Abstract
Sensor degradation and measurement variability are inevitable in industrial environments, where harsh conditions, aging components, and dynamic processes continuously affect measurement quality. The critical challenge is not simply detecting when variability increases existing statistical methods accomplish this effectively but determining the root cause. A drifting sensor and a changing process can produce identical variance signatures in the data, leading operators to either replace functioning sensors unnecessarily or overlook genuine sensor faults while investigating phantom process issues. This diagnostic ambiguity results in wasted maintenance effort and delayed problem resolution. This review paper examines variance-change detection methods for industrial sensor networks and proposes a digital twin framework that moves beyond detection to diagnosis. Statistical methods including rolling variance, Shewhart charts, CUSUM, EWMA, and change-point detection are reviewed. The paper establishes sensor drift as sustained high-variation behavior. Multi-sensor approaches such as PCA and autoencoders are discussed for capturing inter-sensor relationships. The proposed framework uses machine learning models to learn normal sensor relationships, then analyzes prediction error patterns across multiple sensors. A thermal monitoring case study demonstrates how these multivariate patterns distinguish sensor-specific faults from process-wide disturbances.
Keywords:
high variation detection
; sensor monitoring
; digital twin
; random forest
; statistical process control
; industrial monitoring
; predictive maintenance
1. Introduction
Industrial manufacturing has entered an era where sensor networks form the nervous system of production monitoring temperatures in large furnaces, pressures in chemical reactors, vibrations in rotating machinery, and flows in pharmaceutical processes. These sensors feed control loops, trigger safety interlocks, and generate the data streams that drive quality assurance. Yet this dependence creates a critical vulnerability: when sensor measurements become unreliable, consequences cascade silently through operations. Unlike catastrophic failures that trigger immediate alarms, periods of elevated measurement variability often escape detection until their effects surface as rejected batches, equipment damage, or regulatory violations. A temperature sensor drifting by 2°C in a pharmaceutical reactor can invalidate a production batch worth millions; a pressure transmitter exhibiting high variance in a pipeline can mask a genuine leak or trigger costly false shutdowns.
The diagnostic challenge is severe. Industry studies reveal that up to 63% of instrument-related maintenance calls find no problems with suspected equipment, while 75% of control valves pulled for maintenance do not actually need [12]. Six out of ten troubleshooting calls trace back to sensors, transmitters, valves, or connecting wiring [13], yet distinguishing sensor faults from process disturbances remains fundamentally difficult. Elevated variance in a temperature reading can originate from sensor degradation or legitimate process variability and the correct diagnosis determines whether maintenance teams should replace the sensor, investigate upstream conditions, or adjust process parameters. Univariate statistical methods detect that variance has increased but cannot identify the source. Threshold-based alarms trigger when readings exceed limits but cannot differentiate a malfunctioning sensor from a genuine process excursion. The result is chemical manufacturing facilities losing $100,000–$125,000 per hour during unplanned downtime [14], driven by misdirected maintenance, unnecessary replacements, and delayed root cause identification.
Figure 1 contextualizes this diagnostic challenge within a representative industrial facility, where concurrent failure modes motor degradation, pipeline leakage, and process disturbances each impose distinct perturbations on the shared measurement stream. The central time series, marked by a single anomalous high-variation excursion, encapsulates the fundamental ambiguity: elevated variance is statistically observable, yet its causal origin remains unresolvable through univariate signal inspection alone. This diagnostic limitation whether an excursion reflects instrumentation degradation or legitimate process variation directly underlies the misdirected maintenance interventions, unnecessary sensor replacements, and substantial unplanned downtime costs documented above.
Three converging trends make solving this problem increasingly urgent. First, modern plants deploy thousands of sensors generating terabytes of data daily [33], making manual monitoring impossible and automated detection essential. Second, predictive maintenance has become mainstream nearly half of major manufacturers now operate dedicated teams [1] yet these initiatives depend on reliable sensor data that current monitoring methods cannot guarantee. Third, industrial processes continue tightening tolerances and integrating subsystems, amplifying the consequences of measurement unreliability across production lines [7]. The technology exists to address this challenge: machine learning, digital twins, and multivariate statistical methods offer powerful capabilities. What has been lacking is a unified framework connecting these tools to the specific problem of high-variation detection and sensor-versus-process diagnosis. This paper makes the following contributions:
- 1.
- It reviews and categorizes variance-change detection methods for industrial sensor networks, emphasizing their diagnostic limitations.
- 2.
- It unifies high-variation detection and sensor drift under a common statistical perspective based on persistence of variance behavior.
- 3.
- It introduces a digital twin–based reference framework that reframes high-variation detection as multivariate prediction error monitoring rather than univariate signal analysis.
- 4.
- It demonstrates, through an illustrative case study, how residual correlation patterns enable discrimination between sensor-specific faults and process-wide disturbances.
