4. Results of Simulations
Simulations were conducted for each temperature (700, 750, and 800°C) and each steam utilization factor (50%, 60%, 70%, and 80%), totaling 12 cases. For each case, voltage, total input power, LHV efficiency, and the ratio of Balance of Plant (BoP) to total power were calculated for current densities between -1.5 and -0.1 A/cm² (negative current values indicate operation in SOE mode).
Figure 1.
Voltage-Current curve for operating temperature 700°C.
Figure 1.
Voltage-Current curve for operating temperature 700°C.
The voltage values across the entire current density range are very similar for a given temperature and different levels of steam utilization (SU). They decrease from 3.57 V at a current density of -1.5 A/cm² to 1.18 V at -0.1 A/cm². In practical applications, SOEC cells are not exposed to voltages over 1.5 V due to the high degradation rate over time. Therefore, at an operating temperature of 700°C, the current density should not exceed -0.3 A/cm² to avoid excessive degradation.
Figure 1.
Efficiency of the system at 700°C.
Figure 1.
Efficiency of the system at 700°C.
Figure 1.
Efficiency of a system working at 700°C.
Figure 1.
Efficiency of a system working at 700°C.
For all analyzed values of steam utilization (SU), the total power input varies significantly across the entire simulated range of current density. For a nominal power of 25 kW (measured at 700°C), the maximum obtained power is over 76.29 kW for an SU of 0.5 and a current density of -1.5 A/cm², while the minimum value is 2.12 kW for an SU of 0.8 and a current density of -0.1 A/cm². Generally, higher SU requires higher input power. Power decreases with decreasing current density, and the differences between values for different steam utilizations also diminish with decreasing current density.
LHV efficiency steadily increases as the current density approaches 0 A/cm². However, the rate of increase slows down at low current density values. The reason for this will be analyzed using the BoP/P ratio later in this chapter. LHV efficiencies vary between 30% and 70%, with higher values observed for higher steam utilization ratios. The differences between efficiencies for particular SU values become more pronounced as the current density decreases.
Figure 1.
Ratio of BoP to total power input at 700°C.
Figure 1.
Ratio of BoP to total power input at 700°C.
The share of the Balance of Plant (BoP) in total power consumption steadily increases with decreasing current for all steam utilization factor values. The range of the ratio's values is between 0.1 and 0.37. A sudden increase can be observed between -0.2 and -0.1 A/cm² for all SUs. This is caused by the inefficient operation of the system’s devices, such as blowers, which were forced to operate in extreme regions of their characteristic maps. For the given parameter set, the hydrogen blower was working at a very low volumetric flow, resulting in an efficiency decrease to 6%. The air blower was operating at an even lower efficiency of around 4.5%. The working point for a steam utilization value of 0.5 is marked as a red dot in Figure 1. This inefficiency is also reflected in the system's efficiency graph, where the last point is lower than anticipated due to the significantly higher required power input.
Figure 1.
Working point of air blower for -0.1 A/cm2.
Figure 1.
Working point of air blower for -0.1 A/cm2.
Figure 1.
Voltage-Current curve for operating temperature 750°C.
Figure 1.
Voltage-Current curve for operating temperature 750°C.
As expected, the voltage values are lower at higher temperatures. The maximum SOE voltage obtained at -1.5 A/cm² is 2.34 V for SU=0.8, compared to 3.57 V at 700°C. The differences in voltage for different SU levels are also very small. At the current temperature of 750°C, the SOE cell should operate with current densities higher than -0.6 A/cm².
Figure 1.
Total power input of the installation at 750°C.
Figure 1.
Total power input of the installation at 750°C.
At 750°C, the total power input ranges from 55.8 kW for SU=0.5 at -1.5 A/cm² to 2.02 kW for SU=0.8 at -0.1 A/cm². The required power is lower than that at an operating temperature of 700°C, where the maximum was 76.29 kW. Similar to the previous observations, a lower steam utilization ratio necessitates a higher power input.
Figure 1.
Efficiency of the system at 750°C.
Figure 1.
Efficiency of the system at 750°C.
LHV efficiency increases from 40% for SU=0.5 at -1.5 A/cm² to 74% for SU=0.8 at -0.1 A/cm². However, the efficiency for the last case at -0.1 A/cm² is not the maximum observed. The highest efficiency was actually at a higher current density of -0.2 A/cm². A similar effect was observed at 700°C, related to the low efficiency of the system’s devices for the given set of parameters. However, at the lower temperature, the efficiency did not decrease in the last step; the rate of increase was simply smaller.
Figure 1.
Ratio of BoP to total power input at 800°C.
Figure 1.
Ratio of BoP to total power input at 800°C.
The share of Balance of Plant (BoP) in total power input increases as current density decreases, ranging from 0.17 for SU=0.8 at -1.5 A/cm² to 0.39 for SU=0.5 at -0.1 A/cm². Once again, a sudden increase is observed at the end of the analyzed range, specifically at a current density of -0.1 A/cm². This is related to the increased power consumption by the blowers, which are operating in their inefficient regions.
Figure 1.
Voltage-Current curve for operating temperature 800°C.
Figure 1.
Voltage-Current curve for operating temperature 800°C.
The voltage-current curve for 800°C shows the lowest voltage values among the analyzed temperatures. Higher voltages are observed for higher steam utilization (SU) ratios, although the differences remain small. The maximum voltage for SU=0.8 at -1.5 A/cm² is 1.76 V. To protect the cell from rapid degradation, operation at 800°C should not extend below -1 A/cm².
Figure 1.
Total power input of the installation at 800°C.
Figure 1.
Total power input of the installation at 800°C.
At 800°C, the power requirements are again lower than for the previous cases, as explained by the theory described in Chapter 3.1. The highest power values are observed for SU=0.5 and the lowest for SU=0.8. Power values decrease from 46.1 kW for SU=0.5 at -1.5 A/cm² to 1.97 kW for SU=0.8 at -0.1 A/cm².
Figure 1.
Efficiency of the system at 800°C.
Figure 1.
Efficiency of the system at 800°C.
The efficiencies obtained at 800°C are the highest among all the analyzed cases. However, as observed in previous cases, there is a peak at -0.2 A/cm², followed by a slight decline. The highest efficiency was found for SU=0.8 at -0.2 A/cm², with a value of 79.73%.
Figure 1.
Ratio of BoP to total power input at 800°C.
Figure 1.
Ratio of BoP to total power input at 800°C.
The share of BoP in the total power consumption of the system at 800°C again shows a rising trend, but the graph is much flatter than for previous temperatures. This indicates that at higher temperatures, the SU value has a lower impact on the share of BoP in total power consumption. For all values of current density and SU, the share is concentrated around 0.3. The exception is at a current density of -0.1 A/cm², where a sudden rise is observed.
For all different temperature values, the BoP/P ratio is lowest for the highest steam utilization factor. As a result, the total power consumption is also lowest for the highest SU values, and consequently, the efficiency is higher for higher values of steam utilization.