5. Time-Based Model and Experimental Validation for Full-Process Control of Load Transfer Using Bo-BiLSTM
Accurate switch timing prediction provides the prerequisite for achieving precise load transfer control.
This chapter will design a synchronous control strategy based on the switching times (Ton, Toff) predicted by the Bo-BiLSTM model to ensure the safety and rapidity of the transfer process. The core control objective of the model is to accurately estimate the total time control interval from the issuance of the master station command to the final switching action, while ensuring compliance with the “open before close” sequence and time difference constraints even under extreme scenarios. By integrating mathematical modeling with engineering experience, we can systematically evaluate the boundary conditions of time parameters and their impact mechanisms on the overall control process, providing theoretical support for strategy design. This strategy requires, based on precise time synchronization, that the time interval from complete tripping to complete closing be within 20ms, disregarding communication time from the master station to the terminal.
5.1. Time Constraints and Problem Modeling
Control Objective: Total time (interval from trip completion to close completion) must satisfy 0 < Ttotal < 20 ms.
Known Conditions:
Closing time Ton > Trip time Toff, based on switch timing (Ton, Toff) predicted by the Bo-BiLSTM model.
Master Station Command Sequence:
t0: Issue closing control command (target power switch S2)
t0 + △t: Issue trip control command (original power switch S1)
Mathematical Model
Closing completion time: tonend = t0 + Ton
Trip completion time: toffend = t0 + Toff + △t
Total time constraint: Ttotal = tonend - toffend and 0 < Ttotal < 20ms
Known Conditions:
Closing time Ton > Opening time Toff, but specific values are unknown.
Master Station Command Sequence:
t0: Issue closing command
t0 +Δt: Issue opening command
Mathematical Model
Opening completion time: toffend = t0 + Toff
Closing completion time: tonend = t0 + Ton+Δt
Total time constraint: Ttotal = tonend - toffend and 0 < Ttotal < 20ms
5.2. Control Strategy Design: Determination of Dynamic Delay Time Δt
Constraint Derivation:
Disconnection completion must precede reconnection completion (to prevent parallel circulating currents):
toffend < tonend △t < Ton -Toff
Total Time Constraint:
0 < Ttotal < 20ms →Toff -Ton <△t < Toff -Ton+20
Safety Margin Determination:
If nominal values of Ton and Toff are known:
△t = Ton - Toff - 10ms (take midpoint value, reserve 10ms margin)
If parameters are unknown, calibration via experimentation is required:
Step 1: Measure typical values of Ton and Toff in the laboratory.
Step 2: Set △t = Ton - Toff - 10ms and verify that Ttotal ∈ (0, 20) ms.
5.3. Physical Experiment Verification and Result Analysis
Test scenario
Figure 8.
Distribution network load synchronous transfer control time accuracy test.
Figure 8.
Distribution network load synchronous transfer control time accuracy test.
Test method
1.Distribution terminals A and B received BeiDou satellite signals and synchronized normally for 10 minutes;
2.Set the timed tripping moment for distribution terminal A and the timed closing moment for distribution terminal B via master station commands;
3.Tested the contact opening moment of circuit breaker A and the contact closing moment of circuit breaker B using a time synchronization tester;
4.Compared the time difference between the contact opening moment of circuit breaker A and the contact closing moment of circuit breaker B;
5.Repeat the test 10 times.
Experimental data
Table 7.
Accuracy test data for timed action of distribution terminals.
Table 7.
Accuracy test data for timed action of distribution terminals.
| NO. |
The moment when Circuit Breaker A opens |
Closing time of Circuit Breaker B |
Time difference (ms) |
Is the difference between the switch operation time and the model prediction time less than 0.1 milliseconds |
| 1 |
8:50:27.244 |
8:50:27.251 |
7 |
Yes |
| 2 |
8:52:51.831 |
8:52:51.841 |
10 |
Yes |
| 3 |
9:04:10.433 |
9:04:10.443 |
10 |
Yes |
| 4 |
9:09:11.311 |
9:09:11.316 |
5 |
Yes |
| 5 |
9:15:10.211 |
9:15:10.223 |
12 |
Yes |
| 6 |
9:20:20.430 |
9:20:20.433 |
3 |
Yes |
| 7 |
9:25:40.556 |
9:25:40.559 |
3 |
Yes |
| 8 |
9:29:30.466 |
9:29:30.477 |
11 |
Yes |
| 9 |
9:35:10.876 |
9:35:10.879 |
3 |
Yes |
| 10 |
9:40:20.431 |
9:40:20.438 |
7 |
Yes |
Experimental conclusions
This paper validates the Bo-BiLSTM-based synchronous load transfer control method for distribution networks through 10 repeated experiments. Experimental results demonstrate that switch operation times align with model predictions, with all trip and close operation timing deviations controlled within 2–12 ms—fully meeting the 20 ms engineering requirement. This effectively mitigates circulating current risks, proving the proposed control strategy’s effectiveness and reliability.