The remainder of this paper is organized as follows: Section II reviews conventional univariate approaches to variance-change detection. Section III establishes the connection between high-variation moments and sensor drift. Section IV examines multi-sensor monitoring methods. Section V introduces the digital twin framework. Section VI illustrates the framework using a thermal monitoring system. Section VII concludes with limitations and future directions
2. Conventional Univariate Approaches
The methods reviewed in this section were developed for monitoring individual sensor streams to detect when measurement variability deviates from normal levels [5,8]. Each method represents a different approach to answering the fundamental question of whether variance has increased, with distinct tradeoffs between detection speed, sensitivity to different types of changes, computational requirements, and false alarm characteristics. Understanding these tradeoffs is essential for selecting appropriate methods for specific industrial applications.
2.1. Rolling Variance
Rolling variance represents the most intuitive approach to variance monitoring. A sliding window of fixed length moves through the time series data, and at each position the variance or standard deviation of values within the window is calculated. This local variance estimate is compared against a baseline variance established during a period of stable operation. When the ratio of current variance to baseline variance exceeds a predefined threshold, typically set between two and four times the baseline, an alert is generated indicating a high variation moment.
This method detects high variation through direct measurement of spread. Any sustained increase in the scatter of readings causes the rolling variance to rise, and when this rise exceeds the threshold the detection occurs. The window length controls the tradeoff between estimation stability and detection speed, with longer windows of 40-50 samples providing stable estimates but delaying detection, while shorter windows of 15-25 samples respond quickly but may false-alarm on transient spikes. The threshold selection balances sensitivity against false alarm rate, with lower thresholds catching smaller changes but generating more false alerts. This method offers simple implementation, minimal computational requirements suitable for edge deployment, and intuitive interpretation, but lacks formal statistical properties for false alarm control and cannot accumulate evidence for gradual changes. Rolling variance is best suited for real-time monitoring on resource-constrained systems and detecting obvious variance spikes.
2.2. Shewhart Control Charts
Shewhart control charts provide rigorous frameworks for variance monitoring with well-defined statistical properties [2,8]. Consecutive measurements are grouped into rational subgroups of typically four to six samples each. For each subgroup, either the standard deviation is calculated for an S-chart or the range is calculated for an R-chart, and this statistic is plotted against control limits. The control limits are established at three standard deviations from the centerline based on the expected distribution of the subgroup statistic during normal operation, ensuring that approximately 99.73 % of subgroup statistics fall within limits when the process is stable.
Shewhart charts detect high variation by identifying statistically improbable events. A subgroup variance exceeding the upper control limit has less than 0.27 percent probability of occurring during normal operation, so such an exceedance provides strong statistical evidence that process variability has changed. The rigorous statistical foundation, well-defined false alarm rates, and clear visual interpretation make Shewhart charts the industry standard for manufacturing quality control [9]. However, their memoryless property where each subgroup is evaluated independently limits sensitivity to small or gradual changes in variance, as shifts smaller than 1.5 standard deviations may require many subgroups to detect reliably. Shewhart charts are best suited for detecting large sudden variance shifts and for applications requiring statistical rigor and audit compliance.
Although univariate variance-change detection methods effectively identify deviations from normal behavior, they lack the contextual information required to determine whether increased variability originates from sensor degradation or from process disturbances, as illustrated in Figure 2.
2.3. CUSUM
Cumulative Sum charts detect changes by continuously accumulating small deviations over time rather than evaluating each measurement independently [3]. The method maintains a running cumulative sum that tracks how consistently measurements deviate from expected behavior. For variance monitoring, the chart tracks whether squared deviations from the mean are consistently larger than expected. Small positive deviations add to the cumulative sum while deviations in the expected direction reset or reduce it through an allowance parameter. When the cumulative sum exceeds a decision threshold, a high variation condition is declared and the chart is reset.
CUSUM detects high variation by accumulating evidence of persistent deviation. Individual measurements that are only slightly more variable than normal may not trigger an alert on their own, but twenty consecutive slightly-elevated readings will accumulate evidence until the threshold is breached. This makes CUSUM highly effective at detecting small but persistent increases in variability that Shewhart charts would miss, making it well-suited for identifying gradually increasing sensor noise or slowly evolving process instability. The allowance parameter controls sensitivity to specific shift magnitudes and the decision threshold controls false alarm rate, both requiring careful tuning for the application. Because evidence is accumulated over time, CUSUM may respond more slowly to large abrupt changes compared to Shewhart charts. CUSUM is best suited for monitoring gradual variance increases and quality-critical processes where early detection of subtle shifts is important.
2.4. EWMA
The Exponentially Weighted Moving Average chart monitors changes by computing a smoothed estimate that combines recent and past observations with recent data given more weight while older data gradually fades [4,8]. For variance monitoring, squared deviations from the mean are smoothed using this exponential weighting scheme. The smoothed statistic is compared to control limits established based on the expected distribution of the EWMA statistic during stable operation. A single tuning parameter controls the degree of smoothing, with lower values providing more smoothing and higher values making the statistic more responsive to recent data.
EWMA detects high variation by tracking trends in variability while filtering out noise. The smoothing process dampens the impact of isolated spikes, so a single noisy reading has limited effect on the statistic. However, persistent elevation in variance causes the EWMA statistic to steadily rise until it breaches the control limit. This provides an effective balance between responsiveness and robustness, with clear visualization of how variability evolves over time. The smoothing delays detection of sudden large changes, making EWMA less suitable for identifying abrupt failures or step changes in variance. EWMA is best suited for long-term sensor health monitoring and noisy environments where false alarms must be minimized while maintaining sensitivity to sustained high variation periods.
2.5. Change-Point Detection
Change-point detection methods aim to identify the exact time at which a sensor’s variability changed rather than providing continuous monitoring with rolling alerts [5,10]. These methods analyze the time series to divide it into segments where statistical properties remain stable, with each detected change point marking a transition between different variability regimes. Likelihood-based approaches evaluate whether the data is better explained as a single stable regime or as multiple segments with different variance levels. Binary segmentation is a practical approach that repeatedly searches for the most prominent change point, splits the data at that location, and applies the same procedure to each resulting segment. The PELT algorithm[10] improves upon basic segmentation by efficiently finding the optimal set of change points using dynamic programming and pruning rules. Bayesian approaches incorporate prior knowledge about how frequently changes are expected and produce probabilistic estimates of change point locations.
Change-point detection identifies high variation moments by finding the optimal segmentation where each segment has constant variance, with change points marking where variance shifted. This precisely identifies when high variation began and ended rather than simply alerting that something is wrong, enabling accurate root cause analysis and correlation with operational events such as maintenance actions, feedstock changes, or equipment failures. The methods can detect multiple change points within a single dataset and quantify uncertainty in detection results through Bayesian formulations. However, most change-point techniques are designed for retrospective analysis and require access to a complete dataset, limiting their use for real-time monitoring. Detection performance depends on penalty parameters that control the tradeoff between detecting true changes and over-fitting. Change-point detection is best suited for post-incident root cause analysis, determining the onset and duration of high variation periods, and validating alarms raised by real-time monitoring methods.
2.6. Wavelet-Based Methods
Wavelet-based methods analyze sensor signals by decomposing them into components representing different time scales[15]. The wavelet transform separates the signal into high-frequency components that capture rapid fluctuations and low-frequency components that capture slow trends. Variance can then be monitored separately at each scale by tracking the energy in wavelet coefficients at different decomposition levels. High-frequency components typically correspond to measurement noise while low-frequency components reflect genuine process behavior or sensor health changes.
Wavelet methods detect high variation by examining variance changes at different time scales independently. An increase in high-frequency variance suggests increased measurement noise from sensor degradation or electrical interference, while an increase in low-frequency variance suggests changes in the underlying process behavior. This separation enables more targeted diagnosis than methods that treat variability as a single quantity. The approach is effective for non-stationary signals where statistical properties change over time and can detect short-lived high variation moments that are hidden within noisy data. However, wavelet methods are more complex to configure and interpret than time-domain approaches, with results depending on the choice of wavelet function and the number of decomposition levels. Edge effects must be handled carefully for real-time applications. Wavelet methods are best suited for signals with mixed time-scale behavior and for distinguishing measurement noise from process variability.
2.7. Summary
Each method reviewed in this section answers the question of whether variance is increasing through a different mechanism with distinct tradeoffs. Rolling variance provides direct measurement with fast response but lacks formal statistical properties. Shewhart charts offer rigorous false alarm control but are insensitive to small shifts. CUSUM and EWMA accumulate evidence effectively for gradual changes but may delay detection of sudden large shifts. Change-point detection precisely locates when changes occurred but is primarily retrospective. Wavelet methods separate different time scales but add complexity. The choice depends on whether high variation moments are expected to be sudden or gradual, whether real-time response is required, what false alarm rate is acceptable, and whether computational resources are limited. For sudden large variance spikes, rolling variance or Shewhart charts are appropriate. For gradually increasing variability, CUSUM or EWMA perform better. For post-event analysis, change-point detection provides the most information. For separating noise from process effects, wavelet methods are valuable. The fundamental limitation shared by all these methods is that they monitor each sensor relative to its own history without modeling relationships between sensors.
Table 1.
Univariate Variance-Change Detection Methods.
| Method | Gradual | Sudden | Real-Time | Complexity |
|---|---|---|---|---|
| Rolling Variance | Weak | Strong | Yes | Low |
| Shewhart Charts | Weak | Strong | Yes | Low |
| CUSUM | Strong | Limited | Yes | Low |
| EWMA | Strong | Limited | Yes | Low |
| Change-Point Detection | Strong | Strong | No | Medium |
| Wavelet-Based Methods | Strong | Strong | Partial | High |
3. From High-Variation Moments to Sensor Drift
High-variation moments in sensor measurements represent periods during which the statistical behavior of a sensor deviates from its historical or expected characteristics. While short-term fluctuations and transient noise are inherent to any measurement system, a subset of these high-variation moments correspond to persistent and systematic changes in measurement behavior, commonly referred to as sensor drift. Importantly, sensor drift is not an absolute property of the raw signal; rather, it is a relative and statistical phenomenon that emerges through sustained changes in measurement error characteristics over time when compared against a reference, expected process behavior, or historical baseline.[8,9,11]
3.1. Drift as Sustained High-Variation Behavior
From this perspective, sensor drift can be viewed as a specific class of high-variation behavior in which changes in bias, variance, sensitivity, or correlation structure persist across defined time windows instead of dissipating as random noise or isolated anomalies. Figure 2. illustrates six common drift mechanisms: bias drift appears as gradual mean shift, gain drift as changing signal amplitude, random walk as expanding variance over time, aging drift as monotonic degradation, noise-induced drift as increasing measurement scatter, and calibration loss as simultaneous offset and sensitivity change. As a result, most drift identification strategies rely on error analysis and the quantification of measurement uncertainty, rather than direct inspection of raw sensor values. Changes in the mean, variance, slope, or distribution of residuals during stable operating conditions provide stronger and more interpretable evidence of drift than signal-level trends alone.
Figure 3.
Illustration of sensor drift mechanisms. (a) Bias drift: gradual shift in measurement mean. (b) Gain drift: progressive change in sensor sensitivity. (c) Random walk drift: variance accumulates over time. (d) Aging drift: monotonic degradation trend. (e) Noise-induced drift: measurement scatter increases. (f) Calibration loss: simultaneous shift in offset and gain.
Figure 3.
Illustration of sensor drift mechanisms. (a) Bias drift: gradual shift in measurement mean. (b) Gain drift: progressive change in sensor sensitivity. (c) Random walk drift: variance accumulates over time. (d) Aging drift: monotonic degradation trend. (e) Noise-induced drift: measurement scatter increases. (f) Calibration loss: simultaneous shift in offset and gain.

3.2. Unified Framework for Drift Detection
Because drift manifests as a sustained alteration in statistical properties, the same statistical and machine learning techniques used to identify and characterize high-variation moments such as control charts, variance analysis, regression monitoring, and residual-based modeling are naturally applicable to drift detection when augmented with persistence and stability criteria. This unified framing highlights that drift detection is fundamentally an extension of measurement variability analysis, with emphasis placed on temporal consistency and systematic deviation rather than instantaneous magnitude.
3.3. Drift Mechanism Summary
Table 2 summarizes common sensor drift mechanisms as distinct forms of sustained high-variation behavior and maps each mechanism to the corresponding statistical approaches used for their identification. This table provides a unified view showing that drift detection methods are extensions of the high-variation detection methods reviewed in this section, with additional emphasis on persistence and systematic deviation.
4. Multi-Sensor System Monitoring
The methods reviewed in this section extend variance monitoring to multi-sensor systems, leveraging relationships between sensors to improve detection performance. Industrial facilities contain networks of interconnected sensors, and analyzing each sensor in isolation discards valuable relational information.
4.1. Limitations of Single-Sensor Analysis
Monitoring sensors individually creates several challenges in industrial environments. Scalability becomes problematic when facilities with hundreds or thousands of sensors require parallel monitoring instances, each generating alerts that must be reviewed and actioned, potentially overwhelming operators and maintenance teams. Context blindness occurs because an isolated variance increase has different implications depending on what other sensors are simultaneously experiencing, and without system-level context operators cannot assess the scope or severity of detected anomalies. Redundant alerts occur when a single underlying cause affects multiple sensors, generating separate alerts for each that must be manually correlated. Distinguishing sensor faults from process disturbances becomes difficult because both can cause increased variability in individual sensor readings, but appropriate responses differ significantly.[9,11]
4.2. Parallel Detection with Pattern Analysis
The simplest extension to multi-sensor monitoring applies detection methods in parallel across the sensor network and aggregates results for system-level analysis. Each sensor stream feeds one or more detection algorithms configured with sensor-specific parameters, producing both binary alert signals and continuous severity metrics. Alert signals from all sensors are collected into a unified time-synchronized view with normalization to enable meaningful comparison across sensors with different operating ranges. The analysis layer examines patterns across aggregated alerts, recognizing that the spatial pattern of alerts provides information beyond what any single sensor can offer. When multiple related sensors show high variation simultaneously, a process disturbance is more likely than individual sensor faults. When a single sensor shows high variation while related sensors remain stable, a sensor-specific issue is indicated. This pattern-based reasoning provides a framework for scoping investigation but relies on heuristic rules rather than modeling actual relationships between sensors.
4.3. PCA-Based Multivariate Monitoring
Principal Component Analysis learns the normal correlation structure among sensors during healthy operation by identifying the primary directions of variation in multi-sensor data [11]. New data is projected onto these learned directions, and two statistics are monitored to detect anomalies. The Hotelling T-squared statistic captures variation along the learned principal component directions, representing systematic variation that is consistent with normal sensor relationships[11]. The Squared Prediction Error or Q statistic captures variation outside the learned directions, representing residual variation that breaks normal relationships. High systematic variation with low residual variation suggests that sensors are varying more than usual but their relationships are preserved, indicating a process disturbance rather than sensor fault. High residual variation suggests that one or more sensors are behaving inconsistently with their normal relationships to other sensors, indicating sensor-specific issues. PCA effectively captures multivariate relationships and supports fault isolation but assumes linear relationships between sensors and requires representative training data from stable operation.
4.4. Autoencoder-Based Monitoring
Autoencoder neural networks provide a nonlinear extension of the dimensionality reduction concept underlying PCA[16]. The network is trained to compress multi-sensor data into a lower-dimensional representation and then reconstruct the original data. During training on stable data, the autoencoder learns the normal patterns and relationships among sensors by minimizing reconstruction error. During monitoring, the reconstruction error indicates how well current data matches learned patterns. When sensor behavior becomes abnormal, including periods of high variation, the autoencoder struggles to reconstruct the data accurately and elevated reconstruction error signals deviation from learned norms. Autoencoders capture nonlinear relationships that PCA cannot model, scale effectively to many sensors, and learn complex patterns automatically. However, they require substantial training data, provide less interpretable results than PCA, and require careful hyperparameter tuning.
4.5. Summary
Multi-sensor monitoring methods range from parallel univariate detection through linear PCA models to nonlinear autoencoders. While each approach offers anomaly detection capabilities, they present fundamental tradeoffs that limit practical deployment [7,9,11].
PCA-based methods assume linear relationships among sensors, limiting their effectiveness in industrial processes where nonlinear dynamics are common (e.g., temperature-pressure interactions, reaction kinetics). The principal components are fixed to training conditions, causing degraded performance when operating regimes shift. Additionally, PCA contribution plots used for fault isolation can produce misleading results when sensors are highly correlated.
Autoencoders address the nonlinearity limitation but introduce new challenges. The latent representations are inherently opaque, providing no interpretable explanation for why reconstruction error is elevated. Training requires substantial data to avoid overfitting, and the computational cost of hyperparameter tuning can be prohibitive for industrial deployment where models may need frequent retraining.
The digital twin framework based on Machine learning modeling offers a combination of capabilities that neither approach provides individually: it captures nonlinear sensor relationships while maintaining interpretability through feature importance measures, requires modest training data, and explicitly models the input-output structure of the physical process. This explicit structure supports root cause diagnosis when prediction errors increase, feature contributions indicate whether deviation originates from specific sensors or from process-wide input changes.
Table 3 summarizes these tradeoffs.
Table 3 compares methods across four criteria: ability to capture nonlinear sensor relationships, interpretability of anomaly explanations for operators, reliability with limited training data, and explicit modeling of input-output process structure. The input-output criterion is particularly significant while PCA and autoencoders model correlations among sensor outputs only, the digital twin explicitly predicts outputs from process inputs, enabling direct traceability from prediction errors to root causes.
Figure 4.
Landscape of high-variation detection methods in industrial sensor networks. Methods are positioned by detection paradigm and diagnostic capability, highlighting the unique diagnostic role of digital twin–based approaches.
Figure 4.
Landscape of high-variation detection methods in industrial sensor networks. Methods are positioned by detection paradigm and diagnostic capability, highlighting the unique diagnostic role of digital twin–based approaches.

5. Digital Twin Framework
A digital twin is a virtual replica of a physical system that estimates the system state given a set of input conditions[7]. For a given set of process inputs, the digital twin generates expected outputs. Deviations between the predicted outputs and actual sensor measurements indicate that the system behavior has changed. By setting control limits that accommodate model imprecision and sensor noise, the framework prevents unnecessary maintenance interventions triggered by random variations, alerting operators only when deviations exceed meaningful thresholds. The key diagnostic challenge is identifying the root cause of these deviations, whether they arise from sensor drift, process shifts, changes in operating regime, or other factors.
5.1. Framework Architecture
The proposed framework operates in two phases: a learning phase and a monitoring phase.
During the learning phase, a machine learning model is trained using baseline data collected when the system is operating under normal conditions. The model learns the relationships between system inputs and outputs, thereby establishing the expected system behavior under nominal operation.
During the monitoring phase, the trained model predicts expected outputs for incoming process inputs. Prediction errors are computed as
where denotes the actual measurement of sensor i at time t, and denotes the corresponding model prediction. When prediction errors exceed a baseline root mean squared error (RMSE) threshold, the framework flags a high-variation period requiring further root cause analysis.
Figure 5.
Digital twin framework. The model predicts system outputs from process inputs; deviations between predicted and measured values trigger root cause diagnosis.
Figure 5.
Digital twin framework. The model predicts system outputs from process inputs; deviations between predicted and measured values trigger root cause diagnosis.

5.2. Root Cause Diagnosis
The core diagnostic insight is obtained by analyzing which outputs exhibit elevated prediction errors:
- Single-output error elevation: If only one sensor exhibits increased prediction error while all others remain within baseline limits, the fault is localized to that sensor. Typical causes include sensor drift, degradation, or calibration errors.
- Correlated error elevation: If multiple sensors simultaneously exhibit elevated prediction errors, the deviation is attributed to upstream process changes or a shift in the input operating regime beyond the model’s training distribution.
This distinction guides corrective action. Sensor-specific faults typically require recalibration or replacement, whereas correlated deviations necessitate investigation of upstream process parameters or operating conditions.
5.3. Implementation
For a sensor network with n sensors, a Random Forest model is used to predict the measurement of sensor i based on the remaining sensors[6]:
where denotes the trained Random Forest model. Prediction performance is tracked using rolling RMSE computed over sliding time windows. A web-based visualization interface displays raw sensor measurements, prediction errors with threshold exceedances highlighted, and rolling RMSE with high-variation regions shaded.
6. Case Study
The proposed framework is evaluated using a cooking process dataset containing 1,787 samples with three operating scenarios: normal operation, a sensor drift affecting T2, and a process shift. The system is instrumented with three temperature sensors: T1 (pan temperature), T2 (food temperature), and T3 (wall temperature). The process inputs include heater power P, oil volume , food mass , stirring speed S, ambient temperature , and controller gain K.
A Random Forest digital twin is trained exclusively on data from the normal operation scenario and evaluated on all scenarios.
6.1. Baseline Operation (Normal Training)
During normal operation, the system inputs remain within a narrow operating range. Mean heater power is approximately 50 units, oil volume averages 35 ml, food mass is near 350 g, and stirring speed is approximately 69 rpm. Ambient temperature and controller gain remain stable at 24 °C and 1.0, respectively.
Under these conditions, the learned relationships among T1, T2, and T3 are consistent. Mean temperatures remain moderate (T1 ≈ 30°C, T2 ≈ 30°C, T3 ≈ 27°C), and prediction errors stay within the baseline RMSE threshold of approximately 1°C.
6.2. Scenario 1: Sensor Drift in T2
In the sensor fault scenario, the process inputs remain statistically indistinguishable from baseline operation. Heater power, oil volume, food mass, stirring speed, ambient temperature, and controller gain all remain within their normal operating ranges. This confirms that no physical process shift has occurred.
Despite stable inputs, the measured food temperature T2 increases to a mean of 36.4°C, while T1 and T3 remain unchanged relative to baseline. The digital twin continues to predict T2 based on the unchanged relationships learned during training, resulting in elevated prediction errors for T2 only.
Prediction errors for T2 increase sharply, while errors for T1 and T3 remain near zero. Rolling RMSE analysis confirms an isolated variance increase for T2, with no corresponding increase in the other sensors. This error structure indicates a localized sensor fault, consistent with sensor drift, miscalibration, or degraded thermal coupling between the sensor and the food.
6.3. Scenario 2: Process Shift
In contrast, the process shift introduces substantial and simultaneous changes across multiple inputs. Heater power nearly doubles from approximately 50 to 93 units. Oil volume drops sharply from 35 ml to approximately 6 ml, reducing thermal buffering. Food mass decreases from 350 g to 226 g, while stirring speed falls from 69 rpm to 25 rpm. Ambient temperature increases significantly to approximately 35°C, and controller gain rises to 1.55.
These changes fundamentally alter the system’s heat transfer dynamics. As a result, mean temperatures increase across all sensors: T1 rises to approximately 74°C, T2 to 51°C, and T3 to 65°C. Because these operating conditions lie outside the training distribution, the digital twin’s learned relationships no longer hold.
Prediction errors increase simultaneously for all three sensors, producing correlated error elevation rather than isolated deviations. Rolling RMSE values increase across all outputs, with variance rising into the 12–20°C range. This coordinated error pattern is characteristic of a process-level shift driven by input changes rather than sensor malfunction.
6.4. Diagnostic Implications
The case study demonstrates that the framework distinguishes sensor faults from process shifts by exploiting differences in error structure. When inputs remain stable, isolated prediction error elevation identifies sensor-level faults. When multiple inputs shift concurrently, correlated prediction errors across sensors reveal operation outside the trained regime.
Importantly, the framework does not rely on direct fault labels or physical models of heat transfer. Instead, it leverages deviations from learned multivariate relationships, enabling scalable and interpretable diagnostics in complex sensor networks.
Figure 6.
Prediction errors for T1, T2, and T3. Sensor fault (samples 750–1100) affects only T2, while input regime change (samples 1500+) affects all sensors.
Figure 6.
Prediction errors for T1, T2, and T3. Sensor fault (samples 750–1100) affects only T2, while input regime change (samples 1500+) affects all sensors.

Figure 7.
Residual variance under different scenarios. Isolated versus correlated error patterns distinguish sensor faults from process-level deviations.
Figure 7.
Residual variance under different scenarios. Isolated versus correlated error patterns distinguish sensor faults from process-level deviations.

7. Conclusions
This paper reviewed variance-change detection methods for industrial sensor networks, progressing from univariate statistical techniques through multivariate monitoring to a digital twin framework. Rolling variance, Shewhart charts, CUSUM, EWMA, change-point detection, and wavelet methods each offer distinct tradeoffs between detection speed, sensitivity, and computational requirements, but share a fundamental limitation: monitoring sensors independently without modeling inter-sensor relationships.
The conceptual link between high-variation moments and sensor drift was established, demonstrating that drift represents sustained high-variation behavior where changes in bias, variance, or sensitivity persist over time. This unified view shows that the same statistical foundations apply to both transient anomaly detection and long-term drift identification.
The proposed digital twin framework addresses the critical diagnostic gap in existing methods: distinguishing sensor faults from process disturbances. By learning inter-sensor relationships through Random Forest prediction and monitoring residual patterns, the framework enables targeted maintenance decisions. Isolated residual variance elevation indicates sensor-specific faults requiring calibration or replacement; correlated residual increases across multiple sensors indicate process regime changes warranting upstream investigation rather than sensor intervention.
Several limitations warrant consideration. The framework assumes stationary baseline relationships and requires retraining when process conditions permanently change. Detection performance depends on baseline period selection, and the RMSE threshold may require adjustment for sensors with non-Gaussian error distributions. Validation was limited to a laboratory thermal system; industrial-scale evaluation with hundreds of sensors remains necessary.
References
- Siemens. The True Cost of Downtime 2024," Senseye Predictive Maintenance Report, Siemens AG, Erlangen, Germany, 2024. Available online: https://www.siemens.com/senseye-predictive-maintenance.
- W. A. Shewhart, Economic Control of Quality of Manufactured Product; D. Van Nostrand Company: New York, NY, USA, 1931.
- Page, E. S. Continuous inspection schemes. Biometrika 1954, vol. 41(no. 1/2), 100–115. [Google Scholar] [CrossRef]
- Roberts, S. W. Control chart tests based on geometric moving averages. Technometrics 1959, vol. 1(no. 3), 239–250. [Google Scholar] [CrossRef]
- Basseville, M.; Nikiforov, I. V. Detection of Abrupt Changes: Theory and Application; Prentice Hall: Englewood Cliffs, NJ, USA, 1993. [Google Scholar]
- Breiman, L. Random forests. Mach. Learn. 2001, vol. 45(no. 1), 5–32. [Google Scholar] [CrossRef]
- Tao, F.; Qi, Q.; Wang, L.; Nee, A. Y. C. Digital twins and cyber-physical systems toward smart manufacturing and Industry 4.0: Correlation and comparison. Engineering 2019, vol. 5(no. 4), 653–661. [Google Scholar] [CrossRef]
- Montgomery, D. C. Introduction to Statistical Quality Control, 8th ed.; John Wiley & Sons: Hoboken, NJ, USA, 2019. [Google Scholar]
- Qin, S. J. Survey on data-driven industrial process monitoring and diagnosis. Annu. Rev. Control 2012, vol. 36(no. 2), 220–234. [Google Scholar] [CrossRef]
- Killick, R.; Fearnhead, P.; Eckley, I. A. Optimal detection of changepoints with a linear computational cost. J. Amer. Stat. Assoc. 2012, vol. 107(no. 500), 1590–1598. [Google Scholar] [CrossRef]
- Qin, S. J. Statistical process monitoring: basics and beyond. J. Chemom. 2003, vol. 17(no. 8-9), 480–502. [Google Scholar] [CrossRef]
- Engineering, Siege. Sensor Drift vs. Bad Equipment: A Diagnostic Playbook; 2024. [Google Scholar]
- Vista Projects, "Industrial Control System Troubleshooting Tools: Field Guide 2025.
- ARC Advisory Group. Sensor Data Integrity for Process Plants. [CrossRef]
- Minerva, R.; Lee, G. M.; Crespi, N. Digital twins for anomaly detection in the Industrial Internet of Things. IEEE Internet Things J. 2023, vol. 10(no. 10), 8440–8455. [Google Scholar]
- Nguyen, T. N.; Ponciroli, R.; Bruck, P.; Esselman, T. C.; Rigatti, J. A.; Vilim, R. B. A digital twin approach to system-level fault detection and diagnosis for improved equipment health monitoring. Ann. Nucl. Energy 2022, vol. 170, art. 109002. [Google Scholar]
- Tao, F.; Zhang, H.; Liu, A.; Nee, A. Y. C. Digital twin in industry: State-of-the-art. IEEE Trans. Ind. Informat. 2019, vol. 15(no. 4), 2405–2415. [Google Scholar] [CrossRef]
- Jackson, J. E.; Mudholkar, G. S. Control procedures for residuals associated with principal component analysis. Technometrics 1979, vol. 21(no. 3), 341–349. [Google Scholar] [CrossRef]
- MacGregor, J. F.; Kourti, T. Statistical process control of multivariate processes. Control Eng. Pract. 1995, vol. 3(no. 3), 403–414. [Google Scholar] [CrossRef]
- Kourti, T.; MacGregor, J. F. Process analysis, monitoring and diagnosis, using multivariate projection methods. Chemom. Intell. Lab. Syst. 1995, vol. 28(no. 1), 3–21. [Google Scholar] [CrossRef]
- Lucas, J. M.; Saccucci, M. S. Exponentially weighted moving average control schemes: Properties and enhancements. Technometrics 1990, vol. 32(no. 1), 1–12. [Google Scholar] [CrossRef]
- Carson, P. K.; Yeh, A. B. Exponentially weighted moving average (EWMA) control charts for monitoring multivariate autocorrelated processes. Ind. Eng. Chem. Res. 2008, vol. 47(no. 6), 2203–2211. [Google Scholar]
- Endress+Hauser. “Thermocouple operating principle and drift,” Technical Document, Endress+Hauser AG, Reinach, Switzerland. 2024. Available online: https://www.us.endress.com/en/support-overview/learning-center/tc-operating-principle-and-drift.
- Ashcroft Inc. “Why and how to perform a thermocouple calibration,” Application Note, Ashcroft Inc., Stratford, CT, USA, 2024. Available online: https://blog.ashcroft.com/why-how-to-perform-thermocouple-calibration.
- Emerson. Control valve management can pay off big. Pulp Pap. 2008, 28–31. Available online: https://www.emerson.com/documents/automation/article-control-valve-management-can-pay-off-big-ams-en-37566.pdf.
- Pathak, S.; Tahan, N. The future is now for predictive valve maintenance. Processing. Mar 2023. Available online: https://www.emersonautomationexperts.com/2023/valves-actuators-regulators/future-now-predictive-valve-maintenance/.
- ABB. “ABB survey reveals unplanned downtime costs $125,000 per hour,” ABB Ltd., Zurich, Switzerland, 2023. Available online: https://new.abb.com/news/detail/107660/abb-survey-reveals-unplanned-downtime-costs-125000-per-hour.
- Innovapptive. “Reduce unplanned downtime: A $20 billion challenge in the chemical industry,” Innovapptive Inc., Houston, TX, USA. 2024. Available online: https://www.innovapptive.com/blog/reduce-unplanned-downtime-chemical-industry.
- Siemens. “Predictive maintenance goes mainstream,” Siemens Blog, Siemens AG, Erlangen, Germany. Jul 2024. Available online: https://blog.siemens.com/2024/07/predictive-maintenance-goes-mainstream/.
- Saraf, M.; Rezvani Boroujeni, S.; Beaudry, J.; Abedi, H.; Bush, T. Quantifying label-induced bias in large language model self- and cross-evaluations. arXiv. 2025. Available online: https://arxiv.org/abs/2508.21164.
- Vaquet, V.; Artelt, A.; Brinkrolf, J.; Hammer, B. One or two things we know about concept drift—A survey on monitoring evolving environments. Front. Artif. Intell. 2024, vol. 7, art. 1330257. [Google Scholar]
- Lu, J.; Liu, A.; Dong, F.; Gu, F.; Gama, J.; Zhang, G. Learning under concept drift: A review. IEEE Trans. Knowl. Data Eng. 2019, vol. 31(no. 12), 2346–2363. [Google Scholar]
- Diamandis, P. H. “Metatrend #9: Trillion-sensor economy,” Diamandis.com. 2022. Available online: https://www.diamandis.com/blog/metatrend-9-trillion-sensor-economy.
- CFMS, “Industrial IoT: Data analytics and machine learning at the edge,” Centre for Modelling & Simulation, Bristol, U.K. 2025. Available online: https://cfms.org.uk/article/industrial-iot-distributing-big-data-analytics-and-machine-learning-at-the-edge/.
- Rezvani Boroujeni, S.; Abedi, H.; Bush, T. Enhancing glass defect detection with diffusion models: Addressing imbalanced datasets in manufacturing quality control. COMDEM vol. 2, 2025. [CrossRef]
- Mahjourian, N.; Nguyen, V. Sanitizing manufacturing dataset labels using vision-language models. arXiv 2025, arXiv:2506.23465. [Google Scholar]
Figure 1.
Conceptual illustration of high-variation ambiguity in industrial sensor networks. Similar increases in measurement variability may originate from sensor faults or process disturbances, motivating the need for diagnostic methods beyond univariate monitoring.
Figure 1.
Conceptual illustration of high-variation ambiguity in industrial sensor networks. Similar increases in measurement variability may originate from sensor faults or process disturbances, motivating the need for diagnostic methods beyond univariate monitoring.

Figure 2.
Diagnostic ambiguity of univariate variance-based monitoring. Identical increases in sensor variance may result from either sensor faults or process changes, which univariate methods cannot distinguish.
Figure 2.
Diagnostic ambiguity of univariate variance-based monitoring. Identical increases in sensor variance may result from either sensor faults or process changes, which univariate methods cannot distinguish.

Table 2.
Sensor Drift Mechanisms and Corresponding Detection Methods.
| Drift Mechanism | Observed Change | Detection Methods | Rationale |
|---|---|---|---|
| Bias (Offset) Drift | Mean shift | Rolling mean, EWMA, CUSUM | Offset errors directly shift the signal mean |
| Gain (Sensitivity) Drift | Scale change | Regression slope, ratio monitoring | Gain drift alters proportional relationships |
| Random Walk Drift | Increasing variance | Allan variance, variance trend analysis | Errors accumulate stochastically over time |
| Aging / Degradation Drift | Monotonic trend | Trend slope estimation | Physical wear produces gradual degradation |
| Noise-Induced Drift | Variance inflation | Variance control charts | Sensor degradation increases measurement noise |
| Calibration Loss | Global misalignment | Multivariate monitoring (PCA-based) | Offset and gain change simultaneously |
Table 3.
Comparison of Multi-Sensor Monitoring Methods.
| Method | Nonlinear | Interpretable | Small Data | Explicit I/O |
|---|---|---|---|---|
| PCA | No | Yes | Yes | No |
| Autoencoder | Yes | No | No | No |
| Digital Twin (RF) | Yes | Yes | Yes | Yes |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |