discharges, but by signals close to those occurring in an operating cable, and thereby improves the reliability of sensor sensitivity adjustment and the accuracy of measuring the amplitude-time and phase characteristics of PDs. With such a formulation of the problem, a good result can be considered the qualitative coincidence in LTspice modeling of individual sections of PD histograms (a sequential series of PDs over short time intervals). Such a result is achieved by modeling PDs using the Monte Carlo method, namely by modeling a set of time segments of digital PDs and comparing them with the analog counterpart. This was implemented through multiple model runs in LTspice using the .step directive and built-in random variation functions. Each model run corresponds to one realization of the stochastic PD process, and the accumulation of many such realizations allows obtaining stable statistical estimates — histograms, phase distributions, and their trends — which are then compared with experimental data. Due to the high speed of transient calculations and automation of runs, LTspice ensures reproducibility of statistics at acceptable computational costs, which makes the Monte Carlo method a convenient tool for PD analysis in a three-phase distributed model. Examples of such comparison of experimental and numerical PDs are shown in Figure 12 and Figure 13. Figure 12 and Figure 13 show examples of comparing numerical and experimental PD histograms over different time intervals of 0.11 µs and 0.27 µs, respectively. The model successfully reproduces both the stochastic nature of the discharge occurrence and the physical asymmetry of the defect, generating sequences that initiate with either a negative (Figure 12) or a positive (Figure 13) half-wave.
The validity of the model was evaluated by comparing numerical and experimental PD signals over the time interval between three consecutive input pulses of identical shape, polarity, and amplitude, in accordance with GOST R 55191-2012 (harmonized with IEC 60270:2025) regarding pulse resolution time. Qualitative agreement in polarity and shape was established, with a time shift of no more than 5%, which does not exceed the measurement error of time intervals. The discrepancy in PD signal amplitude does not exceed 10%, corresponding to the normative limit of measurement error for PD characteristics (GOST 20074-83; consistent with IEC 60270:2025); for the repetition rate, it is ±2% (GOST R 55191-2012). Statistical validation was performed on the full set of N = 1000 model–experiment pairs (number of Monte Carlo realizations). Prior to calculation, alignment by the maximum of the cross-correlation function and normalization by peak amplitude were performed. The following metrics were obtained: Pearson correlation coefficient r = 0.93 (95% CI [0.89, 0.96]; bootstrap, 10,000 resamples), normalized RMSE = 0.11, and modal phase error Δφ = 2°. The noted time shift is not a sign of model inadequacy, since the PD process is fundamentally stochastic and cannot be reproduced deterministically. The model reproduces a statistical ensemble of realizations rather than a fixed sequence of events. Therefore, the criterion of adequacy is taken to be the stable agreement of statistical patterns and their trends, rather than element-by-element coincidence, which is consistent with the generally accepted methodology for validating stochastic models.
3.2. Verification of the Surface Discharge Transient
In the diagnostic mode of short cable lines, insulation monitoring is carried out according to the scheme in Figure 4. The free conductors of the cable and the sheath at the beginning of the cable line are grounded, while at the end of the cable line the conductors and sheath are open. When testing insulation with alternating voltage at a frequency of 50 Hz, a steady capacitive current – Ic flows in the cable, directly proportional to the cable capacitance multiplied by the applied voltage U, taking into account the angular frequency ω = 2πf and the line length L:
Ic = U · ω · C · L,
During the test, voltage is applied to the cable conductor in steps with a step of 500 V/s. As the voltage increases, the charging (capacitive) current increases. At 2800 V, an unstable surface discharge between the conductor and the sheath was recorded, which did not lead to a complete insulation flashover. It comprises a low-frequency (50 Hz) component of the steady-state capacitive current and a high-frequency pulse component recorded by the RFCT. The latter exhibits characteristic PD features: short duration, a high-frequency spectrum, and phase locking to the supply voltage. The reference (measured) value of the capacitive current should be taken as the readings of the SKAT-70M installation: at a voltage of 2800 V, the current was 24–25 mA. This value is taken as the reference for verification.
The calculated value of the capacitive current was obtained using formula (1) for the reference capacitance of the APvPug-10 kV cable, which is 0.23–0.30 µF/km. For a 100 m segment, the capacitance is ~0.028 µF, which at 2800 V and 50 Hz gives ≈24.6 mA. The calculated value coincides with the measured one. The model value was obtained by shunting the insulation between the conductor and the sheath with a programmable switch in the simulated cable line. The simulated single surface discharge between the conductor and the open end of the sheath was 24.1 mA. Thus, three independently obtained quantities — measured (24–25 mA), calculated (24.6 mA), and model (24.1 mA) — these values are consistent and pertain to the low-frequency component, which confirms the correct modeling of the capacitive current and the equivalent line capacitance. The verification of the high-frequency PD component relies on the following criteria: pulse shape, phase position, and statistical characteristics, as described in Section 3.1. Verification of the model and the real single surface discharge is shown in Figure 14 (a) and (b).
A sheath voltage ripple synchronous with the 50 Hz frequency is present in both oscillograms, but in the model (Figure 14a) it is more pronounced than in the experiment (Figure 14b). In the model, the ripple is caused by numerical oscillations of LTspice (trapezoidal ringing of the trap method), periodic actuation of the SW switch, and resonance of the conductor–sheath circuit. In the experiment, these components are masked by noise of the measurement channel — discrete spectral interference, pulse noise, and intrinsic noise of the oscilloscope input stages. The discrepancy is non-systematic and does not affect the amplitude, shape, and phase of the PD.
3.3. Verification Results of Sheath Voltage Oscillograms for a 100-Meter PCL
The amplitude of the measured voltage at the open end of the sheath for drum-type laying is 0.045 V (Figure 15b), while its value during modeling is 0.04 V (Figure 15a). For comparison, the expected sheath voltage for flat-type laying was calculated: for a 100 m APvPug cable with a sheath made of copper wire with a cross-section of 16 mm2, the reference value of the active resistance of the sheath does not exceed 0.119 Ω, and the charging (capacitive) current of this cable is 0.025 A. With such parameters, the calculated sheath voltage is 0.003 V, which is an order of magnitude lower than the measured value for the drum type. Such a significant discrepancy confirms that for drum-type laying, the sheath voltage is determined not by active resistance and capacitive current, but by the mutual inductance between the conductor and the sheath, which for a multi-turn coil increases proportionally to the square of the number of turns N2. This means that modeling the sheath voltage without taking into account mutual inductance and the skin effect yields an underestimated result and cannot serve as a validity criterion for drum laying. In this case, validation of the model should be performed using the measured value U_sh = 0.045 V with mandatory consideration of the distributed mutual inductance along the cable length. The proposed model with distributed parameters allows varying the ratio of flat/drum laying types in any proportion — from 0/100% to 50/50% and to 100/0% — which corresponds to special operating modes of the cable when part of the drum is unwound when connected to a load. This provides the possibility of checking the adequacy of the model with respect to sheath voltage for a wide range of laying conditions.
3.4. Verification Results of Discharge in Solid Dielectric Layers of a 100-Meter PCL
Figure 16 presents the results of comparing the simulated and experimental single PDs. The pulse shown in Figure 16 was extracted from the general PD histogram (Figure 17) for a 100-meter cable line segment; the compared pulses are close in amplitude-frequency characteristics: frequency ~1 MHz, amplitude ~150 mV.
Due to the non-stationarity of the experimental conditions (drift in temperature, load, and measurement channel parameters), strict equivalence of the PD distributions was not expected. Practically relevant similarity metrics were applied instead of hypothesis tests for distribution equality. The validity of the model is confirmed not by identical histograms, but by the accurate reproduction of the dynamic range boundaries and the topological features of the PD distribution. The mean amplitude of the simulated pulses (over 1000 cycles) deviates from the experimental value by no more than 15%; furthermore, the increase in PD activity with voltage agrees both qualitatively and quantitatively.
3.5. Comparison of the Adequacy of the MRLCG+ABC and RLC Models
Analysis of the simulation results of a cable line based on an equivalent multilevel equivalent circuit with distributed parameters MRLCG + ABC shows good convergence of the AFC/APD of PDs. In terms of research purpose, the proposed model is comparable to a digital cable laboratory, allowing the following critically important aspects to be taken into account in PD modeling: the mutual influence of conductors and the sheath on wave processes in the line under damage; the influence of the sheath grounding scheme on PD measurement; the influence of the line laying geometry on wave process attenuation; and the presence of distributed defects in the insulation. In international practice (CIGRE TB 676, IEC 60270), for complex hybrid models, a model is considered valid if it correctly reproduces the PD repetition frequency (PRF) in steady state with an error ≤ 20% and correctly determines the defect location (fault location, FL). The analysis of the wave process results in Section 2.3 and Section 2.4 demonstrates that the mean amplitude of the simulated pulses (averaged over 1000 cycles) deviates from the experimental mean amplitude by no more than 15%. Furthermore, the model exhibits an increase in activity with rising test voltage, and the impedance matching is adequate. This confirms the correctness of the model for reproducing PD characteristics within the studied range of conditions. It should also be noted that the error in measuring the fault location in a cable line is reduced by the hybrid equivalent circuit MRLCG compared with an RLC circuit. Figure 18a shows a surface discharge of the sheath relative to ground (5 kV discharge). It is known that the distance to breakdown is determined by four times the travel time of the electromagnetic wave, i.e., it is determined by Tx/4 (Figure 18a). In practice, to improve the accuracy of remote fault location, it is customary to take the first half-wave Tx/2 due to topological features (possible “kinks” on the wave decay). The refined model clearly demonstrates the presence of a kink in Figure 18a, which leads to an increase in the fault location error Δt_FL. For a 100-meter PCL length, in the MRLCG model Tx/2 is 1.26 µs, which, at an electromagnetic wave propagation velocity of 160 m/µs, gives the desired fault location equal to 100.8 m; the relative error is <1% of the total cable length, which can well be explained by the inaccuracy of the experimental segment length (~100 m on the reel). For the averaged RLC model, Tx/2 = 1.55 µs, which corresponds to 124 meters, an error of 24%, which is quite significant. A more accurate measurement for the averaged RLC model would be calculation using the full period Tx = 2.9 µs, which corresponds to 116 meters; in that case, the remote fault location error does not exceed 16% of the cable length. Thus, the error in measuring the electromagnetic wave propagation time by different models is Δt_FL = 0.19 µs – 16% of the total length. Such a high error is most likely due to the fact that the simplified model does not take into account the line topology, namely the “drum” type. According to the law of electromagnetic induction, in adjacent turns an EMF is induced that is directly proportional to the rate of change of current in the pulse (di/dt) and the mutual inductance M (E = M (di/dt)). In reality, this parasitic EMF is an interference in drum-type laying; it is superimposed on the main pulse, distorting (“breaking”) its shape during the pulse decay.
The improvement in fault location accuracy upon transitioning to the MRLCG+ABC model is achieved not by introducing new empirical rules for selecting points and not by substituting the wave propagation velocity, but because the model correctly reproduces the physical shape of the signal taking into account distributed parameters and the mutual inductance of turns. This yields two interrelated effects. First, the characteristic points on the simulated oscillogram reflect real physical processes in the line rather than artifacts of the simplified circuit, and the choice of Tx/2 becomes justified. The kink on the decay that the model reproduces makes it possible to unambiguously determine the first half-wave; moreover, it helps avoid confusing it with a parasitic response from mutual inductance. Second, since the model takes into account the “drum” topology and the induced EMF, the calculated wave travel time Tx/2 corresponds precisely to the propagation velocity that is realized in this specific line, rather than to an averaged tabulated value. In other words, the MRLCG model does not “improve” the selection of points or the wave velocity separately — it ensures their consistency: the point by which time is measured and the velocity by which distance is recalculated relate to the same physical process in the real line. This is precisely what reduces the fault location error from 16–24% (RLC) to less than 1% (MRLCG+ABC) and makes the proposed model applicable for practical remote fault location. The considered approach may find application in digital oscillographic reflectometers.
3.6. PD Attenuation in the PCL Sheath and Its Influence on Diagnostic Accuracy
Previously, the adequacy of the proposed hybrid MRLCG+ABC model for describing wave processes and PDs was demonstrated. An important parameter determining the accuracy of insulation diagnostics at early stages and the accuracy of fault location is the attenuation of high-frequency PD signals in the cable line sheath. The attenuation of high-frequency electromagnetic waves in the sheaths of power cable lines is not standardized in technical documentation, but it is an important indicator determining the accuracy of insulation diagnostics by the PD method at early stages. GOST R IEC 61156-5-2012 standardizes the radiation attenuation for shielded cables in the frequency range up to 1000 MHz. The absence of data on the attenuation α(f) (attenuation coefficient) of PDs in reference books forces cable line specialists to resort to various methods for estimating α(f), for example, reference discharge calibration generators or numerical methods [17].
When using calibrators, one of the main problems is the difference between the pulse injected into the line and a real PD; the pulse can differ significantly and introduce up to 50% measurement error, since the generated pulse of the calibrator and a real PD have different points in the electrical circuit, due to which the propagation of the PD signal along a complex (in terms of propagation and distortion) high-frequency cable line with distributed parameters acting as a high-pass filter plays a significant role in the measurement. As noted earlier, it is important to take into account the influence of the sheath grounding mode, since the mode can introduce additional saturation of the core by power-frequency currents, thereby reducing the sensitivity of the sensor. Figure 19 shows an oscillogram of currents at the beginning and end of the sheath of a cable line having solid grounding at the beginning of the line and grounding through a capacitor at the end of the line. From the oscillogram it can be seen that a capacitive current flows in the sheath of the cable line, induced by a voltage source of 2800 V at a frequency of 50 Hz, flowing through the solid grounding of the sheath. The capacitive current is the same both at the beginning of the line Ix(x1:GND) and at the end of the line Ix(x32:GND) (the current curves coincide); Ic varies according to Equation (1).
The PD current in the sheath has a different nature of origin and, as can be seen from Figure 20, differs at the beginning and end of the line; even over such an insignificant segment as 100 meters, the attenuation α(f) manifests itself.
By a numerical method, the discharge amplitude IPD of the PD signal at a distance L from the point of origin can be described by an exponential law:
where I0 is the initial amplitude at the discharge site; α(f) is the frequency-dependent attenuation coefficient (Np/m); L is the distance from the PD site to the measurement point (in meters).
IPD(L) = I0·e(−α(f)·L),
From Equation (2), the attenuation coefficient α(f) is:
take the logarithm of both sides: ln(IPD(L)/I0) = −α(f)L
the attenuation can be calculated as α(f):
α(f) = (1/L) ln(I0 / IPD(L)),
For an APvPug cable with a sheath cross-section of 16 mm2 and a conductor cross-section of 95 m2, as noted earlier, reference books lack data on the attenuation coefficient at high PD frequencies, since at high frequencies the attenuation is determined not so much by the active resistance of the sheath as by dielectric losses in the insulation, the skin effect, and the proximity effect; moreover, for cable line operation in the “drum” or “flat/drum” mode (part of the cable unwound), this influence is only enhanced. The flat/drum laying mode during modeling is controlled by changing the distribution of mutual inductance along the cable line length and the coupling coefficient between the two inductances, k = 0.8–0.9, and by redistributing the inter-turn capacitance into per-unit-length capacitances between conductor–sheath / conductor–conductor per unit length of the modeled cable. For the PD in Figure 20, the attenuation was 3.9 dB or 0.0045 Np/m, which is an order of magnitude higher than the calculated value for a similar cable in flat laying mode, which does not contradict the general physical understanding of the processes for different laying types.
4. Conclusions
By comparing the results of field measurements and mathematical modeling, it is possible to confirm the effectiveness of representing the cable line as hierarchical blocks with a multilevel equivalent circuit. The proposed refined line model with distributed parameters MRLCG+ABC, taking into account frequency-dependent properties as well as the non-uniformity of the line parameter distribution, allows analyzing wave processes at different points of the cable. The mathematical description of PD dynamics in a monitored three-phase cable taking into account the skin effect, proximity effect, and laying method, especially in special “flat/drum” operating modes, requires rather complex calculations; therefore, in practice, averaged values are often used, which leads to calculation errors and an increase in PD measurement error. The results obtained in the study have the following practical value:
-this approach improves the calibration accuracy of PD measuring systems and sensors by converting digital amplitude-frequency characteristics (AFC) of PDs into analog data using special pulse generators. It should be emphasized that the proposed approach does not replace metrological calibration according to IEC 60270:2025, but rather supplements and refines it. Calibration is still performed by injecting pulses of a known charge q0 into the complete test circuit, which ensures measurement traceability. However, unlike the traditional approach, the shape and spectral content of these calibration pulses are as close as possible to real PD signals characteristic of a specific defect type in a given cable line. This approach, in full compliance with IEC 60270 recommendations (specifically, the requirement for a short rise time), yields a scale factor k that more accurately accounts for the frequency-dependent distortions of the measuring channel, thereby improving the accuracy of apparent charge measurement;
-to perform analysis of the sheath voltage U_sheath in diagnostic and operational modes of a three-phase cable. The proposed method for estimating the induced voltage on the cable line sheath will help avoid errors in sheath grounding and develop noise suppression measures;
-the obtained attenuation coefficient value for drum laying is consistent with published data [18,19,20]. The proposed hybrid MRLCG+ABC model provides a comparable level of accuracy, and in terms of taking into account the “drum” topology and distributed mutual inductance, it surpasses simplified approaches that either do not take this factor into account or require empirical correction coefficients. Taking into account distributed mutual inductance and α(f) in the model eliminates this error without empirical corrections.
Author Contributions
Conceptualization, A.Y.; methodology, A.Y.; validation, A.Y. and A.G.; formal analysis, Y.K.; resources, A.Y.; data curation, A.L.; writing—original draft preparation, A.Y.; writing—review and editing, Y.K.; visualization, A.B.; All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the Russian Science Foundation, grant number 25-19-00661.
Data Availability Statement
Data are available on request due to restrictions, e.g., privacy or ethical. The data presented in this study are available on request from the corresponding author. The data are not publicly available due to manufacturer’s trade secret.
Conflicts of Interest
The authors A. Yurov, Y. Kononov, A. Groshev, A. Lukonin, and A. Bogachev declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.
References
- Steennis, F.; Wagenaars, P.; van der Wielen, P.; Wouters, P.; Li, Y.; Broersma, T.; et al. Cables on-line: with travelling wave based temperature monitoring, fault location, PD location and PD related remaining life aspects. IEEE Trans. Dielectr. Electr. Insul. 2016, *23*, 1562–1569. [CrossRef]
- Shafiq, M.; Kiitam, I.; Taklaja, P.; et al. Identification and location of PD defects in medium voltage underground power cables using high frequency current transformer. IEEE Access 2019, *7*, 103608–103618. [CrossRef]
- Milioudis, A.; Andreou, G.; Labridis, D. On-line partial discharge monitoring system for underground MV cables—Part II: Detection and location. Int. J. Electr. Power Energy Syst. 2019, *109*, 395–402. [CrossRef]
- Raymond, W.J.K.; Illias, H.A.; Mokhlis, H.; et al. Partial discharge classifications: Review of recent progress. Measurement 2015, *68*, 164–181. [CrossRef]
- Sahoo, N.; Salama, M.; Bartnikas, R. Trends in partial discharge pattern classification: A survey. IEEE Trans. Dielectr. Electr. Insul. 2005, *12*, 248–264. [CrossRef]
- Chandrasekar, S.; Cavallini, A.; Montanari, G.C.; Puletti, F. Bandwidth and sensitivity issues in PD detection in power cables. IEEE Trans. Dielectr. Electr. Insul. 2007, *14*, 735–743. [CrossRef]
- Tozzi, M. Partial Discharge in Power Distribution Electrical Systems: Pulse Propagation Models and Detection Optimization. Ph.D. Thesis, University of Bologna, Bologna, Italy, 2010.
- Stone, E.J.W.; Panagiotou, P.A.; Mühlthaler, J.; et al. Modelling of insulation in concentrated stator coils for characterisation and material changes. In Proceedings of the 2024 International Conference on Electrical Machines (ICEM), Torino, Italy, 1–4 September 2024.
- Paul, C.R. Inductance: Loop and Partial; John Wiley: Hoboken, NJ, USA, 2010.
- Hencken, K.; Ceccarelli, D.; Borrelli, E.-M.; Krivda, A. Approximate Bayesian Computation for the Analysis of Partial Discharge Data. In Proceedings of the 7th European Conference of the Prognostics and Health Management Society, 2022.
- Ghaedi, A.; Mahmoudian, M.; Rodrigues, E.M.G.; et al. Localization of partial discharge in the high voltage apparatus. Results Control Optim. 2025, *19*, 100XXX. (please add article number). [CrossRef]
- Bu, J.; Zhao, L.; Jiang, B. Simulation-based fault characterization of shearer trailing cables using a distributed multi-conductor model. Results Eng. 2026, *29*, 109728. [CrossRef]
- Hollaus, K.; Bauer, S.; Leumüller, M.; Türk, C. Measurement and modeling of effective cable parameters of unshielded conductors. COMPEL 2021, *41*, 1041–1051. [CrossRef]
- Yurov, A.; Bykadorov, V. Simulation of wave processes in a three-phase power cable line during a floating breakdown. News High. Educ. Inst. Electromech. 2008, Special Issue: Diagnostics of Electrical Equipment, 39–42.
- Yurov, A.; Pirozhnik, A. Analysis of the transition process in a simulated three-phase overhead cable transmission line. News High. Educ. Inst. Electromech. 2019, *62*, 61–65.
- DIMRUS LLC. Catalog of Sensors for Portable and Stationary Monitoring Systems for High-Voltage Electrical Equipment. Available online: https://dimrus.ru/sensors.html (accessed on [date]).
- Sakoda, T.; et al. On-line PD System and PD Locator for XLPE Cables. In Proceedings of the 2020 8th International Conference on Condition Monitoring and Diagnosis (CMD), Phuket, Thailand, 25–28 October 2020; pp. 222–225. [CrossRef]
- Zhongyi Jiang, Hongwen Liu, Ming Tang, Tiejun Xu, Jiandong Peng, Teng Chen, Jianyong Lou. Study on Propagation Characteristics of High Frequency Signal in Medium Voltage XLPE Cable Joints. 2019 IEEE 9th Annual International Conference on CYBER Technology in Automation, Control, and Intelligent Systems (CYBER), 2019, pp. 519–524.
- H. N. O, T. R. Blackburn, B. T. Phung, H. Zhang, M. Vakilian, M. S. Naderi. Investigation of the High Frequency Propagation Characteristics on XLPE Cables. The University of New South Wales, Australia, 2013.
- Xu Lu, Ge Wang, Yuli Wang, Jie Tian, Ying Yu. Research on Propagation Attenuation Compensation Algorithm of PD Signal in Distribution Cable Lines. 2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE), 2022, pp. 1–4.
Figure 1.
Cross-section of a 10 kV cable line: virtual (left) and real (right), where numbers 1 and 2 indicate the discrepancy in distances between the current-carrying parts of the cable.
Figure 1.
Cross-section of a 10 kV cable line: virtual (left) and real (right), where numbers 1 and 2 indicate the discrepancy in distances between the current-carrying parts of the cable.

Figure 2.
Refined equivalent circuit of a segment of the MRLCG+ABC cable line, Ra, Rb, Rc are the active resistances of the conductors of the three-phase cable; La, Lb, Lc are the inductances of the cable, Lo is the inductance of the sheath; CAB, CBC, CAC are the insulation capacitances between the conductors of the cable line; CAO, CBO, CCO are the insulation capacitances between the conductor and the sheath of the cable line; GAB, GBC, GAC are the specific conductances between the conductors; GAO, GBO, GCO are the specific conductances between the conductor and the sheath; Cd is the capacitance of the defective insulation, Cb is the capacitance of the remaining part of the insulation, Co is the capacitance of the entire insulation between the corresponding conductor and the sheath.
Figure 2.
Refined equivalent circuit of a segment of the MRLCG+ABC cable line, Ra, Rb, Rc are the active resistances of the conductors of the three-phase cable; La, Lb, Lc are the inductances of the cable, Lo is the inductance of the sheath; CAB, CBC, CAC are the insulation capacitances between the conductors of the cable line; CAO, CBO, CCO are the insulation capacitances between the conductor and the sheath of the cable line; GAB, GBC, GAC are the specific conductances between the conductors; GAO, GBO, GCO are the specific conductances between the conductor and the sheath; Cd is the capacitance of the defective insulation, Cb is the capacitance of the remaining part of the insulation, Co is the capacitance of the entire insulation between the corresponding conductor and the sheath.

Figure 4.
Equivalent circuit of the cable line at Level 1 in the high-voltage test mode.

Figure 5.
PD measurement scheme in a cable line: (a) schematic diagram; (b) test bench.

Figure 6.
Comparison of PD histograms in time intervals: 1 – control unit of the high-voltage source SKAT; 2 – high-voltage unit SKAT; 3 – two-channel oscilloscope FNIRSI 1013D; 4 – RFCT-5 sensor; 5 – 100-meter cable line.
Figure 6.
Comparison of PD histograms in time intervals: 1 – control unit of the high-voltage source SKAT; 2 – high-voltage unit SKAT; 3 – two-channel oscilloscope FNIRSI 1013D; 4 – RFCT-5 sensor; 5 – 100-meter cable line.

Figure 7.
Discharges in the cable line: (a) surface discharges in the line shunting the insulation between the conductor and the sheath; (b) discharges in the solid insulation layers.
Figure 7.
Discharges in the cable line: (a) surface discharges in the line shunting the insulation between the conductor and the sheath; (b) discharges in the solid insulation layers.

Figure 8.
PD measurement in the cable line: (a) K15-4 N70 470 pF 40 kV; (b) measurement scheme.

Figure 9.
Cyclic APD of surface PD between the conductor and the water-blocking tape: (a) simulated; (b) experimental.
Figure 9.
Cyclic APD of surface PD between the conductor and the water-blocking tape: (a) simulated; (b) experimental.

Figure 10.
Cyclic APD of PD in insulation: (a) model; (b) experimental.

Figure 11.
PD histogram recorded on a one-meter segment of the APvPug-10 kV cable line at a test voltage of 15 kV and a frequency of 50 Hz (RFCT-5 sensor).
Figure 11.
PD histogram recorded on a one-meter segment of the APvPug-10 kV cable line at a test voltage of 15 kV and a frequency of 50 Hz (RFCT-5 sensor).

Figure 12.
Comparison of PD histograms over a 0.11 µs time interval initiating with a negative half-wave: (a) numerical; (b) experimental.
Figure 12.
Comparison of PD histograms over a 0.11 µs time interval initiating with a negative half-wave: (a) numerical; (b) experimental.

Figure 13.
Comparison of PD histograms over a 0.27 µs time interval initiating with a positive half-wave: (a) numerical; (b) experimental.
Figure 13.
Comparison of PD histograms over a 0.27 µs time interval initiating with a positive half-wave: (a) numerical; (b) experimental.

Figure 14.
Single surface discharge: (a) simulated; (b) experimental.

Figure 15.
Sheath voltage relative to ground for drum-type laying: (a) model; (b) experiment.

Figure 16.
Discharges in the cable line: (a) simulated partial discharge with a maximum amplitude of 149 mV at a frequency of 1 MHz; (b) experimental partial discharge with a maximum amplitude of 144 mV at a frequency of about 1 MHz.
Figure 16.
Discharges in the cable line: (a) simulated partial discharge with a maximum amplitude of 149 mV at a frequency of 1 MHz; (b) experimental partial discharge with a maximum amplitude of 144 mV at a frequency of about 1 MHz.

Figure 17.
PD histograms in the cable line: (a) simulated; (b) experimental.

Figure 18.
Oscillogram of a surface discharge at the end of a 100-meter APvPug-10 kV cable line with drum-type laying: (a) comparison of the numerical MRLCG and RLC models; (b) experimental.
Figure 18.
Oscillogram of a surface discharge at the end of a 100-meter APvPug-10 kV cable line with drum-type laying: (a) comparison of the numerical MRLCG and RLC models; (b) experimental.

Figure 19.
Simulation of current in the cable line sheath.

Figure 20.
PD attenuation in the cable sheath.

Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |