Submitted:
08 October 2026
Posted:
10 October 2026
You are already at the latest version
Abstract
Background: A growing number of datacenters are powered by colocated, behind-the-meter (BTM) fossil-fuel generation rather than the public grid. The exposure to air pollution and the health impacts of BTM supply have not been directly compared to the conventional grid supply. Objective: Using Colossus 1 (C1) and Colossus 2 (C2), two datacenters 12 km apart in the Memphis region, we compared the magnitude, spatial distribution, and equity pattern of fine particulate matter (PM2.5)-attributable mortality associated with grid versus BTM supply. Methods: We evaluated two scenarios: (i) a scenario in which C1 and C2 each hypothetically used 240 MW; and (ii) a real-world scenario based on the reported capacity of C1 and the permitted capacity of C2. We estimated population-weighted PM2.5 exposure and attributable mortality by distance, household income, and strata of people-of-color. Results: Under the same 240-MW demand, C1 had higher PM2.5-attributable mortality than C2: 10.83 deaths per year (95% interval, 7.83-13.84) versus 3.67 (2.65–4.68). In the real-world scenario, the order reversed: 11.35 (6.48-17.29) for C2 versus 8.10 (4.60-12.38) for C1. Statistically, 94% of C1 mortality occurred at least 250 km from the facility, while 82% of C2 mortality occurred within 50 km of the facility. The low-income, high-people-of-color stratum accounted for the largest share of C2-attributable mortality. Conclusions: The electricity-supply pathway shaped the magnitude and spatial distribution of PM2.5-attributable mortality. The grid supply dispersed mortality across distant communities, whereas the BTM generation concentrated it near the facility. Our findings support integrating epidemiological evidence into datacenter siting and permitting so that potential public-health consequences can be identified and avoided before decisions are made.
Keywords:
air pollution
; datacenters
; fine particulate matter
; InMAP
; marginal generation
; mortality
1. Introduction
The rapid growth of generative AI is increasing demand for datacenter capacity and the electricity needed to operate them [1,2]. To secure power at a scale and on a timeline that the public grid cannot meet, some developers are adopting unconventional arrangements in which colocated power plants supply datacenters directly [3,4]. These arrangements are known as behind-the-meter (BTM) datacenters, where electricity is generated on-site or nearby rather than supplied entirely through the public grid. Although this remains an emerging paradigm, it is expanding rapidly: as of 21 August 2026, only 4 BTM datacenters were operating in the US, while 43 are being planned [5]. These planned BTM facilities are also considerably larger, with a median reported capacity of 408 MW compared with 66 MW for grid-connected datacenters. As a result, BTM datacenters account for 25.4% of all planned datacenter capacity [5] (Supplementary Figure S6).
This shift matters for public health because where electricity is generated helps determine where combustion-related emissions occur and which populations experience them. Notably, datacenters tend to cluster much closer to urban areas than the power plants that typically supply them. The International Energy Agency (IEA), comparing six major industrial facility types, estimates that datacenters lie roughly 10 km from urban areas on average, compared with about 70 km for power plants [6]. Colocating routine fossil-fuel generation with datacenters can bring electricity-related emissions closer to surrounding communities. Fine particulate matter (PM; particles with diameters no greater than 2.5 m) is a particular concern. Epidemiological studies associate long-term PM exposure with higher all-cause and cardiopulmonary mortality, while experimental evidence identifies inflammatory and vascular pathways through which PM damages the cardiovascular and respiratory systems [7,8]. Thus, understanding where these exposures occur and which populations bear them is central to evaluating the health and health equity implications of datacenter power supply.
A datacenter supplied by colocated gas turbines releases combustion emissions at or near its site, whereas a grid-supplied datacenter adds demand that multiple power plants across the regional grid may meet. When a datacenter connects to the grid, certain power plants have to meet its added demand. Those plants generally rely on natural gas and coal, and their output increases or decreases to follow demand as it changes. Therefore, these plants that increase output in response to increased demand by datacenters are known as marginal units. We modeled this incremental response using marginal dispatch, which identifies the marginal units and assigns the datacenter’s emissions to them [9]. Because marginal units may be located far from the datacenter and from one another, the emissions of a grid-connected datacenter are spread across a broad region, whereas those of a BTM datacenter are released at a single site. This difference in where emissions occur persists even when both pathways deliver the same amount of electricity. It matters for health because four factors shape the resulting PM exposure: where pollutants are released relative to where people live, how high they are released, which pollutants the electricity generation emits and in what amounts, and how the atmosphere transports and chemically transforms them [10,11].
Assessments of datacenter health risks have so far been largely qualitative. Gour et al. surveyed air pollution, water use, noise, and land use around Virginia’s datacenter cluster and called for research quantifying specific health outcomes [12]. Recent studies have begun to trace parts of this electricity-to-health pathway for datacenters. Guidi et al. showed that fossil fuels still supply a substantial share of U.S. datacenter electricity use [13]; Han et al. found that associated air-pollution health costs can vary markedly across counties [14]; and Chen et al. showed that communities hosting datacenter demand do not necessarily bear the associated mortality burden because electricity generation and atmospheric transport redistribute impacts across regions [15]. These studies establish that both electricity source and geography matter, but they do not directly compare colocated BTM generation with conventional grid supply under the same datacenter demand. These findings motivate a direct comparison of colocated generation and grid supply under matched datacenter demand, while also accounting for differences in facility scale.
In this paper, we study the extent to which electricity supply and the scale of the facility (i.e., electricity demand) affect the magnitude and distribution of PM exposure related to the datacenter and the associated mortality burden. We address this question using Colossus 1 (C1) and Colossus 2 (C2), two massive datacenters approximately 12 km apart in the Memphis region. C1 is attached to the power grid, whereas C2 has colocated natural gas BTM supply. Their proximity provides a shared local setting for comparison, while the locations of the generating sources require different regional modeling domains.
Our contributions are threefold. First, we evaluate a hypothetical matched-demand scenario in which C1 and C2 each have the same 240-MW electricity demand, allowing us to examine how grid-connected and BTM power supply change the magnitude and spatial distribution of the resulting PM exposure and mortality burden. Second, we evaluate a real-world facility-scale scenario using the reported 300-MW capacity of C1 and the permit-derived 1,240.5-MW capacity of C2. Because long-term operating levels for these rapidly expanding facilities remain uncertain, we assume a 60% central capacity factor with a 40–80% operating range. Third, across both scenarios, we examine where and among whom these burdens occur, distinguishing near-site from regional impacts and their distribution across household-income and people-of-color strata.
Figure 1.
Pilot sites and modeled electricity sources. Panel A maps C1 and C2 in the Memphis region, the 25 marginal plants contributing to the AVERT response for C1, and the colocated behind-the-meter sources for C2. Panel B shows the modeled supply shares: marginal plants for C1 are grouped by fuel, whereas C2 is represented by 41 on-site turbines and 10 pressure-reduction stations. These source locations and shares define the inventories used in Figure 2 and Figure 3.
Figure 1.
Pilot sites and modeled electricity sources. Panel A maps C1 and C2 in the Memphis region, the 25 marginal plants contributing to the AVERT response for C1, and the colocated behind-the-meter sources for C2. Panel B shows the modeled supply shares: marginal plants for C1 are grouped by fuel, whereas C2 is represented by 41 on-site turbines and 10 pressure-reduction stations. These source locations and shares define the inventories used in Figure 2 and Figure 3.

Figure 2.
Spatial exposure distribution under the matched 240-MW load. Panels A and B show annual incremental PM concentrations from marginal dispatch (AVERT) for C1 and permit-based BTM generation for C2. Each value is shown on a 4 × 4 km InMAP grid cell. Panels C and D show the corresponding population-weighted PM exposure as a ZCTA-level mean, calculated with the canonical 2020 Census tract–county–ZCTA population crosswalk and displayed on 2024 ZCTA polygons. Each column uses the same map extent for its cell-level concentration and ZCTA-level exposure panels; color scales are shared within each row. Source markers identify modeled point sources. Dashed 75-km circles are visual reporting guides and do not filter the full-domain health calculation.
Figure 2.
Spatial exposure distribution under the matched 240-MW load. Panels A and B show annual incremental PM concentrations from marginal dispatch (AVERT) for C1 and permit-based BTM generation for C2. Each value is shown on a 4 × 4 km InMAP grid cell. Panels C and D show the corresponding population-weighted PM exposure as a ZCTA-level mean, calculated with the canonical 2020 Census tract–county–ZCTA population crosswalk and displayed on 2024 ZCTA polygons. Each column uses the same map extent for its cell-level concentration and ZCTA-level exposure panels; color scales are shared within each row. Source markers identify modeled point sources. Dashed 75-km circles are visual reporting guides and do not filter the full-domain health calculation.

Figure 3.
Health comparison for matched-load and site-capacity scenarios. Panels A–C show a fixed 240-MW delivered load: total attributable mortality, cumulative mortality by distance, and the central modeled share of mortality in distance bands. Panels D–F use C1’s reported facility capacity and C2’s permit-derived generating capacity with a 60% central capacity factor (300 MW for C1, modeled average output 180 MW; 1,240.5 MW for C2, modeled average output 744.3 MW). For the distance-based summaries, distance is measured from the datacenter site to the location of the attributable mortality burden; it does not represent the distance that pollution travels from an emitting source. Panels A, B, D, and E show central estimates with whiskers or shading from the reported 95% intervals. Distance-band shares in panels C and F are central deterministic allocations of the InMAP fields. Matched-load rows use the published Pope/COBRA coefficient limits; site-capacity rows additionally propagate the 40–80% capacity-factor distribution through 10,000 Monte Carlo draws.
Figure 3.
Health comparison for matched-load and site-capacity scenarios. Panels A–C show a fixed 240-MW delivered load: total attributable mortality, cumulative mortality by distance, and the central modeled share of mortality in distance bands. Panels D–F use C1’s reported facility capacity and C2’s permit-derived generating capacity with a 60% central capacity factor (300 MW for C1, modeled average output 180 MW; 1,240.5 MW for C2, modeled average output 744.3 MW). For the distance-based summaries, distance is measured from the datacenter site to the location of the attributable mortality burden; it does not represent the distance that pollution travels from an emitting source. Panels A, B, D, and E show central estimates with whiskers or shading from the reported 95% intervals. Distance-band shares in panels C and F are central deterministic allocations of the InMAP fields. Matched-load rows use the published Pope/COBRA coefficient limits; site-capacity rows additionally propagate the 40–80% capacity-factor distribution through 10,000 Monte Carlo draws.

2. Methods
We designed the analysis to separate the health implications of how electricity is supplied (from the grid vs. the datacenter’s own power plant) from those of how large the datacenter is in terms of how much electricity it consumes. We compare these electricity-supply pathways under two scenarios: a hypothetical matched-demand scenario that assumes that C1 and C2 have the same electricity demand and a real-world scenario based on the reported and permitted capacities of the two facilities under specified operating assumptions. Across both scenarios, we trace emissions through atmospheric transport, population exposure, and PM-attributable mortality to characterize the magnitude and distribution of the resulting health burden.
2.1. Study Design and Data Sources
We compare a modeled grid-supply pathway anchored at C1 in Memphis, Tennessee, with C2 and its colocated BTM power plant near Southaven, Mississippi. Their proximity places both projects in the same local setting, while the modeled electricity-supply configurations create distinct emission-source geographies. For the grid pathway, our goal is to represent a datacenter supplied entirely by the public grid, so that it can be compared cleanly with the BTM pathway. We therefore model a grid-supply counterfactual: a hypothetical scenario in which all of C1’s electricity demand is met by the regional grid. We do not reconstruct the electricity C1 has actually used over time, because its historical supply has combined grid electricity with on-site generation. Modeling that mixture would blend the two pathways we aim to separate. In this counterfactual, C1 serves as the geographic anchor. Its location defines the site from which we measure distances to affected populations and the region over which we evaluate health impacts, while the emissions themselves are assigned to the marginal power plants that respond to its demand. The timing of the two facilities provides context for this approach: C1 became operational in 2024, and C2 became operational in January 2026 [16,17].
