2. Theoretical Background
The three-pin method is represented in
Figure 1. The electrode to be measured is connected to a distant auxiliary electrode through a current source with intensity I.
The circuit is completed through the ground. The potential difference between points A and B is
In expression (1), is the potential of the electrode when it is isolated, i.e., the grounding potential. Additionally, it is implicitly assumed that at point x, both the grounding electrode and the auxiliary current electrode behave as point sources of current at ground level. The same applies to the auxiliary electrode with respect to point A. This question should be discussed in the case of long electrodes or not very large distances D.
Based on expression (1), the measured grounding resistance
is defined as
where
is the true grounding resistance. It is clear that
for any given value of x, provided that the quantity in brackets in (2)
is zero. Thus, solving for the value of x, it gives
, known as the 62% rule, provided that the assumptions mentioned above are satisfied. In summary, by placing the auxiliary electrode at a sufficiently distant location D from the grounding point, this rule can be applied to obtain values that are very close to the true grounding resistance.
It is evident that the analysis presented here cannot be applied when measuring an extensive electrode or also when the distance D is not large enough to ensure that the potential generated by the auxiliary current electrode on the electrode to be measured is
as the implicit assumptions described above are no longer valid. An extensive mesh cannot behave like a point source of current unless viewed from an immensely large distance. It also cannot be applied if there is not enough space to place the auxiliary electrode sufficiently far away, even if the grounding system is not very extensive. Since the electrode can no longer be assimilated to a current point,
where
is the potential created by the electrode at point x, considered as isolated and the distance D is not well defined since it must correspond to the distance at which
VA coincides with the true potential of the electrode. Dividing by the injected current I,
Note that from expression (4),
, if and only if
for some value of x, otherwise will be above or below
RG depending on the value of x. This condition is equivalent to the 62% rule when it is not possible to assume that the electrode to be measured behaves as a current point. Next, the so-called correction factor
will be introduced. It is defined as the ratio between the true grounding resistance and the resistance measured in the field
. According to (4), it can be written as
where the coefficients
and
have been introduced. These coefficients
,
turn out to be parameters of the electrodes and can be calculated for single-layered soils of resistivity
.
Therefore, the proposed method requires precise knowledge of the nature, geometry, and placement of the electrode, information that is presumably available, with which to evaluate and . Once is obtained for a specific position of the potential probe, the electrode resistance is measured, and the grounding resistance is found using . Since these expressions have been derived from a drastic simplification, such as considering an extensive electrode as a point source at short distances, it is expected that will depend on x and actually represent an upper bound to the true grounding resistance value. It should be noted that in the three-pin method, the measured resistance is always lower than the real value.
As a comment, the denominator of (5) contains actually the touch potential of the electrode at distance x per unit of current and soil resistivity, known as
and defined by
, so (5) can also be expressed as
The magnitude
can be evaluated theoretically, just like
, given the nature, geometry, and positioning of the electrode in the soil. When dealing with extensive electrodes or with auxiliary current electrodes close to the electrode being measured, it becomes necessary to determine the appropriate value of D to use. It might be useful to rewrite (6) by introducing two distances,
where
D1 represents the distance between the auxiliary current electrode and the coordinate origin used to define the electrode being measured and
D2 is the optimal distance from the auxiliary electrode to the electrode being measured to obtain the potential
VA according to the first equation in (3). In critical situations, that is, when
D1 is not very large, we propose averaging
RG evaluated with two different values of
D2, corresponding to the nearest and farthest distances from the auxiliary electrode to the extensive electrode being measured. It is easy to see that
if both are large compared to the size of the electrode being measured so the point current approximation for the grounding electrode becomes quite accurate.
In the proposed method, we start with a known "theoretical" electrode for which it is possible to calculate
,
and therefore
according to (6). However, the electrode to be measured may not exactly correspond to the "theoretical" electrode. It may be altered for various reasons, so its resistance will not match the theoretical resistance. If we measure
, then applying the correction factor
will not result in
. The main causes include oxidation or deterioration of the conductors that make up the electrode. Besides, the measurement can also be altered because the electrode is interconnected with other external grounds. This is a common practice that significantly reduces the resistance of the joint ground. With electrode deterioration the measure typically leads to grounding resistances
somewhat higher than those of the unaltered electrode, which, when multiplied by the correction factor, results in an overestimation of
. Thus, generally the result will be
. However, for interconnected electrodes, the measurement will give an underestimation of
RG. In either case, the proposed method will give the correct reading that corresponds to the case, and it is the task of the technical staff to determine the usefulness of the measurements. This hypothesis will be verified with the help of a numerical example in which a flat square electrode with a side length of 4 meters, made of conductive rods with a radius of 9mm, is buried at a depth of 0.5 meters. The soil is considered homogeneous with unitary resistivity. We are going to simulate the measurement of the grounding resistance by placing an auxiliary current rod 200 meters away from the electrode using the fall-of-potential method. For the same type of electrode, two situations will be addressed. In one case, the electrode has no issues, while in the other, it is assumed that part of the electrode is damaged and inactive in releasing current to the ground.
Figure 2 shows the profiles of the electrode, and the dotted line represents the path traced to evaluate the potentials on the ground.
The difference of potential profile at points on the ground (z=0) along a straight line from the left side of the electrode at x=-2m to x=180m when the y-coordinate is fixed at y=2m, will be measured for both electrodes. Since the soil has a unit resistivity and the injected current is 1A, this potential difference represents the unit grounding resistance as a function of the distance x at which the potential probe is located, measured by the three-pin method, when the auxiliary electrode is, as previously mentioned, 200 meters from the electrode being measured.
Figure 3 shows the grounding resistance measured using the three-pin method, placing the potential electrode at distance
x. The figure shows this measured resistance for both the original (red line) and the damaged electrode (beige line). The figure also shows the resistance corrected by the correction factor
km, which is shown in the subfigure. The blue line is the result of this correction for the original electrode. As seen, the value
RG = 0.1114 Ω corresponding to the true resistance of the original electrode is obtained. In contrast, for the damaged electrode, applying the correction factor results in an
RG value above the true resistance value, which is 0.1266 Ω. Note that the correction factor is derived from the original electrode parameters and is applied to all situations, whether the electrode is damaged or not.