We conducted two main analyses: (i) a hypothetical matched-demand scenario, in which we supplied each datacenter with the same continuous 240-MW demand (2.1024 TWh/year) to compare the health implications of the two electricity-generation pathways; and (ii) a real-world facility-scale scenario, in which we compare the health implications of the two electricity-generation pathways under the reported 300 MW capacity of C1 and the permit-derived 1,240.5-MW capacity of C2 [18]. Because actual long-term utilization in the real-world facility-scale scenario is uncertain, we assumed an average annual operation equivalent to 60% of capacity, with a prespecified 40–80% operating range. With further expansion planned for both sites [19], the real-world scenario reflects the capacities of the specified facilities at one time rather than the full eventual buildout. The analysis combined datacenter and project records, regional power-system data, air-permit and emission-source information, Census population and demographic data, and county mortality records. Supplementary Text S1.1 defines the estimands, capacities, and data vintages; Supplementary Tables S1 and S4 document the inputs and access points retained.
2.2. Emission Inventory Construction
C1 is located in the service territory of Memphis Light, Gas and Water, which purchases all of its electricity from Tennessee Valley Authority (TVA) [20]. For C1, we represented the modeled grid-supply pathway using the additional emissions from power plants that increased generation in response to added datacenter demand. We estimated this marginal response with EPA AVERT using its 2023 Tennessee region, an aggregate of balancing authorities that represents the TVA system and extends beyond the state boundary [21]. For C2, we represented the BTM pathway using the permit-based inventory of 41 turbines and 10 pressure-reduction stations, including emissions during normal operation and turbine startup and shutdown. We represented each load scenario at the emission-inventory stage, before atmospheric modeling. Both inventories retained source-specific emissions, locations, and release characteristics. We modeled directly emitted PM together with SO, NO, NH, and volatile organic compounds as precursors to secondary PM formation. The 2020 National Emissions Inventory supplied release information for the grid sources [22], while the C2 air permit supplied source and release specifications for the BTM inventory [18]. Supplementary Text S1.2 describes load construction, source matching, emission scaling, and reconciliation.
2.3. Dispersion and Population Exposure Modeling
To estimate annual increments in primary and secondary PM, we modeled both emission inventories using InMAP v1.9.0, a reduced-complexity atmospheric transport and chemistry model [23,24]. Both pathways used 4 × 4 km InMAP cells and the same underlying meteorological and atmospheric chemistry fields.
We used separate regional domains to capture the different spatial extents of the two emission-source configurations. For C1, the modeled grid-supply pathway includes power plants distributed across the Tennessee Valley Authority region, requiring a substantially larger modeling domain (1,632 × 1,524 km). In contrast, the BTM sources for C2 form a compact cluster near the datacenter and were modeled within a smaller regional domain (828 × 712 km). Importantly, the choice of domain does not alter the emissions assigned to either pathway. It determines the spatial area over which those emissions are transported and their population-health effects are evaluated. For instance, in the matched 240-MW analysis, electricity demand is held constant while the source geography—and consequently the spatial distribution of exposure and health burden—differs between the two generation pathways. Each domain contains the complete modeled source inventory and surrounding receptor area, so regional health estimates correspond to the respective site-specific modeling domain. Supplementary Text S1.3, Supplementary Table S5, and Supplementary Figure S1 provide the model settings and geometric diagnostics. We used ZIP Code Tabulation Areas (ZCTAs) as the epidemiologic and reporting geography [25]. A common population surface linked Census tracts, counties, ZCTAs, and InMAP cells, allowing us to calculate the population-weighted PM increment within each ZCTA. Supplementary Text S1.3.3 describes the geographic crosswalk and population allocation.
2.4. Health and Health-Equity Impact Assessment
We combined population-weighted ZCTA-level incremental PM exposure, derived from InMAP concentrations using 2020 Census population data, with 2024 county-level mortality counts for adults aged 18 years and older obtained from CDC WONDER [23,26,27]. We then applied the Pope/COBRA log-linear concentration–response function to estimate annual attributable mortality [7,28]. Because the modeled PM increments are small relative to the long-term ambient concentrations represented in the underlying epidemiologic evidence, this calculation assumes that the published log-linear slope can be applied to marginal concentration changes. We evaluated all-cause nonaccidental, cardiovascular, and respiratory mortality. Cardiovascular and respiratory estimates apply the same CRF to their respective baseline mortality counts. Supplementary Text S1.4 gives the endpoint definitions, allocation procedure, health equation, and distance summaries; Supplementary Table S6 identifies the mortality extracts. We also described how each site’s regional mortality was distributed across joint neighborhood household-income and people-of-color strata, reporting each stratum’s share of regional mortality (Figure 4) and the corresponding mortality per 100,000 residents (Supplementary Figure S5). Supplementary Text S1.5 further describes the methods.
Figure 4.
Descriptive intersectional equity stratification for the site-capacity scenarios. Panels A and B show each household-income-by-people-of-color stratum’s percentage share of regional annual all-cause nonaccidental attributable mortality for C1 and C2, respectively. The central shares and saved joint 95% uncertainty intervals use the same population-weighted ZCTA-to-group crosswalk. Both panels use common demographic cutpoints and a common color scale; unrounded shares sum to 100% within each pathway. The corresponding population-normalized mortality and intervals appear in Supplementary Figure S5. These estimates derive from the complete site-specific health domains and 60% central capacity-factor scenarios in Figure 3. The stratification describes neighborhood contexts and does not estimate causal disparities.
Figure 4.
Descriptive intersectional equity stratification for the site-capacity scenarios. Panels A and B show each household-income-by-people-of-color stratum’s percentage share of regional annual all-cause nonaccidental attributable mortality for C1 and C2, respectively. The central shares and saved joint 95% uncertainty intervals use the same population-weighted ZCTA-to-group crosswalk. Both panels use common demographic cutpoints and a common color scale; unrounded shares sum to 100% within each pathway. The corresponding population-normalized mortality and intervals appear in Supplementary Figure S5. These estimates derive from the complete site-specific health domains and 60% central capacity-factor scenarios in Figure 3. The stratification describes neighborhood contexts and does not estimate causal disparities.

2.5. Uncertainty and Sensitivity Analyses
Throughout, we report 95% intervals rather than confidence intervals. For the hypothetical matched-demand scenario, these intervals propagate the published 95% coefficient limits of the Pope/COBRA CRF while holding the modeled load and concentration field fixed. For the real-world facility-scale scenario, they are the 2.5th–97.5th percentiles from the Monte Carlo analysis jointly propagating the 40–80% operating range and uncertainty in the Pope/COBRA CRF. These intervals do not incorporate uncertainty in emissions, atmospheric dispersion, population allocation, or baseline mortality. Supplementary Text S1.6 specifies the Monte Carlo procedure.
We examined four sensitivity categories. First, we replaced C1’s primary marginal-generation response with a generation-weighted attributional representation, allocating demand across TVA plants according to their observed annual generation using eGRID data [29]. Second, we directly modeled C1 at 120, 180, and 240 MW under both grid representations to assess how emissions, exposure, and mortality changed with demand. Supplementary Text 1.7.1–1.7.2, Supplementary Figures S2–S4, and Supplementary Table S2 describe these comparisons. Third, we replaced the primary Pope/COBRA coefficient with the Chen–Hoek natural-cause mortality coefficient [30]. We evaluated C1’s fixed-load analyses and both sites’ facility-scale analyses, retaining their respective uncertainty procedures. We also isolated the coefficient’s effect for C2 at fixed 60% operation, without sampling the capacity factor (Supplementary Text 1.7.3; Supplementary Table S9). Fourth, we compared C2 at 2 × 2 km and 4 × 4 km resolution at fixed 60% operation, equivalent to 744.3 MW, while retaining the same emissions and outer domain. This comparison evaluated regional and within-50-km mortality. Both fixed-operation C2 tests use CRF-only 95% intervals, unlike the primary facility-scale intervals that jointly propagate operation and health-response uncertainty (Supplementary Text 1.7.4; Supplementary Table S10). Supplementary Text 1.8 describes quality assurance and reproducibility checks.
3. Results
We identified 25 marginal power plants that contributed to the increased electricity demand for C1 for the modeled grid-supply pathway. Figure 1 maps their regional distribution and shows their contributions to the electricity response. Natural gas accounted for 71.3% of the response and coal for 28.7%. Cumberland was the largest individual contributor (12.2%), followed by Paradise (7.8%). In contrast, the C2 BTM pathway concentrated all 41 turbines and 10 pressure-reduction stations at one colocated generation site near the datacenter. Supplementary Figure S1 illustrates the source footprints and their relationship to the retained modeling domains.
3.1. Health Burden in the Hypothetical Matched-Demand Scenario
In the hypothetical matched-demand scenario, we assume that datacenters have the same continuous 240-MW electricity demand. The estimated annual PM increase for C1 extended throughout the regional grid-source network, while the increased annual PM for C2 was concentrated around the datacenter (Figure 2A–B). The corresponding population-weighted ZCTA additional annual exposure to PM retained this contrast: incremental PM was much more dispersed spatially in C1 than C2 (Figure 2C–D).
Under the hypothetical scenario of the same electricity demand, across the entire spatial domain, the annual excess of all-cause nonaccidental mortality attributable to PM was 10.83 (95% interval, 7.83–13.84) for C1 and 3.67 (2.65–4.68) for C2 (Figure 3A; Table 1). Parentheses give 95% intervals. The excess in mortality for C1 increased mainly at greater distances, while C2’s curve rose most rapidly near the site (Figure 3B). Most C1 mortality occurred at distances of at least 250 km, whereas most C2 mortality occurred within 50 km, with the largest share in the 0–25-km band followed by the 25–50-km band (Figure 3C). The cause-specific results followed the same regional and near-site ordering (Table 1).
3.2. Health Burden in the Real-World Scenario
In the real-world scenario, we estimated the additional exposure to PM and the corresponding excess attributable mortality using the reported 300-MW capacity of C1 and the permit-derived 1,240.5-MW capacity of C2 [18]. Under the 60% central operating assumption, these capacities corresponded to modeled average loads of 180 and 744.3 MW, respectively. Annual all-cause nonaccidental attributable mortality was 8.10 (4.60–12.38) for C1 and 11.35 (6.48–17.29) for C2 (Figure 3D; Table 1). These intervals jointly propagate operating and health-response uncertainty. The cumulative curves and distance-band shares retained the matched-demand pattern: C1 accumulated most mortality at distances of at least 250 km, while C2 accumulated most within 50 km (Figure 3E–F). The results for annual respiratory mortality and cardiovascular mortality are summarized in Table 1.
3.3. Distribution of Health Burden Across Population Groups
In the real-world scenario, the mortality burden varied considerably across the joint neighborhood income and people-of-color strata (Figure 4). For C1, the largest share of mortality burden occurred in the middle-income/low-people-of-color stratum, closely followed by the low-income/low-people-of-color stratum; shares decreased across income strata within the middle- and high-people-of-color groups. The smallest share occurred in the high-income/high-people-of-color stratum. For C2, the low-income/high-people-of-color stratum accounted for the largest share, while the low-income/low-people-of-color stratum accounted for the smallest. Within its low-income stratum, shares increased across people-of-color categories. The percentages describe each site’s regional mortality allocation across neighborhood strata, not individual-level differences.
3.4. Sensitivity Analyses
The four sensitivity categories produced three main patterns. First, replacing marginal dispatch with generation-weighted allocation roughly halved C1 regional mortality at 240 MW, from 10.83 (7.83–13.84) to 5.23 (3.78–6.67). Most mortality remained beyond 50 km from the datacenter, and the central regional estimate remained above C2’s matched-demand estimate. Across C1’s directly modeled 120-, 180-, and 240-MW loads, mortality increased approximately in proportion to demand (Supplementary Text 1.7.1–1.7.2; Supplementary Figures S2–S4; Supplementary Table S2). Second, at fixed 60% C2 operation, reducing cell size from 4 × 4 km to 2 × 2 km increased regional all-cause nonaccidental mortality from 11.35 (8.21–14.50) to 13.87 (10.03–17.71), a 22.2% increase. Mortality within 50 km increased from 9.31 (6.73–11.89) to 12.90 (9.33–16.47), a 38.6% increase. These intervals reflect CRF uncertainty only (Supplementary Text 1.7.4; Supplementary Table S10). Third, replacing Pope with Chen–Hoek lowered central all-cause mortality estimates by approximately 32%. At fixed 60% C2 operation, regional mortality was 7.71 (5.84–8.64), with CRF-only uncertainty. The central ordering of the two facility-scale estimates also remained unchanged under the joint-uncertainty analysis (Supplementary Text 1.7.3; Supplementary Table S9).
4. Discussion
This study makes three contributions. First, it extends the emerging concern around datacenter scale and proximity to urban populations by showing that the location of the electricity generation serving these facilities is itself a public-health consideration [1,6,31].
Second, the two-scenario comparison distinguishes the implications of electricity-supply pathway from those of datacenter size: in the hypothetical matched-demand scenario, the modeled grid-supply pathway produced greater additional exposure to PM and consequently greater excess annual mortality that affects a large geographical area, whereas the BTM pathway concentrated mortality closer to the datacenter. Moreover, in the real-world scenario, C2’s substantially greater capacity produced greater absolute regional and near-site excess exposure to PM and excess mortality under the specified operating assumptions. The generation-weighted sensitivity substantially reduced the estimated grid-related mortality burden but did not change the matched-demand ordering or the much greater near-site concentration of the BTM burden (Sec Section 3.4). Thus, the magnitude of the grid-related burden is specific to how the electricity-system response is represented and, for the primary analysis, to the 2023 TVA marginal generation response. It should not be generalized to regions with different marginal generation mixes.
Third, the equity analysis shows that these spatial differences can translate into different population distributions of burden, with the largest BTM-attributable mortality share occurring in the low-income, high-people-of-color stratum. These findings show why electricity demand or emissions intensity alone cannot describe the health implications of datacenter power.
Our results are consistent with a broader literature showing that the health consequences of electricity generation depend strongly on where and how generation occurs. Heath et al. found substantially higher population intake fractions for urban distributed generation than for centralized power plants, driven partly by closer proximity to populations and lower release heights [11]. More recent work similarly finds that 24/7 gas-turbine microgrids can generate meaningful health and equity burdens even when changes in regional air quality appear modest [32]. Olaguer et al. modeled a 25-MW gas turbine and a datacenter’s 10-MW backup generators at microscale and concluded that substantial deployment would be required to affect local air quality [33]. Colossus 2’s 1,240.5 MW capacity, which is nearly fifty times the 25-MW unit modeled by Olaguer et al., is that deployment.
However, distributed generation is not necessarily more harmful in every setting: Carreras-Sospedra et al. found that centralized generation could produce greater population exposure depending on plant location and atmospheric chemistry, while Jing and Venkatram showed that distributed generation could reduce short-term peak concentrations while increasing annual-average concentrations [10,34]. Our results help reconcile these findings by distinguishing regional from near-site burden rather than assigning one electricity pathway a single health ranking. They also complement studies of the interconnected grid showing that electricity-related PM mortality frequently occurs far from where electricity is consumed [35,36]; a recent national datacenter preprint reports a similar geographic separation between datacenter load and grid-related mortality [15]. Muller estimated roughly $25 billion in annual external damages from U.S. datacenter electricity consumption, allocating those damages through the grid characteristics of each facility’s location [37]. This approach assumes grid supply and does not represent a colocated facility whose emissions and affected population are both determined at the site. Finally, our equity pattern is directionally consistent with evidence that power-sector pollution and PM-related mortality vary across race and income [35,38], although our stratification is descriptive and does not estimate differential susceptibility.
4.1. Integrating Health and Equity Evidence into Datacenter Siting and Permitting
The expansion of behind-the-meter generation changes not only how datacenters are powered, but also where decisions about electricity generation are made. Under conventional grid supply, datacenter demand is met through a broader electricity system in which generation siting and emissions are governed through utility planning and environmental regulation. BTM configurations increasingly bring the siting of large computational loads and their dedicated generation into the same project-level decision. This shift makes the location of electricity generation—and the populations surrounding it—relevant when datacenter sites and power-supply configurations are selected.
Existing air-permitting frameworks address important but different questions. For major stationary sources, Prevention of Significant Deterioration review includes emissions controls, air-quality analysis, additional-impact analysis, and public participation, with air-quality modeling principally used to evaluate compliance with ambient standards [39]. EPA guidance separately encourages permitting authorities to consider demographic vulnerability, public-health data, cumulative impacts, and the distribution of potential health effects, but does not establish a single legally binding health-and-equity assessment framework [40]. This distinction parallels a broader environmental-health literature arguing that pollutant- and source-specific regulation can miss cumulative vulnerability and the distribution of health burden across populations [41,42].
For BTM datacenters, health and equity assessment is most useful prospectively, before generation location and supply configuration are fixed. Location-specific research shows that where emissions are reduced or introduced can materially affect population exposure and its distribution even when aggregate emissions are the policy target [43,44]. A formal health-and-equity assessment at the siting and permitting stage could extend conventional air-quality review by comparing feasible power-supply configurations in terms of attributable health burden, its spatial distribution, and its distribution across surrounding populations.
These findings suggest that epidemiological evidence should enter the datacenter governance pipeline before electricity-supply, siting, and permitting decisions are fixed. For colocated generation, evaluating permitted emissions alone can miss how continuously operating sources interact with nearby population density and existing vulnerability; for grid-connected facilities, focusing only on the datacenter site can miss health burdens transferred to communities surrounding marginal generating units. This distinction is particularly relevant for C1 and C2, where electricity demand, generation, and affected populations span a shared regional airshed. Health-impact assessment should accompany reliability, carbon, and energy assessments and evaluate both near-site and regional receptors [14,45]. The real-world scenario also shows that facility scale and expected operation matter and should be disclosed because a pathway with lower mortality per delivered TWh can still produce a larger cumulative burden when deployed at substantially greater scale (Supplementary Table S3). Permitting and infrastructure planning should consider expected operating load and cumulative health burden alongside per-unit emissions.
4.2. Limitations and Future Work
These results should be interpreted with the following considerations. First, the grid counterfactual remains model-dependent. AVERT represents consequential marginal dispatch, whereas the supplementary eGRID analysis provides an attributional, generation-weighted benchmark; neither identifies contractual electricity supply or observed real-time dispatch, and the difference between them shows that the estimated grid burden depends on this choice [9]. AVERT also treats regions as independent [46], so the grid pathway excludes generation changes in neighboring regions that would arise through altered imports or exports. Thus, the results are specific to the modeled TVA electricity system and should not be generalized to regions with different marginal generation mixes.
Second, observed long-term utilization and turbine-level operating schedules are unavailable. Thus, the real-world scenario uses a 60% central capacity factor with a prespecified 40–80% operating range and should not be interpreted as observed annual operation. For C2, BTM emissions were constructed by scaling the permit-based inventory to these modeled operating levels while retaining startup and shutdown emissions. This assumes that operating emissions scale with utilization and may not capture load-dependent changes in turbine efficiency or emission controls; the BTM estimates should be interpreted as scenario-based permit estimates rather than observed emissions. Third, the analysis covers one regional electricity system and two nearby sites, limiting generalizability across generation technologies, grid mixes, and population settings. Fourth, suppressed CDC WONDER counts can affect county baseline mortality, particularly for cause-specific endpoints, and baseline-mortality uncertainty is not included in the reported intervals (Supplementary Tables S7 and S8). Finally, the analysis is limited to PM-attributable mortality (primary and secondary) and does not capture morbidity or health effects from other pollutants.
Supplementary Materials
The following supporting information can be downloaded at the website of this paper posted on Preprints.org
Author Contributions
HG and FD conceptualized the study. HG conducted the analyses and drafted the manuscript. FD supervised the study and acquired funding. Both authors contributed to the review and editing of the manuscript.
Funding
We acknowledge support from the National Institutes of Health under grants R01MD016054 and R01ES037156.
Data Availability Statement
All data used in this study were obtained from publicly available sources. These include the C2 air permit and associated emissions documentation, EPA AVERT, eGRID, and National Emissions Inventory data, U.S. Census population and demographic data, CDC WONDER mortality data, and publicly available datacenter project records.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- International Energy Agency. Energy and AI. International Energy Agency Figure 1.12 on spatial concentration and proximity of facilities to urban areas. 2025. Available online: https://www.iea.org/reports/energy-and-ai.
- Smith, S.J.; Hubbard, A.; Newkirk, A.; Ganeshalingam, M.; Holecek, B.; Sartor, D.; Mills, M.; Shehabi, A. United states data center energy usage report: 2025 update. Technical report. Berkeley, CA (United States), 2026; Lawrence Berkeley National Laboratory (LBNL). [Google Scholar]
- Thomas, M. Bypassing the Grid: How Data Center Developers Are Building Their Own Power Plants. accessed. (accessed on 13 September 2026). Public report summary. Publication date not displayed.
- Jones, Erick C.; Jones, J. Erick C.S. Megawatts to Zettaflops: A Techno-Economic Framework for Grid-Tied Behind-the-Meter Architectures in AI Data Centers. Electricity 2026, 7, 43. [Google Scholar] [CrossRef]
- Cleanview. Free Data Center Tracker Tool. Dynamic U.S. datacenter project database. Dynamic database. Analysis snapshot: August 21, 2026 (3,357 project records; 59 behind-the-meter records). Landing page accessed. (accessed on 13 September 2026).
- International Energy Agency. Spatial concentration of various facilities versus proximity to urban areas, 2024 Chart accompanying Energy and AI; concentration is the inverse of the linearised Nearest Neighbour Index. IEA. 2025. Available online: https://www.iea.org/data-and-statistics/charts/spatial-concentration-of-various-facilities-versus-proximity-to-urban-areas-2024.
- Pope, C.A.; Lefler, J.S.; Ezzati, M.; Higbee, J.D.; Marshall, J.D.; Kim, S.Y.; Bechle, M.; Gilliat, K.S.; Vernon, S.E.; Robinson, A.L.; et al. Mortality risk and fine particulate air pollution in a large, representative cohort of U.S. adults. Environ. Health Perspect. 2019, 127, 077007. [Google Scholar] [CrossRef] [PubMed]
- U.S. Environmental Protection Agency. Technical Report EPA/600/R-22/028; Supplement to the 2019 Integrated Science Assessment for Particulate Matter. U.S. Environmental Protection Agency, Office of Research and Development, Center for Public Health and Environmental Assessment: Research Triangle Park, NC, 2022.
- Thind, M.P.S.; Wilson, E.J.; Azevedo, I.L.; Marshall, J.D. Marginal Emissions Factors for Electricity Generation in the Midcontinent ISO. Environ. Sci. Technol. 2017, 51, 14445–14452. [Google Scholar] [CrossRef] [PubMed]
- Carreras-Sospedra, M.; Vutukuru, S.; Brouwer, J.; Dabdub, D. Central Power Generation versus Distributed Generation—An Air Quality Assessment in the South Coast Air Basin of California. Atmos. Environ. 2010, 44, 3215–3223. [Google Scholar] [CrossRef]
- Heath, G.A.; Granvold, P.W.; Hoats, A.S.; Nazaroff, W.W. Intake Fraction Assessment of the Air Pollutant Exposure Implications of a Shift toward Distributed Electricity Generation. Atmos. Environ. 2006, 40, 7164–7177. [Google Scholar] [CrossRef]
- Gour, N.; Ortiz, L.; Maibach, E. Health Implications of the Rapid Rise of Data Centers in Virginia: An Exploratory Assessment. Front. Clim. 2026, 8, 1648912. [Google Scholar] [CrossRef]
- Guidi, G.; Dominici, F.; Gilmour, J.; Butler, K.; Bell, E.; Delaney, S.; Bargagli-Stoffi, F.J. Environmental Burden of United States Data Centers in the Artificial Intelligence Era. 2024, 2411.09786. [Google Scholar] [CrossRef]
- Han, Y.; Wu, Z.; Li, P.; Wierman, A.; Ren, S. Health-Informed Computing: Estimating and Addressing the Public Health Impact of Data Centers. arXiv 2024, arXiv:2412.06288. [Google Scholar]
- Chen, Y.; Wang, S.; Senga, J.R.L.; White, A.S.; Wong, A.Y.H.; Freese, L.M.; Bell, M.L.; Selin, N.E. Air Quality and Health Impacts of Data Center Electricity Demand in the United States. EarthArXiv 2026. [Google Scholar] [CrossRef]
- Trueman, C. xAI’s Memphis Supercluster has gone live, with up to 100,000 Nvidia H100 GPUs, 2024. Accessed. (accessed on 4 October 2026). [PubMed]
- Musk, E. Announcement of Colossus 2 operation and planned expansion, 2026. 17 January 2026. Available online: https://perma.cc/CB7S-Z9VW (accessed on 4 October 2026).
- Mississippi Department of Environmental Quality. MZX Tech LLC: Draft Air PSD Construction Permit and Application Records. Mississippi DEQ public permit records. Available online: https://opc.deq.state.ms.us/ensearchonline/epd-active-permits-and-coverages.
- Space Exploration Technologies Corp. Prospectus for the public offering to retail investors, 2026. Accessed. (accessed on 4 October 2026).
- Memphis Light, Gas and Water. General. FAQ Commer. Cust. Accessed. 2026. (accessed on 6 October 2026). [CrossRef] [PubMed]
- U.S. Environmental Protection Agency. AVERT: Avoided Emissions and Generation Tool, version 4.3. U.S. Environmental Protection Agency. 2024. Tennessee 2023 regional data file and marginal-generation scenario. Available online: https://www.epa.gov/avert.
- U.S. Environmental Protection Agency. 2020 National Emissions Inventory (NEI) Point-Source Data Release-point coordinates and stack metadata used for source matching. 2023. Available online: https://www.epa.gov/air-emissions-inventories/national-emissions-inventory-nei.
- Tessum, C.W.; Hill, J.D.; Marshall, J.D. InMAP: A model for air pollution interventions. PLoS ONE 2017, 12, e0176131. [Google Scholar] [CrossRef] [PubMed]
- InMAP development team. InMAP Evaluation Data, Version 1.6.1. Release data. Available online: https://github.com/spatialmodel/inmap/releases/tag/v1.6.1.
- U.S. Census Bureau. TIGER/Line Shapefiles, 2024: ZIP Code Tabulation Areas. 2024. Available online: https://www.census.gov/geographies/mapping-files/time-series/geo/tiger-line-file.2024.html.
- U.S. Census Bureau. 2020 Census Demographic Profile (DP1). 2021. Available online: https://data.census.gov.
- Centers for Disease Control and Prevention; National Center for Health Statistics. Multiple Cause of Death, on CDC WONDER Online Database County-level extraction for 2024, single-year ages 18–100+. 2025. Available online: https://wonder.cdc.gov/mcd-icd10-expanded.html.
- U.S. Environmental Protection Agency. CO–Benefits Risk Assessment (COBRA) Health Impacts Screening and Mapping Tool, version 5.2. 2024. Available online: https://www.epa.gov/cobra.
- U.S. Environmental Protection Agency. Emissions & Generation Resource Integrated Database (eGRID) 2023. Plant-level generation and emissions data. 2025. Available online: https://www.epa.gov/egrid.
- Chen, J.; Hoek, G. Long-term exposure to PM and all-cause and cause-specific mortality: A systematic review and meta-analysis. Environ. Int. 2020, 143, 105974. [Google Scholar] [CrossRef] [PubMed]
- Siddik, M.A.B.; Shehabi, A.; Marston, L.T. The Environmental Footprint of Data Centers in the United States. Environ. Res. Lett. 2021, 16, 064017. [Google Scholar] [CrossRef]
- Razeghi, G.; Mac Kinnon, M.; Wu, K.; Matthews, B.; Zhu, S.; Samuelsen, S. Air Quality Assessment of a Mass Deployment of Microgrids. Sci. Total Environ. 2024, 947, 174632. [Google Scholar] [CrossRef] [PubMed]
- Olaguer, E.P.; Knipping, E.; Shaw, S.; Ravindran, S. Microscale Air Quality Impacts of Distributed Power Generation Facilities. J. Air Waste Manag. Assoc. 2016, 66, 795–806. [Google Scholar] [CrossRef] [PubMed]
- Jing, Q.; Venkatram, A. The Relative Impacts of Distributed and Centralized Generation of Electricity on Local Air Quality in the South Coast Air Basin of California. Energy Policy 2011, 39, 4999–5007. [Google Scholar] [CrossRef]
- Thind, M.P.S.; Tessum, C.W.; Azevedo, I.L.; Marshall, J.D. Fine Particulate Air Pollution from Electricity Generation in the US: Health Impacts by Race, Income, and Geography. Environ. Sci. Technol. 2019, 53, 14010–14019. [Google Scholar] [CrossRef] [PubMed]
- Hennessy, E.M.; de Chalendar, J.A.; Benson, S.M.; Azevedo, I.M.L. Distributional Health Impacts of Electricity Imports in the United States. Environ. Res. Lett. 2022, 17, 064011. [Google Scholar] [CrossRef]
- Muller, N.Z. Measuring the Impact of Data Centers in the United States Economy: Monetary Damage from Air Pollution and Greenhouse Gas Emissions. In NBER Working Paper 35100; National Bureau of Economic Research, 2026. [Google Scholar] [CrossRef]
- Josey, K.P.; Delaney, S.W.; Wu, X.; Nethery, R.C.; DeSouza, P.; Braun, D.; Dominici, F. Air Pollution and Mortality at the Intersection of Race and Social Class. N. Engl. J. Med. 2023, 388, 1396–1404. [Google Scholar] [CrossRef] [PubMed]
- U.S. Environmental Protection Agency. Prevention of Significant Deterioration Basic Information. U.S. Environmental Protection Agency, New Source Review Permitting, 2025. 15 December 2025. [Google Scholar]
- U.S. Environmental Protection Agency. EJ in Air Permitting: Principles for Addressing Environmental Justice Concerns in Air Permitting. U.S. Environmental Protection Agency, Office of Air and Radiation, 2022. [Google Scholar]
- Morello-Frosch, R.; Zuk, M.; Jerrett, M.; Shamasunder, B.; Kyle, A.D. Understanding the Cumulative Impacts of Inequalities in Environmental Health: Implications for Policy. Health Aff. 2011, 30, 879–887. [Google Scholar] [CrossRef] [PubMed]
- Yuen, T.K.; Payne-Sturges, D. Using Health Impact Assessment to Integrate Environmental Justice into Federal Environmental Regulatory Analysis. New Solut. 2013, 23, 439–466. [Google Scholar] [CrossRef] [PubMed]
- Wang, Y.; Apte, J.S.; Hill, J.D.; Ivey, C.E.; Patterson, R.F.; Robinson, A.L.; Tessum, C.W.; Marshall, J.D. Location-Specific Strategies for Eliminating U.S. National Racial-Ethnic PM2.5 Exposure Inequality. Proc. Natl. Acad. Sci. 2022, 119, e2205548119. [Google Scholar] [CrossRef] [PubMed]
- Mehdi, Q.; Vasilakos, P. Assessing the Environmental Justice Implications of Decarbonizing the US Electric Grid: Estimating Changes in Asthma Exacerbation by Race and Income. Environ. Res. Health 2024, 2, 045003. [Google Scholar] [CrossRef]
- Farkas, C.M.; Moeller, M.D.; Felder, F.A.; Henderson, B.H.; Carlton, A.G. High Electricity Demand in the Northeast U.S.: PJM Reliability Network and Peaking Unit Impacts on Air Quality. Environ. Sci. Technol. 2016, 50, 8375–8384. [Google Scholar] [CrossRef] [PubMed]
- U.S. Environmental Protection Agency. AVERT Questions and Answers, 2026. Accessed. (accessed on 6 October 2026).
Table 1.
Modeled PM-attributable mortality by scenario, datacenter, and mortality endpoint.
| Scenario | Datacenter (pathway; mean load) | Mortality endpoint | Mortality per year | Mortality per year within 50 km |
| Matched load | Colossus 1 (AVERT; 240 MW) | All-cause nonaccidental | 10.833 (7.831–13.835) | 0.276 (0.199–0.352) |
| Respiratory | 1.188 (0.859–1.517) | 0.024 (0.018–0.031) | ||
| Cardiovascular | 3.473 (2.510–4.435) | 0.092 (0.066–0.117) | ||
| Colossus 2 (BTM; 240 MW) | All-cause nonaccidental | 3.667 (2.651–4.683) | 3.006 (2.173–3.839) | |
| Respiratory | 0.335 (0.242–0.428) | 0.265 (0.191–0.338) | ||
| Cardiovascular | 1.229 (0.888–1.569) | 1.000 (0.723–1.277) | ||
| Site capacity (60% capacity factor) | Colossus 1 (AVERT; 180 MW) | All-cause nonaccidental | 8.102 (4.598–12.382) | 0.207 (0.119–0.315) |
| Respiratory | 0.888 (0.504–1.358) | 0.018 (0.011–0.028) | ||
| Cardiovascular | 2.597 (1.474–3.969) | 0.069 (0.040–0.105) | ||
| Colossus 2 (BTM; 744.3 MW) | All-cause nonaccidental | 11.352 (6.477–17.292) | 9.308 (5.311–14.178) | |
| Respiratory | 1.038 (0.592–1.581) | 0.820 (0.468–1.249) | ||
| Cardiovascular | 3.805 (2.171–5.795) | 3.097 (1.767–4.717) |
Values are attributable deaths per year with 95% intervals. “Mortality per year” is the total over the complete site-specific
study domain; the second estimate is the corresponding reporting summary within 50 km of the datacenter. Matchedload
intervals propagate the Pope/COBRA concentration-response coefficient interval. Site-capacity intervals jointly
propagate the 40–80% capacity-factor distribution and the concentration–response coefficient interval through 10,000
Monte Carlo draws. The all-cause endpoint is all-cause nonaccidental mortality; respiratory and cardiovascular rows use
the corresponding CDC WONDER endpoints.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |